A chemical laboratory is a facility in which chemicals are handled in containers designed to be manipulated easily and safely by one person, for reactions, transfers and other handling.[1] In the United States, NFPA 45, Standard on Fire Protection for Laboratories Using Chemicals, sets out fire-protection provisions for these laboratories. Production or synthesis in larger containers or quantities falls under manufacturing or pilot-plant operations instead. Laboratories combine the population density of an office building with hazards that resemble those of an industrial site using flammable liquids.[1]

The 20th edition of the NFPA Fire Protection Handbook (2008) bases protection on a risk assessment with hazard classification, prevention procedures, fire separation, fire protection systems, ventilation and explosion protection.[1] NFPA 45 sorts laboratory units into four fire hazard classes, A to D, and limits the quantity of flammable and combustible liquids in each class per unit of floor area.[2][3] Typical protection includes automatic sprinklers, laboratory fume hoods, storage cabinets, careful separation of incompatible chemicals and emergency plans that warn responders of unusual hazards.

Definition and scope

NFPA 45 defines a laboratory by the scale at which chemicals are handled. The containers used for reactions, transfers and other handling are designed to be easily and safely manipulated by one person.[1] Operations that produce or synthesise chemicals in larger containers or quantities are treated as manufacturing or pilot plants and fall outside NFPA 45.

Laboratories mix office-type occupancy with industrial-type hazards. The population density of a laboratory is similar to that of an office building, while its hazards can resemble those of an industrial site.[1] Because of the flammable or hazardous materials they use, laboratories are typically classified as "industrial" by NFPA 101, Life Safety Code.[2] Laboratories that do not involve hazardous chemicals are instead counted among business occupancies.[4] In schools, laboratories are treated as hazardous areas, often separated by fire-rated walls and doors. Their occupant load factor is 4.6 m² (50 ft²) net per person, against 1.9 m² (20 ft²) for classrooms.[5]

Hazards in laboratories

Laboratory operations can involve toxins, corrosives, ionising and nonionising radioactive materials, flammable liquids and gases.[6] Distillations heat flammable liquids above their boiling point, under pressure or under vacuum, and some high-pressure reactions involve hydrogen or other flammable gases. The resulting accidents include rapidly spreading flammable liquid fires, explosions and exposure to highly toxic materials. The handbook names flammable liquids and gases, reactions and distillations as the high-risk operations, and notes that distilling a flammable liquid in a 19 L (5 gal) glass vessel is not unusual.[6]

Flammable liquids and their vapours

The fire hazard of a flammable liquid comes from its vapour rather than from the liquid itself.[7] A liquid must first become a gas or mist before it can burn, and in a pool fire this happens by evaporation.[8] The flash point is the temperature at which the vapour-air mixture just above the liquid supports a momentary flash when a small pilot flame is passed over it.[9] Closed-cup tests give lower flash points than open-cup tests. For the hydrocarbon liquids tabulated in the SFPE Handbook, the fire point, at which burning continues, lies about 20 to 40 °C higher.[9] Ignitable mixtures exist only within the flammable range; for ethyl alcohol it runs from about 4 to 19 percent by volume.[7]

NFPA 45 uses the classification of NFPA 30, which is essentially the same as that of OSHA.[10] A flammable (Class I) liquid has a closed-cup flash point below 37.8 °C (100 °F) and a Reid vapour pressure no greater than 276 kPa (40 psia) at that temperature.[10][11] The flash-point boundary was chosen because indoor air in most areas could reach 37.8 °C at some time of the year.[11] Class IA liquids have flash points below 22.8 °C (73 °F) and boiling points below 37.8 °C. Class IB liquids have the same flash point limit but higher boiling points, and Class IC covers flash points from 22.8 to 37.8 °C.[10] Combustible liquids are Class II (37.8 to 60 °C), Class IIIA (60 to 93 °C) and Class IIIB (93 °C or above).[10]

The table applies these limits to the flash and boiling points of liquids listed in the International Fire Engineering Guidelines (2005).[12] The guidelines do not state the test method, so the classes are indicative. Lower flammability limits are given for comparison.

Liquid Flash point (°C) Boiling point (°C) Lower flammability limit (vol%) Class
Diethyl ether −45 35 1.9 IA
Pentane −49 36 1.4 IA
Acetone −18 56 2.6 IB
Hexane −23 69 1.2 IB
Methanol 11 65 6.7 IB
Ethanol 13 79 3.3 IB
Toluene 4 111 1.2 IB
Styrene 31 145 1.1 IC
Acetic acid 43 118 5.4 II
Nitrobenzene 87 211 1.8 IIIA
Ethylene glycol 114 198 3.5 IIIB

Five of the eleven liquids in the table are Class IB. Their flash points lie below normal room temperature, so they give off ignitable vapour without heating, while ether and pentane even boil at about 35 °C.[12] Flames of substances that produce little soot are poorly visible, alcohol being an example, so a small solvent fire can be hard to see.[13] The flammability rating of the NFPA 704 hazard diamond, which runs from 0 to 4, follows the same idea of ease of ignition. A rating of 4 denotes materials that turn rapidly or completely to vapour at atmospheric pressure and normal ambient temperature, and 3 denotes liquids or solids that can be ignited under almost all ambient conditions.[14]

Scatter chart of boiling point against flash point with shaded regions for liquid classes IA to IIIB and labelled liquids
Flammable and combustible liquid classes by flash point and boiling point, with liquids from the International Fire Engineering Guidelines.

