Polyurethane foam is a cellular plastic made from polyurethane, a polymer formed by the reaction of isocyanates with materials such as polyols, and is produced as flexible, semi-flexible and rigid foam.[1][2] Flexible foam is by far the dominant padding in upholstered furniture and is widely used in mattresses, while rigid foam is used as thermal insulation in buildings.[3][4][1] In fire safety the material is known for its very low thermal inertia.

A typical foam has a density of about 20 kg/m³ and a thermal conductivity of 0.034 W/(m·K), so its surface heats up quickly and it ignites easily.[5][6] Once it burns, flexible foam can melt into a burning pool and produce dense smoke, and as a nitrogen-containing polymer it can release hydrogen cyanide as well as carbon monoxide.[7][8] A polyurethane sofa has reached a peak heat release rate of 3,120 kW in tests.[9] The foam can also smoulder for long periods after ignition by a cigarette.[3] In 2003 polyurethane foam on the walls of the Station nightclub in the United States was ignited by pyrotechnics, and 100 people died.[5]

Composition and manufacture

Polyurethanes are a group of polymers produced in two general forms: foams, which may be flexible, semi-flexible or rigid, and elastomers, which include casting compounds, adhesives, coatings and spandex fibre. The basic reaction joins isocyanates with materials that carry reactive hydrogen, such as polyethers, castor oils, amines, carboxylic acids and water. By varying the number of branchings in the molecule, polyurethanes can be made either thermoplastic or thermosetting.[1] In the SFPE Handbook, Beyler and Hirschler describe polyurethanes as polymers with the characteristic group –NH–COO– in their repeating unit, normally made by condensation of polyisocyanates and polyols. Their principal use is as flexible and rigid foams or as thermal insulation.[2] Rigid polyurethanes are so highly cross-linked that it becomes impossible to speak of a molecular weight.[10]

A foam is any polymeric material with a low-density cellular structure, in which the cells can be open or closed.[11] Flexible urethane foams for upholstery and garments, and rigid foams for poured-in-place construction or refrigeration insulation, are blown by steam and carbon dioxide. Both gases are by-products of the reaction that forms the urethane resin, and foams of lower density can be made by adding a low-boiling hydrocarbon to the mixture.[12] Reaction injection moulding is used mainly for polyurethane elastomers and foams with a solid skin and a cellular core. Two or more pressurised reactive streams are mixed at high pressure and injected into a mould, where the reaction continues until the product has set.[13]

Flexible foam is used in upholstered furniture, bedding, sponges, toys, clothing and medical dressings, and rigid urethane foam is used for insulation in building construction.[1] In furniture, polyurethane foams became common in the 1960s. They were first used plain, but today often carry a "topper" layer of polyester batting.[14] A 1997 survey by the US Consumer Product Safety Commission found polyester batting over polyurethane foam in 76 % of upholstered furniture, polyurethane foam alone in 17 % and other padding in 6 %.[14][15] The handbook lists densities of 29 to 47 kg/m³ for flexible foams and 36 to 321 kg/m³ for rigid foams.[16]

Thermal properties and ignitability

The ease of ignition of polyurethane foam follows from its thermal properties. Typical values are a thermal conductivity of 0.034 W/(m·K), a density of 20 kg/m³ and a heat capacity of 1,400 J/(kg·K).[5][17] For yellow pine the conductivity is more than 4 times higher, the density more than 30 times and the heat capacity twice as high. Polyurethane therefore cannot conduct heat away from its surface as well as wood and needs less energy to ignite.[5] The product of the three properties, the thermal inertia kρc, is about 950 W²·s/(m⁴·K²) for the foam against about 255,000 W²·s/(m⁴·K²) for pine, a factor of about 270.

Drysdale illustrates the effect with everyday experience: a hand placed on a block of polyurethane foam feels warm, because the foam does not conduct heat away from the skin. He gives a thermal inertia of 950 W²·s/(m⁴·K²) for the foam and 780,000 W²·s/(m⁴·K²) for oak.[18] Polyurethane foam can therefore be ignited very easily, whereas solid polyurethane of high density is relatively difficult to ignite.[6] NUREG-1805 draws the general conclusion that density is the most important material property for ignition: the surface of a low-density material heats more rapidly and ignites sooner.[19] In experiments by the US National Institute of Standards and Technology (NIST) after the Station fire, wall-mounted ether-based polyurethane foam ignited within 10 seconds when exposed to pyrotechnics like those used in the nightclub. The sparks did not have enough energy to ignite birch plywood.[5]

Log-scale bar chart of thermal inertia: polyurethane foam 950, fibre insulation board 20,000, asbestos 90,000, oak 780,000, steel 160,000,000.
Thermal inertia kρc of polyurethane foam compared with other materials, on a logarithmic scale.

