An oxygen-enriched atmosphere (OEA) is an atmosphere in which the concentration of oxygen exceeds 21 percent by volume, or the partial pressure of oxygen exceeds 160 torr (21.3 kPa), or both.[1] Normal air contains about 21 percent oxygen, so any added oxygen or any compression of air creates such an atmosphere.[2][3] Oxygen-enriched atmospheres are used on purpose in medicine, industrial processes, caisson work, deep-sea exploration, spaceflight and aviation, and they can form by accident wherever oxygen or compressed air is transported, stored or used.[1] In most of them materials ignite more easily and burn faster, and items normally considered noncombustible in air can burn very well.[4][5][6]

The degree of hazard depends on the oxygen concentration, the diluent gas and the total pressure, so not every oxygen-enriched atmosphere is more dangerous than air.[7] The NFPA Fire Protection Handbook (2008) describes US practice for managing the hazard. It relies on an oxygen compatibility assessment, careful design and cleaning, and extinguishing systems that act within a second.[8][6][9]

Definition and thresholds

Air contains 78 percent nitrogen, 21 percent oxygen and 1 percent other gases by volume.[2] Oxygen is one side of the fire triangle, together with fuel and temperature, and a fire stops spreading and may go out when the oxygen level falls far enough.[2] Oxygen itself is clear, odourless, tasteless and colourless, and it is the most common oxidising agent in the atmosphere.[1] It reacts with many materials in highly exothermic reactions, which release heat.[1] Oxygen does not burn, but most fires burn more rapidly when the oxygen concentration is increased.[10]

The handbook definition has two separate criteria: a concentration above 21 percent by volume, or an oxygen partial pressure above 160 torr (21.3 kPa).[1] Either criterion is sufficient. The partial pressure criterion means that compressed air is an oxygen-enriched atmosphere although its composition is unchanged. Allen (2008) states this directly for medical air: air compressed above ambient pressure, that is above 14.7 psi (101 kPa), constitutes an oxygen-enriched atmosphere.[3] In such air the ease of ignition is increased and the flame spread rate is greater than in air at ambient pressure.[3]

The same thresholds appear elsewhere in the handbook. Catalytic sensors for flammable gas detection sit inside a flame arrester that suits conventional gas-air mixtures. Where the atmosphere contains more than 21 percent oxygen by volume, or the oxygen partial pressure exceeds 21.27 kPa (160 mm Hg), special arresters may be necessary.[11]

The definition marks a boundary; it is not a measure of hazard. Rosales and Stoltzfus (2008) note that some oxygen-enriched atmospheres support combustion much like ambient air, and some cannot support the combustion of normally flammable materials at all.[7] A mixture of 4 percent oxygen in nitrogen or helium at 12 atm (1216 kPa) will not support the combustion of paper. Its oxygen partial pressure is nevertheless 365 torr (48.7 kPa).[7] Most oxygen-enriched atmospheres met in practice do accelerate combustion and ease ignition, and so increase the fire hazard.[7]

Partial pressure and concentration

The partial pressure of a gas is the share of the total pressure that the gas contributes, and the partial pressures of all gases in a mixture add up to the total pressure.[12] Table 9.17.1 of the handbook, taken from NFPA 53 (2004 edition), shows that the oxygen partial pressure of air rises in proportion to the total pressure. It is 160 torr at 1 atm, 320 torr at 2 atm and 800 torr at 5 atm.[7] The relation behind the table multiplies the oxygen volume fraction by the total absolute pressure.

Line chart of oxygen partial pressure of air rising with total pressure, crossing the 160 torr threshold at 1 atm
Oxygen partial pressure of air and the oxygen fraction that gives 160 torr, at total pressures from 1/5 to 5 atm.

