Contents
Positive pressure ventilation (PPV) is a firefighting technique in which a fan supplies fresh air to an enclosure. The added air raises pressure relative to adjoining spaces or outdoors and can drive smoke towards an outlet. The route between inlet and outlet determines which parts of the building the smoke crosses.[1][2]
Fresh air has two effects during a fire. It can displace smoky gases from part of a building, and it can supply oxygen to burning fuel. If oxygen was limiting combustion, the heat release rate can rise. A clearer entrance can therefore coexist with worsening conditions elsewhere. The condition of the fire and the route available to the gases both matter when interpreting a change in visibility.[1][3][4]
Pressure and the available openings
A fan changes one of the forces acting on the air. Hot smoke rises through buoyancy. Wind and differences in indoor and outdoor temperatures also create pressure differences across openings. An open door, a broken window or a link to a shaft can connect spaces that previously exchanged little air. The resulting smoke movement depends on all these paths.[2][4]
The pressure difference and the flow through an opening describe different things. A closed door can sustain a pressure difference while passing relatively little air through its gaps. An open doorway provides a much larger path. A fan’s presence alone therefore does not establish the direction of smoke travel in every room.[5][1]
Interaction with the fire
In a ventilation-controlled fire, hot fuel can generate combustible gases faster than the available oxygen allows them to burn. Adding air changes that balance. Under particular conditions a rapid burning of accumulated gases after air enters is called a backdraft. An increase in burning rate can also occur without a backdraft.[3]
The Australian verification data sheets describe the same interaction in building smoke-control design. Incoming air close to a fire can increase heat release or deflect the plume into an occupied area. The location of the people between the fire and the exhaust is therefore as relevant to the interpretation as conditions near the fan.[4][1]
Portable fans and fixed systems
A portable fan supplies air during an incident. A fixed stair pressurisation system serves a different purpose. It maintains a pressure difference across a boundary to limit smoke entering a protected escape route. Both use pressure, but a stair enclosure and a compartment being cleared of smoke have different airflow objectives.[1][5]
Reading an incident description
A useful description identifies the inlet, outlet, intervening rooms and the state of significant doors or windows. It also distinguishes observations made while the fire was burning from observations made after extinguishment. Once the fire is out, there is no longer an active fuel bed whose heat release can respond to the added oxygen. Smoke can still travel into connected spaces.[1][2][3]
See also
Notes
- ↑ 1.0 1.1 1.2 1.3 1.4 1.5 Iqbal and Salley (2004), Appendix F, p. F-46, citing Nolan (2000).
- ↑ 2.0 2.1 2.2 Klote (2002), ch. 4-12, pp. 4-274–4-278.
- ↑ 3.0 3.1 3.2 Van Rossum (2027), §§4.8–4.9.
- ↑ 4.0 4.1 4.2 Australian Building Codes Board (2020), Data Sheet B1, §§1.5.4.3–1.5.4.4, pp. 21–22.
- ↑ 5.0 5.1 Klote (2002), ch. 4-12, pp. 4-278–4-280.
References
- Australian Building Codes Board. (2020). Fire safety verification method: Data sheets.
- Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission fire protection inspection program (NUREG-1805). U.S. Nuclear Regulatory Commission.
- Klote, J. H. (2002). Smoke control. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed.). National Fire Protection Association.
- Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.