Skip to content
From Fire Safety Academy Wiki
Contents
  1. 1Definition and classification
  2. 2Natural and synthetic rubbers
  3. 3Combustion properties
    1. 3.1Heat of combustion
    2. 3.2Ignition and decomposition
    3. 3.3Oxygen index
  4. 4Fire behaviour
  5. 5Fire hazards in storage and use
    1. 5.1Stored rubber and tyres
    2. 5.2Cables, belts and linings
    3. 5.3Furniture and seating
  6. 6Fire testing and its limits
  7. 7Fire protection and firefighting
  8. 8See also
  9. 9Notes
  10. 10References

Rubber and elastomers are polymers that can be stretched a long way and spring back almost completely to their original shape at room temperature.[1] Natural rubber comes from the latex of the rubber tree, while synthetic elastomers such as styrene-butadiene rubber, neoprene and silicone rubber are made to imitate or surpass it.[2][3] Strictly speaking rubbers are not plastics, but the NFPA Fire Protection Handbook treats them together with plastics because their chemistry and fire behaviour overlap.[4]

As generally used, rubber is not easily ignited and does not burn unusually fast, but a rubber fire is known for its smell and its dense smoke.[5] Natural rubber and the other hydrocarbon rubbers release more than twice as much heat per kilogram as wood when they burn completely.[6] Large quantities therefore make severe fires. Stored tyres, conveyor belts, rubber-lined process equipment and rubber-jacketed cables are the typical problem cases.[5][7] Small flame tests say little about such fires.[8] Sprinkler protection for stored rubber is therefore based on commodity classes derived from intermediate-scale and full-scale fire tests.[9]

Definition and classification

The SFPE Handbook classifies polymers by their physical properties into elastomers, plastics and fibres. Elastomers, or rubbers, show a long-range extensibility that is almost completely reversible at room temperature. Plastics deform only partly reversibly, and fibres have a high tensile strength but stretch little.[1] Elastomers have elastic moduli of 105 to 106 N/m², against 107 to 108 N/m² for plastics and 109 to 1010 N/m² for fibres. An elastomer can be stretched by roughly 500 to 1,000 percent before it breaks, a plastic by 100 to 200 percent and a fibre by only 10 to 30 percent.[1]

Tree of polymers split into elastomers, thermosets and thermoplastics, with bars comparing stiffness and stretch of elastomers, plastics and fibres.
Elastomers are one of three polymer classes. They are far less stiff than plastics and fibres and have much greater elongation at break.

The NFPA Fire Protection Handbook divides polymers into three classes: elastomers, thermosets and thermoplastics. Its list of elastomers includes butadiene, butyl, fluoroelastomers, Hypalon, isoprene, natural rubber, neoprene, nitrile, polysulfide, silicones and urethane.[10] Elastomers are commonly called synthetic rubbers, and their fire characteristics are usually similar to those of natural rubber.[3]

Chemically, most general-purpose rubbers are polydienes. These are hydrocarbon polymers with one double bond in each repeating unit, and they are generally elastomeric.[1] Polyisoprene can be natural or synthetic, and polybutadiene is used mostly as a substitute for rubber. Other dienes appear in copolymers such as styrene-butadiene rubber (SBR) and ethylene-propylene-diene rubber (EPDM), valued for their abrasion resistance and impact strength.[1] Polychloroprene, better known as neoprene, is a chlorinated polydiene used for oil-resistant wire and cable materials and for resilient foams.[11]

The elastic state depends on temperature. Above its glass transition temperature a polymer becomes soft and rubbery, so a rubber band is meant to be used above that temperature.[11] The handbook tables give glass transition temperatures of about −70 °C for natural rubber, −52 °C for SBR, −40 °C for neoprene and −127 °C for silicone rubber.[12][13][14]