Rearranged, it gives the highest oxygen fraction that keeps the partial pressure at the sea-level value of air. The relation describes only how much oxygen is present. It says nothing on its own about flammability, because the diluent gas and the total pressure also matter.[7]

pO2=xO2ptot xO2,max=prefptot

Symbol Description Unit
pO2 partial pressure of oxygen kPa (or torr)
xO2 volume (mole) fraction of oxygen in the gas mixture –
ptot total absolute pressure of the atmosphere kPa (or torr)
pref reference oxygen partial pressure, 21.3 kPa (160 torr) kPa (or torr)
xO2,max oxygen fraction that gives pref at ptot –

Worked example 1: compressed air. A caisson or chamber is held at 3 atm absolute, which is 304.1 kPa, with ordinary air containing 20.9 percent oxygen.[7] The oxygen partial pressure is 0.209 × 304.1 kPa = 63.5 kPa, or about 477 torr. Table 9.17.1 rounds this to 480 torr, three times the sea-level value, and marks it as an oxygen-enriched atmosphere.[7] To keep the partial pressure at 160 torr at this total pressure, the oxygen fraction would have to fall to 160/2280 = 7.0 percent; the table lists 6.9 percent.[7]

Worked example 2: reduced pressure. The space station was designed for 30 percent oxygen at 10.2 psia (70.3 kPa).[7] The partial pressure is 0.30 × 70.3 kPa = 21.1 kPa (158 torr), just below 160 torr. The atmosphere is still oxygen-enriched, because 30 percent exceeds 21 percent.

Worked example 3: high pressure, low concentration. For the 4 percent mixture at 12 atm, the partial pressure is 0.04 × 1216 kPa = 48.6 kPa, or 365 torr. This is more than twice the 160 torr threshold, so the mixture meets the definition, yet it does not support the burning of paper.[7]

Where oxygen-enriched atmospheres occur

Rosales and Stoltzfus (2008) list many circumstances in which fires and explosions can occur in intentional or unintentional oxygen-enriched atmospheres.[7] They include the transport, transfer and production of oxygen, such as truck delivery of liquid oxygen, leaks or venting from storage, and the recharging of containers. Medical uses include inhalation therapy, life-support systems, resuscitation, hyperbaric chambers and anaesthesia. Industrial uses include petrochemical processing, steel making, mining, wastewater treatment, microchip manufacturing, pulp bleaching, caisson work and underwater tunnelling.[7] In aerospace, the NASA space shuttle orbiter used gaseous oxygen at concentrations up to 25.9 percent under normal conditions.[7]

Many oxygen-enriched atmospheres are inadvertent. They can result from poor design, malfunction or misuse of oxygen storage and dispensing equipment, or from the substitution of oxygen for air or nitrogen.[7] Oxygen is more soluble in aircraft fuel than nitrogen, and it can come out of solution during flight as the pressure falls, creating a hazardous enriched atmosphere.[7] Nitrous oxide, used as a mild anaesthetic and as an aerosol propellant, can also produce an oxygen-enriched atmosphere.[7][4] A release of liquid hydrogen can condense oxygen out of the surrounding air, which adds the hazard of an oxygen-enriched environment.[13]

Misuse of oxygen in hot work is a further cause. Manz and Blank (2008) state that oxygen must never be used to cool a worker, to ventilate a confined space or to dust off clothing.[14] Tests and experience have shown that oxygen-saturated clothing, or clothing in an oxygen-enriched atmosphere, will burn in a flash, with very serious and sometimes fatal results.[14] Some industrial processes require people to work in atmospheres enriched above the normal oxygen content, and these present a high fire hazard to the clothing of the workers.[15]

Effect on ignition and combustion

Raising the oxygen concentration lowers the energy needed for ignition and raises the flame spread rate.[4] At a fixed volume percentage of oxygen, the minimum ignition energy varies inversely with the square of the pressure, and below a certain minimum pressure ignition does not occur.[4] The Society of Fire Protection Engineers (SFPE) handbook gives ignition energies of a few tenths of a millijoule for near-stoichiometric mixtures in air, and as low as a few thousandths of a millijoule in oxygen.[16] Kanury (2002b) adds that in pure oxygen quenching distances are smaller, and flame temperatures and flame speeds are larger.[17]