Reactive and incompatible chemicals

Some chemicals react dangerously when they come into contact, a property known as chemical incompatibility. Oxidising chemicals are usually not combustible themselves but supply oxygen that accelerates burning, so combustible materials and flammable liquids should not be stored with them.[15] Chlorates should not be stored with acids or combustible materials, and inorganic peroxides react with acids to give hydrogen peroxide. Water-reactive chemicals such as hydrides and alkali metals should be stored dry, and air-reactive chemicals such as aluminium alkyls must be kept away from air, in both cases without incompatible materials nearby.[16] Perchloric acid is widely used in analytical laboratories; explosions have occurred at wood and plastic laboratory hoods after long exposure to its vapours.[17]

Segregation is the first principle of good chemical storage. It can take the form of a separate building, fire walls with drainage, an intervening empty space or intervening storage of inert materials.[18] The design must also consider vessels rupturing in a fire and incompatible materials mixing. NFPA 45 requires incompatible materials to be segregated in all laboratory storage, and products kept together in a storage cabinet must be compatible.[10][3] Storage areas should display NFPA 704 signs, marked with the most severe health, flammability and instability hazard present.[18]

NFPA 704 diamond with blue health, red flammability, yellow instability and white special quadrants, with short scale explanations
The NFPA 704 hazard diamond: health (blue), flammability (red) and instability (yellow) have ratings from 0 (low) to 4 (high); the white quadrant uses special-hazard symbols.

Laboratory unit classes and allowable quantities

NFPA 45 classifies laboratory units as Class A (high fire hazard), Class B (moderate), Class C (low) or Class D (minimal).[2] Class A units may hold the largest quantities of flammable and combustible liquids and liquefied flammable gases, and Class D units the smallest. Class A and B units also face limits on their maximum area and need greater fire separation. Instructional laboratories are Class C or D, and educational laboratories are Class D or limited to 50 percent of the Class C quantity.[2] A laboratory built to a lower class may not be used for a higher-risk operation, even temporarily.[19]

The allowable quantity grows with the floor area of the unit, up to a maximum for the unit regardless of its size.[3] NFPA 45 (2004 edition), as reproduced in the handbook, gives the quantities per 9.3 m² (100 ft²) of a sprinklered unit. These values are for calculation only and do not require the liquids to be spread evenly over the floor. Larger quantities are allowed when liquids are kept in storage cabinets or safety cans.[3] The total allowed is therefore:

Vallowed=min⁡(qA9.3 m2, Vunit)

Symbol Description Unit
Vallowed Maximum quantity of liquid allowed in the laboratory unit L
q Tabulated quantity per 9.3 m² for the unit class, liquid class and storage condition L per 9.3 m²
A Floor area of the laboratory unit m²
Vunit Tabulated maximum quantity per laboratory unit L

Worked example. A sprinklered Class B unit of 200 m² uses Class I liquids. Outside cabinets and safety cans the table allows 20 L per 9.3 m², with a maximum of 1,136 L per unit.[3] The area term gives 20 × 200/9.3 = 430 L, which is below the cap, so 430 L is the limit. Including cabinets and safety cans, the values are 38 L per 9.3 m² and 2,270 L, which gives 817 L; the extra 387 L must be kept in cabinets or safety cans. For this class the cap of 1,136 L governs only above about 528 m².

Four rising lines that level off, showing allowed litres of Class I liquid against laboratory unit area for classes A to D
Maximum quantity of Class I flammable liquid outside storage cabinets and safety cans in a sprinklered laboratory unit, by unit class and floor area.