Natural and synthetic rubbers

Natural rubber is a constituent of latex, the white milky sap collected from the rubber tree. The processed rubber is used in sheets for shoe soles, extruded into inner tubes, or moulded under heat and pressure into tyres and hot-water bottles.[2] Liquid latex is coated on fabrics for waterproofing, mixed with cement and added to water-based paints. It is also expanded into foam latex, or foam rubber, whose density is set by the ratio of rubber to air and the size of the cavities.[2]

Vulcanisation is the curing process that cross-links rubber. Vulcanised rubber cannot be reshaped or remoulded when it is reheated.[2] In this respect it resembles a thermoset, a plastic that is substantially infusible and insoluble once it has been cured.[10] Prolonged vulcanisation produces hard rubber, known in England as ebonite or vulcanite, used for products such as battery cases and combs.[2]

The distinction between thermoplastics and thermosets matters for cables. The NRC fire dynamics tools list ethylene-propylene rubber, nitrile rubber, SBR, polybutadiene, neoprene and silicone rubber among the thermosetting cable insulations, which are usually qualified to IEEE 383.[15] Thermoplastic elastomers form a separate family: they are rubberlike, but unlike vulcanised rubbers they can be processed and recycled like thermoplastics.[16]

Synthetic rubbers imitate the elasticity of natural rubber and can also be vulcanised. Butadiene with styrene gives SBR, used extensively in automobile tyres, and butadiene with acrylonitrile gives nitrile rubber.[2] Butyl rubber is a copolymer of isobutylene and isoprene, and neoprene is a strong and durable synthetic made from chloroprene. Other types include ethylene-propylene rubber, polybutadiene and polyisoprene, the synthetic equivalent of natural rubber. Silicone rubber incorporates the inorganic element silicon. Some silicone formulations have been used as firestops in openings in fire walls, where their flexibility performs better than grout or plaster.[2]

The term synthetic foam rubber usually means a soft, flexible foam of the polyurethane type, based on either polyester or polyether.[2] In the Browns Ferry nuclear plant fire of 22 March 1975, electricians sealing air leaks in a cable spreading room with "spongy foam rubber" tested the seals with a candle. The candle ignited the foam, and the fire spread through the polyurethane into the reactor building.[17]

Combustion properties

Heat of combustion

The heat of combustion is the heat released when a fuel burns completely with oxygen and the products return to 25 °C. The gross, or upper, value is measured in an oxygen bomb calorimeter, in which the water formed ends up as liquid. The net, or lower, value leaves the water as vapour.[18] For simple fuels the two values are linked through the hydrogen content of the fuel. Each percent of hydrogen by mass lowers the net value by 0.2183 MJ/kg relative to the gross value:[18]

Δhcl=Δhcu−0.2183[%H]

Symbols in the heat of combustion relation
Symbol Description Unit
Δhcl net (lower) heat of combustion, water as vapour MJ/kg
Δhcu gross (upper) heat of combustion, water as liquid MJ/kg
[%H] hydrogen content of the fuel, percent by mass –

Worked example: natural rubber. Polyisoprene, the polymer in natural rubber, has the repeating unit C5H8 with a molecular weight of 68.12 g/mol and a gross heat of combustion of 44.90 MJ/kg.[12] With the handbook's atomic weight of 1.01 for hydrogen, its eight hydrogen atoms weigh 8 × 1.01 = 8.08 g per mole.[19] The hydrogen content is therefore 8.08 / 68.12 = 11.86 percent. The net heat of combustion then follows as:

Δhcl=44.90−0.2183×11.86=42.31 MJ/kg

This agrees within 0.01 MJ/kg with the net value of 42.32 MJ/kg in the handbook table.[12] The same calculation for SBR, C10H13 with a gross value of 44.15 MJ/kg, gives the tabulated 42.00 MJ/kg.[13]

Heats of combustion of rubbers compared with wood[6][13]
Material Gross (MJ/kg) Net (MJ/kg)
Natural rubber (polyisoprene) 44.9 42.3
Butyl rubber 45.8 –
Styrene-butadiene rubber (SBR) 44.15 42.00
Automobile tyre 32.6 –
Latex foam 33.9–40.6 –
Neoprene (gum) 24.3 –
Silicone rubber 15.5–16.8 –
Red oak 20.2 18.7