Measured ignition properties vary widely. The International Fire Engineering Guidelines, citing Babrauskas (2003), give a minimum heat flux for piloted ignition of below 10 to 16 kW/m² for flexible foam and below 10 kW/m² for rigid foam. For autoignition the values are 16 kW/m² for flexible foam and 22 to 26 kW/m² for rigid foam.[20] Table 6.17.7 of the NFPA handbook lists 16 to 30 kW/m² for flexible and 20 to 28 kW/m² for rigid foams. It gives ignition temperatures of 729 to 852 K (456 to 579 °C) for flexible foams, whereas NUREG-1805 lists 280 °C.[16][21] Babrauskas attributes such spreads to differences in specimen size, orientation, air flow, heat flux and composition.[16]

Estimating the time to ignition

For a thick solid exposed to a constant radiant heat flux, the time to ignition is the time its surface needs to reach the ignition temperature. This time grows with the thermal inertia and with the square of the temperature rise required. It falls with the square of the amount by which the heat flux exceeds the critical heat flux, below which ignition does not occur. NUREG-1805 gives this relation as the method of Mikkola and Wichman, taken from the SFPE engineering guide on piloted ignition:[22]

tig=π4kρc(Tig−Ta)2(q˙′'r−q˙′'cr)2

Symbol Description Unit
tig Time to ignition s
kρc Thermal inertia of the material (kW/(m²·K))²·s
Tig Ignition temperature °C
Ta Ambient temperature °C
q˙′'r External (radiant) heat flux kW/m²
q˙′'cr Critical heat flux for ignition kW/m²

The relation assumes a thermally thick material, through which the heat wave has not yet reached the rear face. A slab behaves in this way until the heated depth, approximately 2αt with α the thermal diffusivity, approaches its thickness.[18] The critical heat flux and the ignition temperature are not unique material constants. Each correlation derives them in its own way from test data, and NUREG-1805 warns that the critical heat flux should not be confused with the minimum heat flux for ignition.[19][21]

As a worked example, NUREG-1805 lists for polyurethane foam an ignition temperature of 280 °C and a thermal inertia of 0.00095 (kW/(m²·K))²·s. For 12.3 mm plywood it gives 390 °C and 0.16 (kW/(m²·K))²·s.[21] The NFPA handbook gives a critical heat flux of 16 kW/m² for plywood.[23]

No measured critical heat flux for the foam is available in these sources. To show the formula's sensitivity, assume 10 and 16 kW/m² as illustrative values, taken from the separate minimum-flux data quoted above.[20] These data are not measured critical heat fluxes for this correlation.[19] With an exposure of 25 kW/m², an ambient temperature of 20 °C and the lower assumed value for the foam, the formula gives

tig=π4×0.00095×(280−20)2(25−10)2≈0.22 s

With the upper assumed value of 16 kW/m², the formula gives about 0.62 s for the foam. It gives about 212 s for plywood under the same exposure.[22] The illustrative calculation therefore yields 0.22–0.62 s for the foam and 212 s for plywood. These are model outputs for the stated inputs, not measured ignition times or general predictions. For comparison, NUREG-1805 reports measured ignition times of 150 s for hardboard at 30 kW/m² and 250 s for wood particle board at 20 kW/m².[24]

Illustrative ignition-time curves: two assumed critical heat fluxes for foam and a curve using a published value for plywood.
Illustrative model curves for polyurethane foam with assumed critical heat fluxes of 10 and 16 kW/m², compared with plywood at 16 kW/m².

