Overhaul is the stage of Firefighting in which crews search the fire area for hidden and smouldering fire after the main fire has been suppressed, so that the fire is completely extinguished.[1][2] In US fireground operations, as described in the 2008 Fire Protection Handbook, walls, ceilings and other building components are checked during overhaul and opened where necessary.[1] The work is needed because burning can survive in porous fuels, building voids and piled goods after the flames are gone. The key to stopping a smouldering fire is to get the heat out of the fuel.[3][4][5]

Overhaul is a traditional task of ladder companies, alongside search and rescue, forcible entry, ventilation and salvage.[6] Opening concealed spaces releases smoky, toxic and smouldering material, and building components may contain asbestos. Firefighters and fire investigators therefore wear full protective gear, including breathing apparatus, until the building is free of smoke and airborne contaminants.[1] Overhaul also changes the burn patterns that investigators later interpret.[7] In the United States, fires that rekindled after being extinguished have led to negligence claims against fire departments.[8]

Definition and place in fireground operations

Klaene and Sanders (2008) state that the purpose of overhaul is to ensure that the fire is completely extinguished. To keep property damage to a minimum while reaching that goal, overhaul must be carried out in a well-planned, systematic manner.[1] They discuss it under property conservation, the third of the US operational priorities after life safety and extinguishment.[9] Before overhaul starts, the incident commander sizes up whether the fire has severely damaged the building's structural components. If it has not, firefighters may enter to complete overhaul, and where damage is minor the occupants may sometimes be allowed back in.[1]

Comly (2008) counts overhaul operations among the segments of the time needed for fire control. They follow fire detection, occupant notification, fire department notification and response, assessment of the fire situation and suppression activities.[2] In a sprinklered warehouse where the sprinklers have controlled the fire, there is time to plan the operations needed for final extinguishment, overhaul and salvage.[10] Van Rossum (2027) calls the last phase of a fire the decay phase, which can start because the fuel runs out or because the fire service intervenes.[11]

Horizontal timeline of fire control segments from detection to suppression and overhaul
Segments of the time needed for fire control, ending with overhaul operations.

Snyder (2008) also assigns salvage and overhaul to industrial fire brigades. He notes that efforts should be made, concurrently with fire fighting, to reduce the damage caused by the fire and by the fire-fighting itself, through salvage and overhaul. Brigades therefore need salvage and overhaul equipment to minimise water, smoke and fire damage during and after a fire.[12][13] Overhaul is thus closely tied to Salvage, the protection of property and contents from avoidable damage.

Wildland firefighting has its own final stage, called mop-up. Smalley (2008) describes it as the work needed, once a fire is called controlled, to put out all embers or sparks so that none can cross the fireline. Mop-up normally combines two actions: putting the fire out and disposing of fuel, either by burning it or by removing it so that it cannot burn.[14] Patrolling the control line and checking that the fire is out before leaving are further steps.[14]

Why fires rekindle

Ohlemiller (2002) defines Smouldering as a slow, low-temperature, flameless form of combustion, sustained by the heat evolved when oxygen attacks the surface of a solid fuel directly.[15] It typically occurs in porous, finely divided fuels that form char. These aggregates insulate well, so that combustion can continue despite low heat release rates.[15] Van Rossum (2027) likewise distinguishes flaming and smouldering combustion, and notes that flaming causes the most acute danger.[16] Smouldering also provides a pathway to flaming that weak heat sources can start.[15]

Removing oxygen alone does not stop such a fire. According to Ohlemiller (2002), the true key is getting the heat out of the fuel, which can be extraordinarily difficult. Oxygen removal is insufficient unless it is sustained until the fuel has cooled so far that readmitted oxygen will not cause reignition.[3] Yu and Newman (2008) make the same point for inert gas extinguishment: if the gas dissipates after several minutes, a glowing ember or hot metal can reignite the fire. Reignition is common for deep-seated fires, such as those in upholstered furniture or cartons of documents.[17] Solution from high-expansion foam tends to penetrate ordinary combustibles, yet deep-seated fires may still require overhaul.[18]