Table 9.17.3 of the handbook, based on NFPA 53 (2004 edition), compares gases and liquids in air and in oxygen at atmospheric pressure.[18] For methane the minimum ignition energy falls from 0.300 mJ in air to 0.0030 mJ in oxygen, a factor of 100.[19] For hydrogen it falls from 0.017 mJ to 0.0012 mJ, and the minimum ignition temperature falls from 520 °C to 400 °C.[18] The autoignition temperature of a material also drops rapidly as pressure rises, up to about 1000 psi (7 MPa), and then stays almost constant.[18]

The flammable range widens mainly at its upper end. The lower flammable limits of most hydrocarbon fuels, anaesthetics and solvents lie between 1 and 5 percent by volume in air or oxygen at 1 atm.[20] The lower limits in oxygen differ little from those in air, but the upper limits in oxygen are much higher, often about 50 percent.[18] Methane is flammable between 5.0 and 15.0 percent in air and between 5.1 and 61.0 percent in oxygen. For hydrogen the ranges are 4.0 to 75.0 percent and 4.0 to 95.0 percent.[19][18] Flashpoints in oxygen are slightly lower than in air, and higher pressure generally broadens the flammable range.[20]

Range bars of methane and hydrogen flammable limits in air and oxygen, plus bars of minimum ignition energy on a log scale
Flammable ranges and minimum ignition energies of methane and hydrogen in air and in oxygen at atmospheric pressure.

Solids follow the same pattern. Kanury (2002a) describes experiments in which cellulose was ignited in oxygen-enriched air at high pressure. The time to ignition fell sharply as the oxygen fraction or the pressure rose, and so did the surface temperature at ignition.[21] Hot plate tests summarised in the handbook show the same trend for cotton sheeting. Its ignition temperature at 1 atm was 465 °C in air, 390 °C in 42 percent oxygen and 360 °C in pure oxygen; at 4 atm the values were 365, 340 and 325 °C.[22]

Line chart of cotton sheeting ignition temperature falling with pressure for air, 42 percent oxygen and pure oxygen
Minimum hot plate ignition temperature of cotton sheeting in air, 42 % oxygen and 100 % oxygen at total pressures of 1 to 4 atm.

Spark ignition is affected even more. Textile fabrics can be ignited by a spark of 2.3 J in 100 percent oxygen, whereas in normal air at least 193 J is required.[18] Single fibres of organic materials, such as lint, cotton tufts and fluffy fabrics, may be ignited by a 0.02 J static spark in 100 percent oxygen but not in 64 percent oxygen.[18]

Flames are also hotter. Drysdale (2002) shows that propane burning in air will not exceed about 2000 K, while in pure oxygen, without nitrogen as a heat sink, dissociation limits it to about 3500 K.[23] The NUREG-1805 fire dynamics tools give a similar example: the hottest part of a Bunsen flame reaches about 1600 °C, an oxy-acetylene cutting torch about 3500 °C. Any increase in the oxygen supply, including an oxygen-enriched atmosphere, gives higher temperatures than combustion in normal air.[24]

Flame spread and material flammability

Rosales and Stoltzfus (2008) call the rate of flame spread the single most important property for the development of a fire hazard in an oxygen-enriched atmosphere.[25] Flame spread is much faster upward, because of buoyant convection, than horizontally or downward. It increases with the oxygen concentration at constant pressure and with the total pressure at a constant oxygen percentage.[25] Raising the oxygen partial pressure can move a material from the nonflammable to the flammable category.[18] Almost all polymers are flammable in 100 percent oxygen at atmospheric pressure.[26]

The oxygen index test is commonly used to rank materials for oxygen-enriched atmospheres.[27] In the SFPE handbook, Beyler (2002b) defines the oxygen index as the oxygen mole fraction of the oxidant stream at the flammability limit of a diffusion flame.[28] Many common materials ignite and burn in as little as 16 percent oxygen, while fluorocarbon plastics did not propagate flame even in 100 percent oxygen.[27]