With a thermal diffusivity of 1.21 × 10−6 m²/s for the foam, the heated depth at these calculated times is 1.0 to 1.7 mm. A foam cushion or wall lining thicker than this depth would satisfy the thermally thick assumption for this illustration.[17] In a separate NIST experiment, pyrotechnic sparks ignited exposed foam within 10 seconds but did not ignite plywood; that exposure was different from the fixed heat flux assumed here.[5]

Burning behaviour and heat release

The way the foam decomposes shapes its role among plastics in fire. As a class, polyurethanes do not break down below 475 K (202 °C). A major mechanism is the breaking of the bond between polyol and isocyanate formed during polymerisation: the isocyanate vaporises and recondenses as a smoke, while the liquid polyol remains and decomposes further.[25] In flexible foams one decomposition path produces gaseous isocyanates that repolymerise in the gas phase and condense as a "yellow smoke".[26] The NFPA handbook describes the same process as the formation of liquid polyols and gaseous isocyanates, and notes that some polyurethane foams form a char.[27]

Flowchart: heated foam splits into isocyanate vapour, which condenses as yellow smoke, and liquid polyol, which forms a burning pool.
Simplified decomposition path of flexible polyurethane foam. Above about 475 K the polyol–isocyanate bond breaks into isocyanate vapour and liquid polyol.

The liquid stage matters in real fires. In a fire in bulk storage of flexible foam blocks, the liquefied plastic can form a pool that burns like a flammable liquid with a high flash point. Fire fighters may therefore meet a pool fire similar to a Class B fire beneath burning foam.[7][28] Studies in England showed that pool burning can account for about 50 % of the peak heat release rate of an upholstered chair.[29] Expanded, low-density foam also generally burns with a higher heat release rate than the same polymer in rigid, unexpanded form.[30]

The table shows peak heat release rates of furnishings in unconfined burning, as listed in NFPA 921 (2004 edition) and reproduced in the 2008 handbook.[9] Masses are converted from pounds, and the polyurethane items burn several times more intensely than the cotton ones of similar mass.

Representative peak heat release rates, unconfined burning[9]
Item Mass (kg) Peak heat release rate (kW)
Cotton easy chair 17.7–31.8 290–370
Cotton mattress 11.8–13.2 40–970
Polyurethane mattress 3.2–14.1 810–2,630
Polyurethane easy chair 12.2–27.7 1,350–1,990
Polyurethane sofa 51.3 3,120

Babrauskas notes that a medium-sized sofa can reach 2 to 3 MW only 3 to 5 minutes after ignition, and that about 5 MW is common for large sofas. Less than 2 MW is enough to cause flashover in a room with a normal-sized door.[31] Introduction to Fire Safety Engineering uses 2.5 MW as a guide value for an average living-room sofa.[32] When polyurethane foam replaced traditional padding in the 1970s, the heat release rates of furniture rose to many times those of traditional types.[33] These values make the foam a main driver of the upholstered furniture fire.

Range bars of peak heat release rate: cotton items 40 to 970 kW, polyurethane items 810 to 3,120 kW, with a line at 2,000 kW for flashover.
Peak heat release rates of cotton and polyurethane furnishings in unconfined burning, with the level of about 2 MW that can cause flashover in a room with a normal door.

In tests relevant to mattress flammability, mattresses show the same pattern. In SFPE Handbook data, a polyurethane foam mattress of 14 kg with PVC ticking reached 2,630 kW, and mattresses of 4 to 6 kg reached 760 to 1,620 kW. A neoprene mattress of 18 kg reached only 70 kW.[34] In another series, mattresses with a bench-scale heat release rate below 165 kW/m² gave room fires of less than 100 kW. Those above it gave fires of 1 to 2 MW, with an abrupt transition.[34] In US prisons, certain types of polyurethane foam mattresses are a significant fuel source because they support fast fire development, high heat release and heavy smoke production.[35]

Values for the heat of combustion differ with formulation and method. The handbook tables give a net heat of combustion of 26.30 MJ/kg for polyurethane and 22.70 MJ/kg for an ester-based grade, and the International Fire Engineering Guidelines give 26 MJ/kg for polyurethane foam.[36][37] The Australian Fire Safety Verification Method data sheets give chemical heats of combustion of 17.6 MJ/kg for flexible and 16.9 MJ/kg for rigid foam from well-ventilated bench-scale tests.[38] The effective heat of gasification of flexible foam is low, 1.2 to 2.7 MJ/kg.[16] A low heat of gasification increases the hazard, because less heat is needed to produce fuel vapour.[27]

Smoke and toxic gases

Dense smoke is characteristic of both treated and untreated urethane foams. In a study of smoke density cited in the handbook, urethane foams under flaming or non-flaming exposure obscured vision within a fraction of a minute, and under flaming exposure in less than 15 seconds.[7] For modelling, the Australian data sheets give soot yields of 0.188 kg/kg for flexible and 0.118 kg/kg for rigid foam, values that NUREG-1805 also lists.[38][39] Introduction to Fire Safety Engineering quotes 0.23 kg/kg for polyurethane.[40] The C/VM2 commentary of New Zealand points out that reported soot yields for flexible polyurethane range from 0.01 to 0.23, more than an order of magnitude. Carbon monoxide yields vary by a factor of 4 and the effective heat of combustion by about ±25 %, because of different test conditions and additives.[41]