The same logic appears in risk analysis for US nuclear power plants. The fire probabilistic risk assessment method NUREG/CR-6850 assumes that a fire will reflash if a gaseous suppressant concentration cannot be maintained for the prescribed time. A second discharge or intervention by plant personnel is then needed to regain control.[19][20] Self-heating materials are a more extreme case. Gray (2002) notes that deep-seated burning started by spontaneous ignition, as in bagasse, woodchip or peat piles, can be difficult to extinguish completely and often reignites days after apparent extinction.[21]

In buildings, fire hides in concealed spaces. Corbett (2008) identifies hidden fires as a major hazard of the voids in buildings of ordinary construction. Dropped ceilings in old buildings adapted to new uses provide huge voids through which hidden fire can travel.[4][22] To make sure that no fire remains, walls, ceilings and other structural components are checked during overhaul and opened where necessary.[1] Thermal imaging cameras, which detect temperature differences through smoke and darkness, are used among other things to search for hidden fire in concealed spaces.[23]

Cross-section of a fire-damaged room showing hidden fire in a ceiling void and wall cavity and smouldering furniture, with overhaul actions
Places where fire can survive after the main fire is out, and the overhaul actions that address them.

Outdoor fuels behave in a similar way. In forest fuels, apparently dead fires often reignite, because enough heat can remain even when neither flames nor smoke are visible. To prevent this, an experienced firefighter feels out the fuels by hand before leaving. If heat is still present, the danger of reignition exists and the control job is incomplete.[24]

Methods and case examples

In sprinklered warehouses, fire control by sprinklers still calls for manual final extinguishment. J. Moore (2008) describes overhaul in a warehouse as breaking open smouldering pallets, extinguishing residual fire inside loads, and then removing them from the building. Where possible, this is done under the protection of operating sprinklers, and at the very least several charged hose lines must be available.[5]

High-rack storage makes the work harder. Firefighters and hose lines may have to reach levels of 30 ft (9.1 m) or 80 ft (24.4 m), a problem that the pre-incident plan must address and that should be practised in on-site drills.[25] Ground ladders inside buildings are generally limited to the length of a typical fire department ladder, and stock wetted by sprinklers and hose streams often falls from the racks.[26]

Fire may rekindle when cartons of stock are broken open during overhaul. J. Moore (2008) therefore sets basic rules for shutting down sprinklers. The sprinklers stay on until extinguishment is positively determined, charged hose lines must be in place before they are shut down, and a person with a radio waits at the control valve to reopen it. The system is restored to full operation as soon as possible.[25]

Flowchart of the rules for shutting down sprinklers during warehouse overhaul and reopening the valve if fire rekindles
Basic rules for shutting down sprinklers during overhaul of a warehouse fire (US practice, 2008).

For established fires in large quantities of plastics, FM Global Research, as described by Benedetti and Colonna (2008), recommends "buttoning up" the building and letting the sprinklers work for hours if necessary before final mop-up. Shutting off sprinklers to vent the smoke is described as dangerous.[27] In storage facilities, the sprinkler water supply must last long enough for sprinkler control, manual fire fighting and mop-up. Golinveaux (2008) gives two hours as typical, or 90 minutes where a central station monitors the fire alarms.[28] Materials-handling equipment and qualified operators are needed to move stock during overhaul and salvage, and the operators may need training in breathing apparatus.[29] Manual roof vents in a sprinklered building can also be used during manual overhaul.[30]

Case reports show how long overhaul can take. On 10 September 1985, two sprinklers extinguished a fire in a dumpster on the 43rd floor of WTC 1, and the FDNY used a standpipe line during overhaul.[31] At a sprinklered records storage building in Chicago in October 1996, the fire was under control after nearly 10 hours. A full box alarm assignment then worked on overhaul for more than 24 hours.[32] The Chicago Fire Department kept the sprinklers discharging for days, while contractors overhauled and removed the contents with heavy equipment.[33] In a separate discussion of records storage in caverns, Beals (2008) says that a fire controlled by sprinklers still requires fire department overhaul and extinguishment, smoke removal and data recovery.[32]