Examples from Table 9.17.7 are polyacetal at 16, Plexiglas at 18.5, nylon 66 at 30.5 and polyvinylidene fluoride (Kynar) at 39.[29] Fluorocarbon FEP tubing reached 77 and fluorocarbon PFA 100, while fluorocarbon TFE did not propagate.[29] Beyler and Hirschler (2002) note a lack of confidence today in the limiting oxygen index technique as a measure of flammability.[30] Rosales and Stoltzfus (2008) add that absolute flammability thresholds are difficult to establish without testing the actual configuration of use.[26]

Flame-retardant additives such as halogens, borax, phosphates and metal oxides remain effective for many materials up to about 30 to 35 percent oxygen.[18] Treated materials may burn differently and give off corrosive or toxic vapours.[18] Nomex fibre kept its flame-retardant behaviour in air at four atmospheres (59 psig or 400 kPa). At that pressure and at oxygen concentrations of 40 percent or more, it supported combustion, though at a much slower rate than untreated fabrics.[15] For electrical wiring, PTFE insulation is the most resistant to ignition and flame in these atmospheres; Kapton resists ignition but is susceptible to arc tracking.[25]

All metals, with the possible exception of gold and platinum, can be expected to ignite in oxygen at some elevated temperature and pressure.[31] Titanium, magnesium and lithium are the most ignitable common metals, and nickel, copper and cobalt the least.[31] A type 316 stainless steel rod of 3.3 mm diameter burns upward in oxygen at 7 MPa (1000 psi) at about 11 mm/s. A 6061 aluminium rod of the same size burns at about 64 mm/s.[31]

Flammability limits as such do not exist for most structural alloys, because they burn mostly in the liquid phase.[31] Two practical measures rank them instead: the threshold pressure, which is the minimum oxygen pressure that supports combustion of a standard sample, and the oxygen index at a given pressure.[8] In the threshold tests of Table 9.17.10, rods of commercially pure silver, Monel 400 and brass 360 did not sustain combustion even at the highest pressure tested, 68.9 MPa (10,000 psi).[32]

Health care applications

Oxygen-enriched atmospheres are encountered during practically every inhalation anaesthetic and respiratory therapy procedure, and nitrous oxide is also considered one.[33] A medical gas system pipes gases such as oxygen, nitrous oxide and medical air from remote sources to the bedside.[5] Because such atmospheres are present in many therapeutic applications, fire and explosion prevention in health care facilities must take into account the control of fuels and ignition sources.[34] In these atmospheres combustible substances have a lower ignition temperature and burn more rapidly than in air, and flame spread can be extremely rapid if bedding or clothing is saturated with oxygen.[35] Potential ignition sources include electrosurgical units, lasers, fibreoptic light sources, adiabatic compression of gases, sparks, static electricity and defibrillators.[33]

Helium-oxygen mixtures, used for some respiratory conditions and for laser airway surgery, should be treated as oxygen-enriched atmospheres.[3] Helium delays ignition because of its high thermal conductivity, but once ignition occurs the flame spreads faster and burns hotter than in a nitrogen mixture.[3] In hyperbaric chambers the oxygen percentage is usually raised on purpose, and the elevated pressure increases the oxygen partial pressure further.[33][36] In the United States, safety standards for hyperbaric chambers are set out in NFPA 99, Standard for Health Care Facilities, as described in the 2008 handbook.[36]

Pressure surges are a specific risk in oxygen equipment. A cylinder valve that is opened quickly can cause dangerous adiabatic compression heating of the oxidising gas downstream. Allen (2008) therefore recommends opening cylinder valves slowly, so that the metal of the regulator can dissipate the heat.[33] Aluminium is particularly susceptible to ignition under oxygen enrichment and high pressure. It has been held responsible for a number of fires in aluminium cylinder regulators used by first responders, and brass regulators are recommended instead.[33]

Design and oxygen compatibility assessment

Because flammability thresholds are hard to establish, much of the assessment work focuses on the presence and probability of ignition mechanisms.[26] Table 9.17.2 of the handbook lists internal sources, such as particle impact, rapid pressurisation, flow friction, galling and electrical arcs. It also lists external sources, such as welding, lightning, smoking and open flames.[4]