Because polyurethane contains nitrogen, its fire gases can include hydrogen cyanide (HCN). Nitrogen-containing polymers release HCN in smouldering fires, during pyrolysis and in flaming combustion.[8] The lethal dose of HCN is about 25 times smaller than that of carbon monoxide.[42] The yields of HCN and carbon monoxide from polyurethanes increase with the pyrolysis temperature, and other toxic products include nitrogen oxides, nitriles and tolylene diisocyanate.[25] The International Fire Engineering Guidelines note that smouldering polyurethane foam can yield significant HCN, so analysis cannot always be restricted to carbon monoxide.[43] Concern about "supertoxicants" in fire smoke has diminished, and one of the few documented examples was a neurotoxin formed from a non-commercial rigid polyurethane foam.[44]

The NIST reconstruction of the Station nightclub fire shows how fast these hazards develop. Non-fire-retardant, ether-based polyurethane foam was glued over plywood panelling in a drummer's alcove, and within 60 seconds the alcove was fully involved. In less than 90 seconds, the gas temperature at 1.4 m above the floor exceeded 400 °C and the heat flux exceeded 30 kW/m². At the same time the oxygen volume fraction fell below 0.05, while the HCN and carbon monoxide fractions exceeded 0.0015 and 0.03.[45] Occupants would likely have had less than 1.5 minutes to escape. In a duplicate test with automatic sprinklers, the sprinklers operated within 30 seconds and conditions remained tenable.[46]

Smouldering

Flexible foam also takes part in smouldering, the slow, flameless combustion typically started by a cigarette in upholstery or bedding. This scenario makes smouldering a major contributor to residential fire deaths. The combination of a cellulosic fabric with polyurethane foam can smoulder over a much wider range of conditions than the foam alone, because the fabric adds heat to the foam while competing for oxygen.[47] Without oxygen many flexible foams form no char, yet char oxidation is a necessary source of heat for smouldering. In one test configuration the evolved gases contained 6 to 7 mole % carbon monoxide.[48]

Smouldering may or may not turn into flaming. Times of 22 minutes to several hours between placing a cigarette and the onset of flaming have been reported, and in a closed room flaming can revert to smouldering when the oxygen runs out.[3] In polyurethane foam the transition to flaming appeared to start within the char layer left behind by the smoulder front, rather than at the foam surface.[49] Smouldering fires involving polyurethane foams have also produced smoke explosions, when unburned fuel and carbon monoxide formed a flammable mixture that later ignited.[50] Soaking or even immersing a smouldering item in water may not ensure extinction. The handbook advises removing such items from the premises, tearing them apart and wetting the pieces thoroughly.[15]

Fire-retardant grades and protection

Several strategies reduce the hazard of furniture foam. In California, Technical Bulletin 117 tested naked foams with a vertical Bunsen burner, and a small amount of fire retardant normally produced a dramatic improvement in this test. The state has required fire-retardant-treated, or equivalent, furniture foams since 1975.[51] Full-scale tests at NIST showed, however, that a chair with foam complying with Technical Bulletin 117 gave essentially the same heat release rate as one with ordinary foam.[33] Advanced foam formulations mainly improve the heat release rate rather than the ignitability.[52]

In the United Kingdom, regulations from the late 1980s required furniture and mattresses to resist small flames and cigarettes. Furniture there generally uses advanced fire-retardant polyurethane foams, and a government survey claimed a 40:1 benefit to cost ratio, although a US reanalysis disputed this.[53] Babrauskas adds that materials with much lower toxicity per gram are not available, so reducing the heat release rate is the practical way to limit the toxic hazard of furniture.[4]

Design measures also work. The simplest strategy is to use less foam, because peak heat release rate depends strongly on the mass of upholstery. Ordinary high-resiliency foam can be replaced by combustion-modified high-resiliency foam, and lightweight interliners of 70 to 170 g/m² between fabric and foam act as a radiation shield and flame barrier.[4][54] For mattresses, an add-on barrier cover reduced the peak heat release rate of one commercial mattress from 1,900 kW to 100 kW. Mattresses made with a barrier in the factory gave 20 to 40 kW.[29] Such flame retardant treatments and barriers are at the core of mattress and furniture fire standards.