Electric vehicles add a new problem. A Dutch study by the Netherlands Institute for Public Safety (NIPV) notes that the energy remains in an extinguished battery, so that the fire can keep reigniting for several hours.[34] The report separates putting out the flames from the long-term cooling of the battery pack, and stresses continuous temperature monitoring.[35] To prevent a new fire in the car park, the vehicle may be removed by the fire service and a vehicle salvage company, then cooled in an immersion container. Covering the car with foam is not useful, because the fire can reignite under the foam.[35][36] At the Singelgarage fire in Alkmaar on 1 July 2020, a police robot towed away an electric car whose battery kept reigniting.[37]

Flowchart of post-fire handling of an electric car: put out flames, cool and monitor the battery, remove the car, immerse it
Post-fire handling of an electric vehicle in an indoor car park (Dutch practice, 2021).

Hazards to firefighters

Overhaul takes place in a contaminated atmosphere. Klaene and Sanders (2008) warn that opening concealed areas releases smoky, toxic and smouldering materials into the work area, and that ceilings, walls and floors may contain asbestos. Firefighters and fire investigators working inside must therefore stay in full protective gear, including Self-contained breathing apparatus, until the building is completely free of smoke and airborne contaminants.[1] Benedetti (2008) counts toxic effects on firefighters during overhaul among the post-fire effects of smoke, although that term more usually refers to smoke damage to sensitive equipment.[38]

Smouldering material is a source of Carbon monoxide. Gann and Bryner (2008) explain that carbon monoxide is produced by both smouldering and flaming combustion. Smouldering produces it slowly, but without vigorous mixing with room air, so lethal concentrations can build up near the source within 10 minutes. Elsewhere in the room this may take 1 to 3 hours.[39] Ohlemiller (2002) adds that smouldering typically converts a substantially larger fraction of the fuel to toxic compounds than flaming does, though more slowly.[15] For plastics in commercial use, Benedetti and Colonna (2008) state that the carbon monoxide hazard greatly outweighs the toxic effects of other fire gases.[27]

Heat and structure pose further risks. Massive concrete stores heat that is not available to extend the fire, but Corbett (2008) warns that this retained heat may cause serious health hazards to firefighters during operations and overhauling.[40] Breathing apparatus rated for 30 to 45 minutes probably lasts only half as long during strenuous work.[29] Sprayed-on fire protection on steel can be dislodged easily during fire-fighting and overhaul. A complete examination of the structure is then needed to find the extent of the damage.[41]

Overhaul and fire investigation

In the United States, the local fire department generally has the primary responsibility to document a fire and to make an initial determination of its origin and cause.[42] Custer and Sheppard (2008) stress that burn patterns represent the total burning history of the event, including damage that may have occurred during extinguishment and overhaul. Patterns from fires extinguished early are more meaningful than those left after near-total destruction.[7]

In Fire investigation, investigators are advised to interview the fire department crews about their actions, because some damage may have been caused by fire fighting and overhaul rather than by the fire.[43] Ventilation, fire-fighting activities and overhaul are among the factors that can alter the patterns seen by investigators.[7] The timing also has a legal side. Under US practice, exigent circumstances exist while the fire department retains custody of the scene, and they often end with any break in the on-scene presence of fire department personnel. The allowable duration depends on the jurisdiction.[44]

Ending operations and liability

Klaene and Sanders (2008) link the decision on re-entry to the size-up before overhaul: where damage to structure and contents is minor, occupants may sometimes be allowed back in.[1] Before occupancy is permitted, Pessiki (2008) considers it imperative to check that the fire damage does not impair the integrity of zones of safety, means of egress and smoke towers. The operation of fire doors, fire dampers and other protective systems in undamaged areas must also be confirmed.[41] Sprinkler systems shut down during overhaul are to be restored to full operation as soon as possible.[25]