The table shows two groups. Hydrocarbon rubbers such as natural rubber, butyl rubber and SBR release about 44 to 46 MJ/kg, about 2.2 times the value for red oak.[6] Neoprene, which contains chlorine, and silicone rubber release much less, about 24 MJ/kg and 16 MJ/kg respectively.[6] The International Fire Engineering Guidelines give rounded values of 45 MJ/kg for isoprene rubber, 37 MJ/kg for foam rubber and 32 MJ/kg for tyres.[20] In real fires combustion is rarely complete, and some carbon goes to carbon monoxide instead of carbon dioxide.[18]

Bar chart: hydrocarbon rubbers about 44 to 46 MJ/kg, tyre 32.6, neoprene 24.3, red oak 20.2 and silicone rubber 15.5 to 16.8 MJ/kg.
Gross heat of combustion of rubbers compared with red oak, from oxygen bomb calorimeter data.

Ignition and decomposition

Like other solid fuels, rubbers burn through pyrolysis: heat breaks the large molecules into smaller ones and releases flammable gases, a step that needs no oxygen.[21] Polyisoprene decomposes by random scission of its chains, giving fragments of about eight to ten monomer units. In nitrogen, decomposition begins at 475 K (about 202 °C).[22] Polybutadiene is more stable. When heated in air at 525 K (about 252 °C), it forms a dark crust that keeps out further air.[22] Neoprene decomposes like polyvinyl chloride and gives off hydrogen chloride from about 615 K (about 342 °C).[22]

A compilation by Babrauskas groups ignition temperatures by type of solid. Elastomers ignite at 318 ± 42 °C with a pilot flame and at 353 ± 56 °C by autoignition. These central values are lower than the tabulated values for thermoplastics (369 °C and 457 °C) and thermosetting plastics (441 °C and 514 °C); the source does not define what its ± values represent.[23]

In pure oxygen the picture changes sharply. In tests to ASTM G72 in pure oxygen at 10.3 MPa, the autoignition temperature was 159 °C for EPDM and 173 °C for nitrile rubber. Butyl rubber reached 208 °C, neoprene 258 °C and silicone rubber 262 °C.[24] Fire resistance is therefore an important selection property for nonmetals in an oxygen-enriched atmosphere, where they are also sensitive to ageing.[25]

Ignition under radiant heat is described by the critical heat flux for ignition and the thermal response parameter (TRP), which links the time to ignition to the net heat flux. Measured in the fire propagation apparatus, isoprene has a critical heat flux of 10 kW/m² and a TRP of 174 kW·s1/2/m². Latex foams have 16 kW/m² and 113 to 172 kW·s1/2/m².[26] Conveyor belts of SBR have 10 to 15 kW/m² and 336 to 429 kW·s1/2/m². Belts of chloroprene rubber need 20 kW/m², with a TRP of 760 kW·s1/2/m², and are much harder to ignite.[26]

Oxygen index

The oxygen index is the minimum oxygen concentration in a flowing mixture of oxygen and nitrogen that supports candle-like downward burning of a small sample, measured to ASTM D2863. Normal air contains about 20.9 percent oxygen. In principle a material with an oxygen index above 25 percent should therefore burn only under extreme conditions, but in practice the test mainly shows how easily a burning material is extinguished.[27] In the handbook table, SBR foam has an oxygen index of 16.9, natural rubber foam 17.2, polybutadiene 18.3 and polyisoprene rubber 18.5. Chlorinated and silicon-containing rubbers score higher: neoprene rubber 26.3 to 40.0 and silicone rubber 30.0. The values apply to materials without added fire retardants, which can raise the oxygen index substantially.[28]

Bar chart of oxygen index: SBR, natural rubber and polybutadiene 16.9 to 18.5; red oak 23.0; silicone rubber 30.0; neoprene 26.3 to 40.0.
Oxygen index of rubbers without fire retardants (ASTM D2863), with the oxygen content of air (20.9 percent) and the 25 percent level for comparison.