A single flammable liquid storage cabinet may hold no more than 454 L (120 gal) of Class I, II and IIIA liquids.[20] Such cabinets are typically double-walled 18-gauge sheet steel with a 38 mm (1.5 in.) air space, a three-point latch and a door sill at least 51 mm (2 in.) high to retain spills. Neither NFPA 30 nor NFPA 45 requires the cabinets to be vented.[10]

NFPA 45 also sets maximum container sizes, with extra limits for lower flash point liquids in educational and instructional laboratories.[10] Bulk stock and larger containers belong in inside liquid storage areas designed to NFPA 30.[3] Class I liquids should not be transferred between conductive containers larger than 3.8 L (1 gal) unless the containers are bonded or grounded. Dispensing to or from containers of up to 19 L (5 gal) should take place in a fume hood or in an area ventilated to keep vapour below 25 percent of the lower flammable limit.[3]

Laboratory design and passive protection

NFPA 45 sets fire separation requirements, including door and window assemblies, from the amount of flammable and combustible liquids and flammable gases in use or storage, hazardous waste included.[19] The handbook suggests working from the intended use to the chemical inventory, the in-use and storage needs and the waste. The total then gives the laboratory unit class and, from it, the allowable area and construction. The layout must also place exits, storage cabinets, spill containment, hoods, emergency showers and eyewash stations.[2]

Fires in laboratories can intensify quickly, so any delay in egress cannot be tolerated.[2] Main aisles used for emergency egress should be at least 0.91 m (36 in.) wide, and benches at least 1.5 m (5 ft) apart; 1.8 m (6 ft) is the desired spacing in teaching laboratories. A second means of access from the unit to a means of egress is required in six situations. These include a Class A work area above 46.5 m² (500 ft²), a Class B, C or D work area above 93 m² (1,000 ft²), and a hood next to the primary exit.[2]

Plan of a laboratory unit with benches, a fume hood away from the primary exit access, a storage cabinet and two access doors
Plan of a laboratory unit showing egress widths, bench spacing and the position of the fume hood and storage cabinet.

An explosion hazard that could block egress also triggers the second access. So does a compressed-gas cylinder larger than a lecture bottle holding a flammable gas or one with an NFPA 704 health rating of 3 or 4. A cylinder release that would prevent safe egress also qualifies. The sixth case is a cryogenic container with those gas or release hazards.[2]

Exit doors from Class A and B units should swing in the direction of travel and be self-closing. If the supply air stops while the hoods keep exhausting, the room can reach such a negative pressure that the door is very hard to open.[2] Solvents should not be stored under a fume hood, because that is where laboratory fires are most likely to start.[19] Benches should be noncombustible and nonporous; wood is porous and combustible, and fibreglass can degrade under strong disinfectants and release toxic smoke when ignited. Electrical work follows NFPA 70, with receptacles and switches kept away from spill areas and enough outlets to avoid extension cords.[19]

Where the hazard assessment finds an explosion hazard, such as rupture of apparatus, an overpressurised system or implosion under vacuum, the occupants must be protected.[6] Options include explosion venting, special protected enclosures for vacuum and distillation equipment, and isolating high-risk work in specially designed buildings. Deflagration venting directs expanding gases out of an enclosure to a safe location, and suits cases where toxicity and environmental contamination are not a concern.[21] It is one of four protection strategies, with pressure containment, suppression and isolation.[22]

Ventilation and laboratory hoods

Laboratories must be ventilated continuously and are kept at negative pressure relative to the rest of the building, with some exceptions.[23] Supply air must not bring toxic or flammable vapours back into the room, so fresh air intakes are placed well away from exhaust discharges. Vapours from normal work are removed with nonrecirculated air through hoods and local exhaust.[6] Canopy hoods, biological cabinets and laminar flow cabinets serve other purposes and cannot replace laboratory hoods.[6]

Work with toxic or flammable materials in quantities that cannot be handled safely in the open room belongs in a laboratory fume hood. Modern hoods work under negative pressure with face velocities of 0.41 to 0.61 m/s (80 to 120 ft/min), most often 0.5 m/s.[23] Hood ducts must be noncombustible, and automatic fire dampers should not be placed in them. The building fire alarm should not shut down hood exhaust, because that could cause a dangerous build-up of vapours. Hoods for perchloric acid must be dedicated to that use and fitted with a water spray wash-down system.[23]

Active fire protection

The 2004 edition of NFPA 45 added a requirement for automatic fire-extinguishing systems in all new laboratories.[24] Class A and B laboratories should be protected as ordinary hazard (Group 2) and Class C and D laboratories as ordinary hazard (Group 1) under NFPA 13. A study by the US National Institute of Standards and Technology showed that quick-response sprinklers controlled flammable liquid test fires in laboratories more quickly than standard-response sprinklers.[24] Accidental discharge onto sensitive equipment is a common concern, but such discharges are almost nonexistent apart from mechanical damage, which concealed heads prevent, and microbiologically induced corrosion.