Rekindled fires have led to legal claims in the United States. Brodoff (2008) cites a Maryland case in which negligence was alleged in the failure to properly control and extinguish a brush fire. The fire reignited and caused a second fire that destroyed a warehouse.[45] In another US case, firefighters restored power to a warehouse after the fire without first having the electrical system checked or obtaining a permit. The fire rekindled and destroyed the building.[8] The court refused immunity, because the building code and fire department policy prohibited restoring power in that way.[8]

A records fire in 2000 shows the steps that can follow extinguishment. After a fire at the US National Archives' Washington Regional Records Center in February 2000, employees moved smouldering boxes out while the fire was still being fought. Once it was out, fire watches were set, cleanup started and drying equipment was ordered. About 100 m³ of records were wetted, but only about 50 boxes were lost.[33] In wildland firefighting, the incident commander takes steps to ensure that the fire has been extinguished before the area is abandoned.[14]

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 Klaene and Sanders (2008), p. 13-10.
  2. ↑ 2.0 2.1 Comly (2008), p. 11-42.
  3. ↑ 3.0 3.1 Ohlemiller (2002), p. 2-206.
  4. ↑ 4.0 4.1 Corbett (2008), p. 12-135.
  5. ↑ 5.0 5.1 J. Moore (2008), pp. 20-174–20-175.
  6. ↑ Denlinger (2008), pp. 12-63–12-64.
  7. ↑ 7.0 7.1 7.2 Custer and Sheppard (2008), p. 3-35.
  8. ↑ 8.0 8.1 8.2 Brodoff (2008), p. 12-103.
  9. ↑ Klaene and Sanders (2008), p. 13-5.
  10. ↑ J. Moore (2008), p. 20-173.
  11. ↑ Van Rossum (2027), §4.11.
  12. ↑ Snyder (2008), p. 12-194.
  13. ↑ Snyder (2008), p. 12-196.
  14. ↑ 14.0 14.1 14.2 Smalley (2008), p. 13-71.
  15. ↑ 15.0 15.1 15.2 15.3 Ohlemiller (2002), p. 2-200.
  16. ↑ Van Rossum (2027), §4.1.
  17. ↑ Yu and Newman (2008), p. 2-87.
  18. ↑ Scheffey (2008), p. 17-48.
  19. ↑ Nowlen et al. (2005b), p. 11-12.
  20. ↑ Nowlen et al. (2005b), p. 11-29.
  21. ↑ Gray (2002), p. 2-212.
  22. ↑ Corbett (2008), p. 12-133.
  23. ↑ Duggan (2008), p. 12-87.
  24. ↑ Smalley (2008), p. 13-58.
  25. ↑ 25.0 25.1 25.2 J. Moore (2008), p. 20-175.
  26. ↑ J. Moore (2008), p. 20-164.
  27. ↑ 27.0 27.1 Benedetti and Colonna (2008), p. 6-230.
  28. ↑ Golinveaux (2008), p. 16-85.
  29. ↑ 29.0 29.1 J. Moore (2008), p. 20-174.
  30. ↑ Heskestad (2008), p. 18-70.
  31. ↑ Kuligowski et al. (2005), p. 8.
  32. ↑ 32.0 32.1 Beals (2008), p. 9-115.
  33. ↑ 33.0 33.1 Beals (2008), p. 9-116.
  34. ↑ Sun et al. (2020), as cited in Van der Graaf et al. (2021/2023), p. 26.
  35. ↑ 35.0 35.1 Van der Graaf et al. (2021/2023), p. 46.
  36. ↑ Van der Graaf et al. (2021/2023), p. 47.
  37. ↑ Van der Graaf et al. (2021/2023), p. 12.
  38. ↑ Benedetti (2008), p. 6-8.
  39. ↑ Gann and Bryner (2008), p. 6-12.
  40. ↑ Corbett (2008), p. 12-136.
  41. ↑ 41.0 41.1 Pessiki (2008), p. 19-72.
  42. ↑ Custer and Sheppard (2008), p. 3-31.
  43. ↑ Custer and Sheppard (2008), p. 3-34.
  44. ↑ Custer and Sheppard (2008), p. 3-33.
  45. ↑ Brodoff (2008), pp. 12-100–12-101.

