  1. 1Uneven heating and cracking
  2. 2What changes when glass falls
  3. 3New Zealand’s modelling assumption
  4. 4Describing an assumed opening
  5. 5See also
  6. 6Notes
  7. 7References

Glass breakage in fire occurs when uneven heating creates stresses that a pane can no longer withstand. The exposed part of a window may heat rapidly while the edge sheltered by the frame remains cooler. A crack relieves some of the stress. Fragments may remain held by the frame, so the first visible crack and the creation of a ventilation opening can be separated in time.[1][2]

The distinction matters for a compartment fire. While cracked glass remains in place, it can still restrict the exchange of air and smoke. If glass falls away, air can enter and hot gases can escape. A fire calculation therefore needs to distinguish damage to the pane from the area actually open to flow.[2][3][4]

A framed pane has a warmer centre and a cooler band at its shielded edge. No failure temperature is assigned.
Unequal heating across a pane produces thermal stress. The frame partly shields the perimeter. Based on Davoodi (2008), §18.1, p. 18-11.

Uneven heating and cracking

Hot gases and thermal radiation heat the exposed area of a window. The warmer glass tends to expand relative to the cooler perimeter. The resulting stress depends partly on how the frame shields and holds the pane. Heating rate, glass properties, the frame and the gasket all contribute to the uncertainty in when fragments will fall.[1][2][5]

What changes when glass falls

Fresh air entering an opening can support a larger fire if the available oxygen had been limiting combustion. At the same time, some smoke that would otherwise enter adjoining rooms can escape outdoors. A change in the ventilation factor therefore affects both the fire and where its products travel.[2][4]

Outside the building, flames projecting from an opening can expose the next storey to a façade fire. Radiation can also cross intact glazing and expose objects beyond it. The presence of an external heat exposure alone cannot establish when the pane fell out.[5][1]

Two panes with similar cracks. Glass remains in the first frame. A missing piece in the second forms an opening.
A crack can leave a pane in place. Fallout changes the area available for air and smoke to pass. Based on Ministry of Business, Innovation and Employment (2013), commentary on §2.2.1(m), p. 41.

New Zealand’s modelling assumption

New Zealand’s C/VM2, second edition (2025), treats exterior windows without a fire-resistance rating as fully open at the earlier of two events. One is an average upper gas layer temperature of 500 °C. The other is the fire becoming limited by ventilation. Thus a ventilation-limited fire can trigger the model opening while the upper layer is still below 500 °C.[3]

The temperature belongs to the gas layer in this design method. Predicting the fracture of an individual pane would require evidence about its uneven heating and support. The commentary relates the thermal condition to the onset of flashover. C/VM2 treats fire-resistant glazing separately and allows it to remain in place up to its rated time.[3][2]

Either an average upper layer temperature of 500 °C or ventilation limitation triggers the modelled opening, whichever comes first.
New Zealand’s verification method uses the earlier of the two conditions for exterior windows without a fire-resistance rating. Based on Ministry of Business, Innovation and Employment (2025), §2.1.5.1–2.1.5.2, p. 16.

Describing an assumed opening

A design record can distinguish the first crack from the first open area. It can also state how much of the original window that area represents. This makes clear which event changes the ventilation in the calculation. The Australian verification data sheets likewise call for the assumed state of doors and windows to be stated when deriving a design fire.[2][4]

See also

Notes

  1. ↑ 1.0 1.1 1.2 Davoodi (2008), §18.1, p. 18-11.
  2. ↑ 2.0 2.1 2.2 2.3 2.4 2.5 Ministry of Business, Innovation and Employment (2013), commentary on §2.2.1(m), p. 41.
  3. ↑ 3.0 3.1 3.2 Ministry of Business, Innovation and Employment (2025), §2.1.5.1–2.1.5.2, p. 16.
  4. ↑ 4.0 4.1 4.2 Australian Building Codes Board (2020), Data Sheet B1, §§1.5.4.3–1.5.4.4, pp. 21–22.
  5. ↑ 5.0 5.1 Australian Building Codes Board et al. (2005), §1.6.4.1, pp. 1.6-6–1.6-7.

References