Fire behaviour

Burning rubber is notable for its smell and dense smoke.[5] The soot yield, the fraction of the fuel that leaves the fire as soot, depends on the fuel and on the combustion conditions. Plastics produce relatively much soot, wood much less.[29] Pre-flashover soot yields are 0.015 kg/kg for wood, 0.14 kg/kg for PVC and 0.23 kg/kg for polyurethane.[29] For silicone rubber, bench-scale tests in well-ventilated conditions gave a soot yield of 0.078 kg/kg and a chemical heat of combustion of 10.9 MJ/kg.[30][31] In small-scale flaming tests, latex gave a mass optical density of 0.65 m²/g and neoprene 0.40 m²/g, against 0.33 m²/g for polyurethane and 0.17 m²/g for cotton.[32]

In the 2008 handbook’s account of commercial plastics, carbon monoxide from incomplete combustion is the leading toxic fire gas.[33] Chlorine-containing neoprene gives off hydrogen chloride as it decomposes.[22] Rubbery caulking materials based on ethylene sulfide release sulfur dioxide. These irritating gases can also corrode metals and electrical equipment.[33]

The slow deterioration of rubber and plastics over time is often the result of slow oxidation.[34] The handbook rates foam rubber in consumer products as having a moderate tendency to self-heating. It may heat spontaneously after forced drying in home or commercial dryers or after contact with heating pads, whereas natural drying does not cause it.[35] Scrap rubber and buffings also have a moderate tendency. Sheets and slabs are comparatively safe unless they are loaded or stored before cooling thoroughly.[36]

Fine rubber dust can also explode. In the handbook's dust explosion test data, rubber dust with a particle size of 34 μm reached a maximum explosion pressure of 7.4 bar. Its KSt value was 106 bar·m/s.[37] Rubber processing dust is therefore a dust explosion hazard.

Fire hazards in storage and use

Stored rubber and tyres

Plastics, a group that in NFPA sprinkler practice includes the rubbers, can produce about 1.5 to 3 times as much heat per unit weight as wood or paper and can burn much faster.[38] In the United States, NFPA standards, as described in the 2008 edition of the Fire Protection Handbook, place plastics in Groups A, B and C for sprinkler design. The list covers unmodified materials, because fire-retardant additives inhibit ignition but usually leave the heat release unchanged once burning starts.[38] Group A plastics, the most severe group, include butyl rubber, EPDM, nitrile rubber, polybutadiene, polyester elastomer, SBR and expanded natural rubber. Chloroprene rubber, silicone rubber and unexpanded natural rubber are in Group B, which behaves similarly to a Class IV commodity.[38][39] In this commodity classification, natural rubber thus moves from Group B to Group A when it is expanded.

Bulk storage of rubber items, particularly tyres, gives hot, very smoky fires that are difficult to control. Water applied to the surface may be only marginally effective, because the fire can burrow into the material.[5] In the United States, NFPA 13, as described in the handbook, requires special sprinkler protection where such storage is more than 1.52 m (5 ft) high.[5] Unpackaged tyres form their own horizontal and vertical flues, and the inside of a tyre carcass can flame beyond the reach of sprinkler water.[40] These problems, and the role of high-expansion foam, are treated in Rubber tyre storage. A wooden pallet of bagged SBR pellets reached a heat release rate close to 7 MW before it had to be extinguished, without reaching its peak.[41]

The International Fire Engineering Guidelines reproduce Swiss survey data from 1967 to 1969 on fire load density. They give 600 MJ/m² for rubber goods manufacture and rubber processing, and 800 MJ/m² for a rubber goods store.[42] Storage in both manufacturing categories carries 5,000 MJ/m² per metre of storage height.[42][43] Storage stacked 3 m high in these categories thus has 15,000 MJ/m².