Rigid and sprayed foams used as foam plastic insulation raise similar problems. Untreated rigid polyurethane burns rapidly and is readily ignited, while fire-retardant grades resist small, short ignition sources and often stop burning when the flame is removed. In a 1969 review of fires, a high rate of flame spread appeared to be especially typical of sprayed-on polyurethane and rigid polyurethane boards, and tunnel flame spread ratings ranged from 5 to 1,375.[7]

In the United States, model building codes as described in the 2008 handbook require foamed plastic wall insulation to be covered by a thermal barrier such as 12.7 mm (½ in.) gypsum board.[55] NFPA 101 and NFPA 5000, as described by Hirschler (2008b), do not allow foam plastics as interior finish unless fire tests support their use.[56] In New Zealand, the 2013 commentary to the first edition of C/VM2 treats exposed polyurethane foams as typical Group Number 4 linings. Such linings lead to flashover within 2 minutes and are not acceptable in occupied spaces.[57]

Industrial uses carry their own risks. In 1975, at the Browns Ferry nuclear power plant in the United States, electricians checking a cable penetration seal of polyurethane with a candle flame ignited the sealant. The fire spread to the grouped cables, reached temperatures up to 816 °C and damaged more than 1,600 cables.[58][59]

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 Benedetti and Colonna (2008), p. 6-222.
  2. ↑ 2.0 2.1 Beyler and Hirschler (2002), pp. 1-111–1-112.
  3. ↑ 3.0 3.1 3.2 Babrauskas (2008b), p. 6-109.
  4. ↑ 4.0 4.1 4.2 Babrauskas (2008b), p. 6-124.
  5. ↑ 5.0 5.1 5.2 5.3 5.4 5.5 Madrzykowski and Stroup (2008), pp. 2-34–2-35.
  6. ↑ 6.0 6.1 Drysdale (2008), p. 2-17.
  7. ↑ 7.0 7.1 7.2 7.3 Benedetti and Colonna (2008), p. 6-225.
  8. ↑ 8.0 8.1 Gann and Bryner (2008), p. 6-13.
  9. ↑ 9.0 9.1 9.2 NFPA 921 (2004), as cited in Custer (2008), p. 2-50.
  10. ↑ Beyler and Hirschler (2002), p. 1-129.
  11. ↑ Benedetti and Colonna (2008), pp. 6-209–6-210.
  12. ↑ Ouellette (2008), p. 9-62.
  13. ↑ Ouellette (2008), p. 9-60.
  14. ↑ 14.0 14.1 Babrauskas (2008b), p. 6-106.
  15. ↑ 15.0 15.1 Babrauskas (2008b), p. 6-110.
  16. ↑ 16.0 16.1 16.2 16.3 Babrauskas (2008a), p. 6-283.
  17. ↑ 17.0 17.1 Van Rossum (2027), §5.5.
  18. ↑ 18.0 18.1 Drysdale (2008), p. 2-8.
  19. ↑ 19.0 19.1 19.2 Iqbal and Salley (2004), pp. 6-5, 6-7.
  20. ↑ 20.0 20.1 Babrauskas (2003), as cited in National Research Council of Canada et al. (2005), p. 3.3-4.
  21. ↑ 21.0 21.1 21.2 Iqbal and Salley (2004), p. 6-7.
  22. ↑ 22.0 22.1 Iqbal and Salley (2004), p. 6-8.
  23. ↑ Quintiere (1998), as cited in Budnick et al. (2008), p. 3-159.
  24. ↑ Iqbal and Salley (2004), p. 6-4.
  25. ↑ 25.0 25.1 Beyler and Hirschler (2002), p. 1-128.
  26. ↑ Beyler and Hirschler (2002), pp. 1-114–1-115.
  27. ↑ 27.0 27.1 Madrzykowski and Stroup (2008), pp. 2-32–2-33.
  28. ↑ Benedetti and Colonna (2008), p. 6-230.
  29. ↑ 29.0 29.1 Babrauskas (2008b), p. 6-126.
  30. ↑ Custer (2008), p. 2-50.
  31. ↑ Babrauskas (2008b), p. 6-120.
  32. ↑ Van Rossum (2027), §4.5.
  33. ↑ 33.0 33.1 Babrauskas (2002b), p. 3-29.
  34. ↑ 34.0 34.1 Babrauskas (2002b), p. 3-21.
  35. ↑ Jaeger (2008), p. 20-134.
  36. ↑ Babrauskas (2008a), p. 6-278.
  37. ↑ National Research Council of Canada et al. (2005), p. 3.3-6.
  38. ↑ 38.0 38.1 Australian Building Codes Board (2020a), Data Sheet B2, p. 21.
  39. ↑ Iqbal and Salley (2004), p. 18-4.
  40. ↑ Karlsson and Quintiere (2000), as cited in Van Rossum (2027), §6.2.
  41. ↑ Ministry of Business, Innovation and Employment (2013), p. 57.
  42. ↑ Gann and Bryner (2008), p. 6-15.
  43. ↑ National Research Council of Canada et al. (2005), p. 2.4-12.
  44. ↑ Gann and Bryner (2008), p. 6-17.
  45. ↑ Gann and Bryner (2008), pp. 6-28–6-29.
  46. ↑ Gann and Bryner (2008), pp. 6-29–6-30.
  47. ↑ Ohlemiller (2002), p. 2-206.
  48. ↑ Ohlemiller (2002), p. 2-202.
  49. ↑ Ohlemiller (2002), p. 2-208.
  50. ↑ Iqbal and Salley (2004), p. 15-4.
  51. ↑ Babrauskas (2008b), pp. 6-113, 6-115.
  52. ↑ Babrauskas (2008b), p. 6-115.
  53. ↑ Babrauskas (2008b), p. 6-107.
  54. ↑ Babrauskas (2008b), p. 6-125.
  55. ↑ Benedetti and Colonna (2008), p. 6-229.
  56. ↑ Hirschler (2008b), p. 18-36.
  57. ↑ Ministry of Business, Innovation and Employment (2013), p. 21.
  58. ↑ Iqbal and Salley (2004), p. A-1.
  59. ↑ Sheridan (2008), p. 9-187.