References

  • Beals, J. A. (2008). Protection of records. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-105–9-117). National Fire Protection Association.
  • Benedetti, R. P. (2008). Fire hazards of materials. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-3–6-9). National Fire Protection Association.
  • Benedetti, R. P., & Colonna, G. R. (2008). Polymeric materials. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-209–6-231). National Fire Protection Association.
  • Brodoff, M. (2008). Liability of fire service organizations for negligent fire fighting. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 12-99–12-106). National Fire Protection Association.
  • Comly, A. M., Jr. (2008). Building and site planning for fire safety. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-39–11-45). National Fire Protection Association.
  • Corbett, G. P. (2008). Effect of building construction and fire protection systems on fire fighter safety. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 12-127–12-141). National Fire Protection Association.
  • Custer, R. L. P., & Sheppard, D. T. (2008). Fire loss investigation. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-31–3-41). National Fire Protection Association.
  • Denlinger, R. F. (2008). Managing fire-rescue departments. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 12-51–12-78). National Fire Protection Association.
  • Duggan, B. P. (2008). Information management and computer technology. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 12-79–12-97). National Fire Protection Association.
  • Gann, R. G., & Bryner, N. P. (2008). Combustion products and their effects on life safety. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-11–6-34). National Fire Protection Association.
  • Golinveaux, J. E. (2008). Sprinkler systems for storage facilities. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 16-71–16-89). National Fire Protection Association.
  • Gray, B. (2002). Spontaneous combustion and self-heating. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-211–2-228). National Fire Protection Association; Society of Fire Protection Engineers.
  • Heskestad, G. (2008). Venting practices. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 18-57–18-72). National Fire Protection Association.
  • Klaene, B. J., & Sanders, R. (2008). Fireground operations. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 13-3–13-11). National Fire Protection Association.
  • Kuligowski, E. D., Evans, D. D., & Peacock, R. D. (2005). Post-construction fires prior to September 11, 2001 (NIST NCSTAR 1-4A). National Institute of Standards and Technology.
  • Moore, J. (2008). Storage occupancies. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-157–20-178). National Fire Protection Association.
  • Nowlen, S. P., Najafi, B., Wyant, F. J., Forester, J., Kazarians, M., Kolaczkowski, A., Joglar, F., Funk, D., Hannaman, G., & Anoba, R. (2005b). EPRI/NRC-RES fire PRA methodology for nuclear power facilities: Vol. 2. Detailed methodology (NUREG/CR-6850; EPRI 1011989). Electric Power Research Institute; U.S. Nuclear Regulatory Commission, Office of Nuclear Regulatory Research.
  • Ohlemiller, T. J. (2002). Smoldering combustion. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-200–2-210). National Fire Protection Association; Society of Fire Protection Engineers.
  • Pessiki, S. (2008). Analyzing structural fire damage. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 19-65–19-76). National Fire Protection Association.
  • Scheffey, J. L. (2008). Foam extinguishing agents and systems. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-45–17-70). National Fire Protection Association.
  • Smalley, J. C. (2008). Wildland fire management. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 13-53–13-79). National Fire Protection Association.
  • Snyder, M. (2008). Industrial fire loss prevention. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 12-177–12-198). National Fire Protection Association.
  • Van der Graaf, J., Hessels, T., & Rosmuller, N. (2023). Fire safety of indoor car parks accommodating electrically powered vehicles. Nederlands Instituut Publieke Veiligheid. (Original work published 2021)
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.
  • Yu, H.-Z., & Newman, J. S. (2008). Theory of fire extinguishment. In A. E. Cote, C. C. Grant, J. R. Hall, Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-79–2-92). National Fire Protection Association.