Cables, belts and linings

Rubber or plastic jacketing on grouped electrical cables has provided the fuel for cable fires in the electrical and communications industries. Butyl/neoprene and neoprene rubber insulation tend to burn readily and fail small-scale cable tests of the IEEE 383 type.[5] Rubber conveyor belts, especially in coal handling, continue to be a major cause of fire loss in the mining industry.[7] Of 24 conveyor belt fires in the coal industry from 1978 to 1999, six began with an open flame, five with spontaneous ignition and five with friction.[7] Belts are made of solid woven or layered elastomers such as SBR, chloroprene rubber or PVC, reinforced with fibres such as nylon.[44] Their protection is covered in Conveyor fire protection.

Tewarson ranks such belts with the fire propagation index (FPI). This index combines the ease of ignition, expressed by the TRP, with the chemical heat release rate per unit width during upward burning in air enriched to an oxygen mass fraction of 0.40. A high heat release and a low TRP give a high index and fast fire spread.[45] The constants 1000 and 0.42 combine to about 750:[45]

FPI=1000(0.42Q˙'ch)1/3TRP=750(Q˙'ch)1/3TRP

Symbols in the fire propagation index
Symbol Description Unit
FPI fire propagation index (m/s1/2)/(kW/m)2/3
Q˙'ch chemical heat release rate per unit width of the sample during upward propagation kW/m
TRP thermal response parameter kW·s1/2/m²

Materials with an FPI below 7 show no propagation beyond the ignition zone. Values of 7 to 10 give decelerating propagation, 10 to 20 slow, non-accelerating propagation, and values above 20 accelerating propagation.[45] For conveyor belts about 600 mm long and 100 mm wide, the non-propagating condition is FPI ≤ 7.[44]

Worked example: two conveyor belts. In large-scale tunnel tests, fire did not spread over a chloroprene rubber belt but did spread over a belt of chloroprene and SBR. For the chloroprene belt, small-scale tests gave a TRP of 760 kW·s1/2/m² and a peak Q˙'ch of 114 kW/m. The mixed belt gave 400 kW·s1/2/m² and 73 kW/m.[44] The equation above then gives:

FPICR=750×1141/3760=750×4.85760≈4.8

FPICR/SBR=750×731/3400=750×4.18400≈7.8

Tewarson rounds these to 5 and 8. In this example, the chloroprene belt stays below the limit of 7 and the mixed belt exceeds it.[44] Yet Table 3-4.4 labels the chloroprene belt as propagating, contradicting the example’s reported large-scale outcome.[46] The higher TRP of the chloroprene belt determines its lower calculated FPI despite its greater heat release.

Two columns: chloroprene belt FPI 4.8, below the limit of 7, and chloroprene/SBR belt FPI 7.8, above it, on four propagation bands.
Calculated fire propagation index of two belts in Tewarson’s Example 5. Its reported chloroprene test outcome conflicts with Table 3-4.4.

Rubber linings are common in mineral processing plants, inside vessels, piping, pumps and cyclones, where they resist acid and abrasion. They create a high hidden combustible load in an otherwise noncombustible facility.[47] Fires in such linings are hard to reach for manual firefighting, sprinklers can rarely be arranged to act on them, and the fire spreads inside while releasing dense black smoke.[47] Hot work on dry rubber-lined piping or tanks can ignite the lining and spread fire unhindered from vessel to vessel through lined pipes.[7] Ceramics and special alloys can replace rubber linings if this is decided early in the design stage.[48]

Furniture and seating

Neoprene foam is often used in rail-car seating. It shows excellent fire performance but is usually too costly and too dense for other applications.[49] In tests on chair mock-ups, flames still spread quickly over thermoplastic cover fabrics even when the neoprene foam beneath did not significantly flame.[50] The cover fabric, not the padding alone, governed flame spread over the upholstered item.