The oxygen compatibility assessment described by Rosales and Stoltzfus (2008) is a systematic way to judge the likelihood of a fire in an oxygen component or system. It serves both as a design guide and as an approval process.[8] Its eight steps start with the most severe operating conditions, the flammability of the materials and the ignition mechanisms present. The kindling chain and the reaction effect follow, and the results are then recorded, reviewed with others, finalised and archived.[8] The kindling chain is the ability of a fire, once started in one part, to propagate and burn through the component.[26] In the worked valve example in the handbook, a credible ignition mechanism exists, but the Monel 400 body is nonflammable, so no burnthrough is expected and the reaction effect is rated negligible.[37]

Flowchart of the eight steps of an oxygen compatibility assessment from operating conditions to archiving
The eight steps of the oxygen compatibility assessment for oxygen components and systems.

The handbook lists seven design techniques that limit ignition and fire spread.[6] They are avoiding concentrations of combustible material near heat or ignition sources, spatial separation, heat-sink masses for thermal damping, flashover barriers, sealed or inerted packaging, automatic fire monitoring, and flashback arresters in hose lines.[6] All materials in contact with the enriched atmosphere should be cleaned of foreign material.[6] Allen (2008) adds that systems carrying compressed air, oxygen or nitrous oxide must be kept free of hydrocarbon contaminants such as solvents and lubricants.[33] In the practice described in the 2008 handbook, electrical equipment is limited to that approved for the maximum expected oxygen pressure and concentration. This is because contacts that are safe in air can burn away in oxygen and ignite insulation.[6]

Fire extinguishment

Fires in oxygen-enriched atmospheres place extra demands on extinguishing systems because of easy ignition, faster flame spread, higher burning intensity and the flammability of materials that resist fire in air.[9] According to Rosales and Stoltzfus (2008), an extinguishant must act rapidly, be inherently nontoxic and not produce toxic or corrosive decomposition products.[9] Water has proved effective when applied in sufficient quantity. A water spray density of 1¼ gpm/ft² (50 L/min/m²) applied for 2 minutes extinguishes cloth burning in 100 percent oxygen at atmospheric pressure.[9] The spray must cover the whole protected space and penetrate deep enough to reach fires within layers, such as clothing.[9]

Halon 1301 has proved effective, but its use is restricted under the Montreal Protocol; carbon dioxide and nitrogen have been used as diluents, though carbon dioxide must be restricted in occupied areas.[9] No reliance should be placed on blankets of Nomex, wool or fibreglass.[9] In compressed-air atmospheres fire blankets and dry chemical agents are ineffective, because burning continues in gas pockets and the material must be cooled with water.[3] Because flame spread is so fast, the 2008 handbook describes fixed systems in the United States that actuate automatically in less than 1 second after a detectable flame is perceived.[9] In occupied areas a manual water hose of at least ½ in (13 mm) inside diameter, with a nozzle pressure of at least 50 psi (345 kPa) above ambient, is usually provided as well.[9]