References

  • Australian Building Codes Board. (2020a). Data sheets: Fire Safety Verification Method (Handbook annex, Print version 1.1).
  • Babrauskas, V. (2002b). Heat release rates. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-1–3-37). National Fire Protection Association; Society of Fire Protection Engineers.
  • Babrauskas, V. (2008a). Tables and charts. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-269–6-294). National Fire Protection Association.
  • Babrauskas, V. (2008b). Upholstered furniture and mattresses. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-103–6-128). National Fire Protection Association.
  • Benedetti, R. P., & Colonna, G. R. (2008). Polymeric materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-209–6-231). National Fire Protection Association.
  • Beyler, C. L., & Hirschler, M. M. (2002). Thermal decomposition of polymers. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 1-110–1-131). National Fire Protection Association; Society of Fire Protection Engineers.
  • Budnick, E. K., Hunt, S. P., & Wright, M. T. (2008). Closed form enclosure fire calculations. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-145–3-166). National Fire Protection Association.
  • Custer, R. L. P. (2008). Dynamics of compartment fire growth. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-49–2-58). National Fire Protection Association.
  • Drysdale, D. (2008). Physics and chemistry of fire. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-3–2-20). National Fire Protection Association.
  • Gann, R. G., & Bryner, N. P. (2008). Combustion products and their effects on life safety. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-11–6-34). National Fire Protection Association.
  • Hirschler, M. M. (2008b). Interior finish. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 18-23–18-42). National Fire Protection Association.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Jaeger, T. W. (2008). Detention and correctional occupancies. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-129–20-138). National Fire Protection Association.
  • Madrzykowski, D., & Stroup, D. W. (2008). Flammability hazard of materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-31–2-48). National Fire Protection Association.
  • Ministry of Business, Innovation and Employment. (2013). Commentary for Building Code clauses C1–C6 and Verification Method C/VM2.
  • National Research Council of Canada, International Code Council, Department of Building and Housing, & Australian Building Codes Board. (2005). International fire engineering guidelines (2005 ed.). Australian Building Codes Board.
  • Ohlemiller, T. J. (2002). Smoldering combustion. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-200–2-210). National Fire Protection Association; Society of Fire Protection Engineers.
  • Ouellette, G. (2008). Plastics industry and related process hazards. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-53–9-65). National Fire Protection Association.
  • Sheridan, D. J. (2008). Electric generating plants. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-179–9-189). National Fire Protection Association.
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.