Fire testing and its limits

The form of a product, whether solid, film, foam or powder, strongly affects its fire properties, so fire tests should reflect the end-use configuration.[3] Small-scale methods such as the oxygen index test and the UL 94 flammability test are now used mainly for product development and production control. With their small, low-intensity ignition sources, they are unsuitable for judging behaviour in a room fire.[8]

Silicone rubbers can be formulated to keep combustibility to a minimum under ordinary conditions, but not all of them have that quality. One silicone rubber failed the requirement of no flashover in a quarter-scale room fire test at the National Bureau of Standards.[5] Apparatus that measure heat release and smoke development at varying radiant heat fluxes, such as the cone calorimeter and the fire propagation apparatus, give more realistic assessments than the older methods of fire testing.[8][51]

Fire protection and firefighting

Plastics other than cellulose nitrate are classified as ordinary combustibles, and rubber fires are fought with the methods used for wood and other Class A fires.[33] The NRC fire dynamics tools also name rubber among the ordinary combustibles of Class A.[52] Water from automatic sprinklers or hose spray nozzles can be used for fire control, but stored rubber is a harder case.[33] Water may fail to reach a fire that has burrowed into a pile or into the inside of tyres.[5][40] High sprinkler densities are needed for tyre storage, and high-expansion foam combined with sprinklers has proved very effective.[40]

Prevention relies largely on less hazardous materials. In mining, less hazardous conveyor belting and hydraulic hoses are required underground under certain conditions, and fire-retardant belting is preferred in processing buildings. Slippage and sequence switches on conveyors prevent friction heating.[48] Hot work is a particular hazard near rubber-lined equipment, because hot slag falling into an open tank can ignite the lining.[7]

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 1.4 Beyler and Hirschler (2002), p. 1-111.
  2. ↑ 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 Benedetti and Colonna (2008), p. 6-223.
  3. ↑ 3.0 3.1 3.2 Benedetti and Colonna (2008), p. 6-211.
  4. ↑ Benedetti and Colonna (2008), p. 6-209.
  5. ↑ 5.0 5.1 5.2 5.3 5.4 5.5 5.6 5.7 Benedetti and Colonna (2008), p. 6-226.
  6. ↑ 6.0 6.1 6.2 6.3 Babrauskas (2008a), p. 6-280.
  7. ↑ 7.0 7.1 7.2 7.3 7.4 L. J. Moore (2008), p. 9-215.
  8. ↑ 8.0 8.1 8.2 Benedetti and Colonna (2008), p. 6-227.
  9. ↑ Golinveaux (2008), p. 16-72.
  10. ↑ 10.0 10.1 Benedetti and Colonna (2008), p. 6-210.
  11. ↑ 11.0 11.1 Beyler and Hirschler (2002), p. 1-112.
  12. ↑ 12.0 12.1 12.2 Babrauskas (2008a), p. 6-277.
  13. ↑ 13.0 13.1 13.2 Babrauskas (2008a), p. 6-279.
  14. ↑ Babrauskas (2008a), p. 6-275.
  15. ↑ Iqbal and Salley (2004), p. A-8.
  16. ↑ Ouellette (2008), p. 9-57.
  17. ↑ Iqbal and Salley (2004), p. H-8.
  18. ↑ 18.0 18.1 18.2 Babrauskas (2008a), p. 6-269.
  19. ↑ Drysdale (2008), p. 2-15.
  20. ↑ National Research Council of Canada et al. (2005), p. 3.3-6.
  21. ↑ Van Rossum (2027), §3.1.
  22. ↑ 22.0 22.1 22.2 22.3 Beyler and Hirschler (2002), p. 1-128.
  23. ↑ Babrauskas (2003), as cited in National Research Council of Canada et al. (2005), p. 3.3-4.
  24. ↑ Hshieh et al. (1996), as cited in Rosales and Stoltzfus (2008), p. 9-231.
  25. ↑ Rosales and Stoltzfus (2008), p. 9-230.
  26. ↑ 26.0 26.1 Tewarson (2002), pp. 3-87–3-88.
  27. ↑ Hirschler (2008a), p. 6-42.
  28. ↑ Babrauskas (2008a), p. 6-282.
  29. ↑ 29.0 29.1 Van Rossum (2027), §6.2.
  30. ↑ Tewarson (2002), p. 3-112.
  31. ↑ Australian Building Codes Board (2020a), Data Sheet B2, p. 20.
  32. ↑ Mulholland (2002), p. 2-264.
  33. ↑ 33.0 33.1 33.2 33.3 Benedetti and Colonna (2008), p. 6-230.
  34. ↑ Benedetti (2008), p. 6-5.
  35. ↑ Babrauskas (2008a), p. 6-289.
  36. ↑ Babrauskas (2008a), p. 6-292.
  37. ↑ Schwab (2008c), p. 6-146.
  38. ↑ 38.0 38.1 38.2 Golinveaux (2008), p. 16-73.
  39. ↑ Golinveaux (2008), p. 16-74.
  40. ↑ 40.0 40.1 40.2 Golinveaux (2008), pp. 16-86–16-87.
  41. ↑ Babrauskas (2002b), pp. 3-16–3-17.
  42. ↑ 42.0 42.1 National Research Council of Canada et al. (2005), p. 3.4-6.
  43. ↑ National Research Council of Canada et al. (2005), p. 3.4-2.
  44. ↑ 44.0 44.1 44.2 44.3 Tewarson (2002), p. 3-94.
  45. ↑ 45.0 45.1 45.2 Tewarson (2002), p. 3-92.
  46. ↑ Tewarson (2002), p. 3-93.
  47. ↑ 47.0 47.1 L. J. Moore (2008), p. 9-214.
  48. ↑ 48.0 48.1 L. J. Moore (2008), p. 9-216.
  49. ↑ Babrauskas (2008b), p. 6-125.
  50. ↑ Babrauskas (2008b), p. 6-119.
  51. ↑ Benedetti and Colonna (2008), p. 6-228.
  52. ↑ Iqbal and Salley (2004), p. B-13.