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 1.4 Rosales and Stoltzfus (2008), p. 9-225.
  2. ↑ 2.0 2.1 2.2 Van Rossum (2027), §4.2.
  3. ↑ 3.0 3.1 3.2 3.3 3.4 3.5 Allen (2008), p. 6-191.
  4. ↑ 4.0 4.1 4.2 4.3 4.4 Rosales and Stoltzfus (2008), p. 9-227.
  5. ↑ 5.0 5.1 Allen (2008), p. 6-188.
  6. ↑ 6.0 6.1 6.2 6.3 6.4 6.5 Rosales and Stoltzfus (2008), p. 9-241.
  7. ↑ 7.00 7.01 7.02 7.03 7.04 7.05 7.06 7.07 7.08 7.09 7.10 7.11 7.12 7.13 7.14 7.15 7.16 Rosales and Stoltzfus (2008), p. 9-226.
  8. ↑ 8.0 8.1 8.2 8.3 Rosales and Stoltzfus (2008), p. 9-237.
  9. ↑ 9.0 9.1 9.2 9.3 9.4 9.5 9.6 9.7 9.8 Rosales and Stoltzfus (2008), p. 9-242.
  10. ↑ Iqbal and Salley (2004), p. 1-8.
  11. ↑ Cholin (2008a), p. 14-103.
  12. ↑ Friedman (2002), p. 1-100.
  13. ↑ Rivkin (2008b), p. 21-59.
  14. ↑ 14.0 14.1 Manz and Blank (2008), p. 9-82.
  15. ↑ 15.0 15.1 Stull and Chines (2008), p. 6-99.
  16. ↑ Beyler (2002b), p. 2-181.
  17. ↑ Kanury (2002b), p. 2-195.
  18. ↑ 18.00 18.01 18.02 18.03 18.04 18.05 18.06 18.07 18.08 18.09 Rosales and Stoltzfus (2008), p. 9-230.
  19. ↑ 19.0 19.1 Rosales and Stoltzfus (2008), p. 9-229.
  20. ↑ 20.0 20.1 Rosales and Stoltzfus (2008), p. 9-228.
  21. ↑ Kanury (2002a), p. 2-239.
  22. ↑ Rosales and Stoltzfus (2008), p. 9-232.
  23. ↑ Drysdale (2002), p. 1-96.
  24. ↑ Iqbal and Salley (2004), p. 3-9.
  25. ↑ 25.0 25.1 25.2 Rosales and Stoltzfus (2008), p. 9-235.
  26. ↑ 26.0 26.1 26.2 26.3 Rosales and Stoltzfus (2008), p. 9-239.
  27. ↑ 27.0 27.1 Rosales and Stoltzfus (2008), p. 9-233.
  28. ↑ Beyler (2002b), p. 2-183.
  29. ↑ 29.0 29.1 Rosales and Stoltzfus (2008), p. 9-234.
  30. ↑ Beyler and Hirschler (2002), p. 1-124.
  31. ↑ 31.0 31.1 31.2 31.3 Rosales and Stoltzfus (2008), p. 9-236.
  32. ↑ Rosales and Stoltzfus (2008), p. 9-238.
  33. ↑ 33.0 33.1 33.2 33.3 33.4 33.5 Allen (2008), p. 6-194.
  34. ↑ Allen (2008), p. 6-190.
  35. ↑ Allen (2008), p. 6-192.
  36. ↑ 36.0 36.1 Allen (2008), p. 6-195.
  37. ↑ Rosales and Stoltzfus (2008), p. 9-240.

References

  • Allen, M. (2008). Medical gases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-187–6-196). National Fire Protection Association.
  • Beyler, C. L. (2002b). Flammability limits of premixed and diffusion flames. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-172–2-187). National Fire Protection Association; Society of Fire Protection Engineers.
  • Beyler, C. L., & Hirschler, M. M. (2002). Thermal decomposition of polymers. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 1-110–1-131). National Fire Protection Association; Society of Fire Protection Engineers.
  • Cholin, J. M. (2008a). Gas and vapor detection systems and monitors. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 14-99–14-112). National Fire Protection Association.
  • Drysdale, D. D. (2002). Thermochemistry. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 1-90–1-98). National Fire Protection Association; Society of Fire Protection Engineers.
  • Friedman, R. (2002). Chemical equilibrium. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 1-99–1-109). National Fire Protection Association; Society of Fire Protection Engineers.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Kanury, A. M. (2002a). Flaming ignition of solid fuels. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-229–2-245). National Fire Protection Association; Society of Fire Protection Engineers.
  • Kanury, A. M. (2002b). Ignition of liquid fuels. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-188–2-199). National Fire Protection Association; Society of Fire Protection Engineers.
  • Manz, A. F., & Blank, M. E. (2008). Welding, cutting, and other hot work. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-73–9-83). National Fire Protection Association.
  • Rivkin, C. H. (2008b). Vehicle fueling using gaseous fuels. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-41–21-76). National Fire Protection Association.
  • Rosales, K., & Stoltzfus, J. M. (2008). Oxygen-Enriched atmospheres. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-225–9-243). National Fire Protection Association.
  • Stull, J. O., & Chines, S. A. (2008). Fibers and textiles. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-75–6-102). National Fire Protection Association.