References

  • Australian Building Codes Board. (2020a). Data sheets: Fire Safety Verification Method (Handbook annex, Print version 1.1).
  • Babrauskas, V. (2002b). Heat release rates. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-1–3-37). National Fire Protection Association; Society of Fire Protection Engineers.
  • Babrauskas, V. (2008a). Tables and charts. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-269–6-294). National Fire Protection Association.
  • Babrauskas, V. (2008b). Upholstered furniture and mattresses. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-103–6-128). National Fire Protection Association.
  • Benedetti, R. P. (2008). Fire hazards of materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-3–6-9). National Fire Protection Association.
  • Benedetti, R. P., & Colonna, G. R. (2008). Polymeric materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-209–6-231). National Fire Protection Association.
  • Beyler, C. L., & Hirschler, M. M. (2002). Thermal decomposition of polymers. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 1-110–1-131). National Fire Protection Association; Society of Fire Protection Engineers.
  • Drysdale, D. (2008). Physics and chemistry of fire. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-3–2-20). National Fire Protection Association.
  • Golinveaux, J. E. (2008). Sprinkler systems for storage facilities. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 16-71–16-89). National Fire Protection Association.
  • Hirschler, M. M. (2008a). Concepts and protocols of fire testing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-35–6-60). National Fire Protection Association.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Moore, L. J. (2008). Mining and mineral processing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-203–9-223). National Fire Protection Association.
  • Mulholland, G. W. (2002). Smoke production and properties. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-258–2-268). National Fire Protection Association; Society of Fire Protection Engineers.
  • National Research Council of Canada, International Code Council, Department of Building and Housing, & Australian Building Codes Board. (2005). International fire engineering guidelines (2005 ed.). Australian Building Codes Board.
  • Ouellette, G. (2008). Plastics industry and related process hazards. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-53–9-65). National Fire Protection Association.
  • Rosales, K., & Stoltzfus, J. M. (2008). Oxygen-Enriched atmospheres. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-225–9-243). National Fire Protection Association.
  • Schwab, R. F. (2008c). Dusts. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-141–6-152). National Fire Protection Association.
  • Tewarson, A. (2002). Generation of heat and chemical compounds in fires. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-82–3-161). National Fire Protection Association; Society of Fire Protection Engineers.
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.