Sprinklers need not be extended into hoods unless an existing hood used for flammable liquids has an interior flame spread index above 25, or a hazard assessment calls for it.[24] Where hood protection is provided, tests showed sprinklers with water mist nozzles to be the most effective option when nonthermal damage outside the hood matters. Even with water-reactive chemicals present, the reaction is not severe enough to rule out water on a flammable liquid fire in a hood, provided the hood is not used for significant open storage. Clean agents are less suitable: fire tests in the United Kingdom showed that they break down into significant toxic by-products in flames, and the hood must be shut down for them to work.[24]

Laboratory buildings with two or more storeys above or below ground need standpipes.[24] Portable extinguishers can control a small incipient fire, but a flammable liquid or chemical fire can be dangerous for an untrained operator. Staff designated to use extinguishers therefore need hands-on and go/no-go training. Where a risk assessment, hazard class or code calls for a fire alarm system, it must follow NFPA 72 and alert everyone who may be affected.[24]

Procedures and emergency planning

The handbook lists four kinds of risk reduction in order of preference.[6] Inherent safety removes the hazard, for example by using supercritical carbon dioxide instead of hexane for extraction. Passive measures, such as a reactor built to contain its maximum overpressure or a fire-rated wall, need no device to work. Active measures, such as sprinklers, must be reliably designed, installed and maintained, while procedures cover chemical handling, open flames, extension cords and maintenance.[6]

Hazardous chemicals such as flammable solids, oxidisers and organic peroxides may only enter a laboratory designed and protected for their quantity and hazard, and should be kept to the minimum needed.[25] Gas cylinders should also be kept to a minimum. Lecture bottles of pyrophoric gases, gases with a health rating of 3 or 4, or gases rated 2 without physiological warning properties need continuously ventilated enclosures. Larger cylinders with similar hazards need ventilated gas cabinets, and cabinets for pyrophoric gases need internal sprinklers.[25] Shelves need lips of at least 19 mm (¾ in.) against seismic shaking and should not be placed above sinks, and an inventory system should track chemicals in and out.[10]

Responders to a laboratory fire may meet poisons, corrosives, irritants, radioactivity, nonionising radiation and biological hazards.[23] Laboratories using radioactive materials must be identified in the emergency plan. Management should encourage the public fire department to learn these hazards through inspections, joint planning and drills. Entrances to laboratory units and storage areas should carry signs that warn of unusual or severe hazards, although NFPA 45 endorses no single convention for them.[10] Each laboratory needs an evacuation plan that also covers spills and releases, and fire exit drills should be held at least once a year.[10]

These requirements describe US practice as summarised in 2008, with NFPA 45 in its 2004 edition; later editions and other countries may differ. The quantity table reproduced in the handbook covers sprinklered units only. A risk assessment should identify the critical operations, such as reactions and distillations, and NFPA standards are minimum requirements rather than best practice.[6][25]

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 1.4 Anderson (2008a), p. 9-157.
  2. ↑ 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 Anderson (2008a), p. 9-158.
  3. ↑ 3.0 3.1 3.2 3.3 3.4 3.5 3.6 Anderson (2008a), p. 9-164.
  4. ↑ Marburger (2008), p. 20-105.
  5. ↑ Szachnowicz (2008), p. 20-120.
  6. ↑ 6.0 6.1 6.2 6.3 6.4 6.5 6.6 6.7 Anderson (2008a), p. 9-161.
  7. ↑ 7.0 7.1 Slye (2008), p. 6-197.
  8. ↑ Van Rossum (2027), §4.1.
  9. ↑ 9.0 9.1 Kanury (2002b), p. 2-190.
  10. ↑ 10.00 10.01 10.02 10.03 10.04 10.05 10.06 10.07 10.08 10.09 Anderson (2008a), p. 9-163.
  11. ↑ 11.0 11.1 Slye (2008), p. 6-198.
  12. ↑ 12.0 12.1 National Research Council of Canada et al. (2005), pp. 3.3-2–3.3-3.
  13. ↑ Van Rossum (2027), §4.3.
  14. ↑ C. J. Wright (2008a), p. 13-123.
  15. ↑ Davenport (2008), p. 7-45.
  16. ↑ Davenport (2008), p. 7-50.
  17. ↑ Davenport (2008), p. 7-52.
  18. ↑ 18.0 18.1 Davenport (2008), p. 7-44.
  19. ↑ 19.0 19.1 19.2 19.3 Anderson (2008a), p. 9-159.
  20. ↑ Ordile (2008), p. 7-28.
  21. ↑ Ural and Garzia (2008), p. 17-155.
  22. ↑ Ural and Garzia (2008), p. 17-154.
  23. ↑ 23.0 23.1 23.2 23.3 Anderson (2008a), p. 9-162.
  24. ↑ 24.0 24.1 24.2 24.3 24.4 24.5 Anderson (2008a), p. 9-160.
  25. ↑ 25.0 25.1 25.2 Anderson (2008a), p. 9-165.

References

  • Anderson, R. R. (2008a). Fire protection of laboratories using chemicals. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-157–9-166). National Fire Protection Association.
  • Davenport, J. A. (2008). Storage and handling of chemicals. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-43–7-55). National Fire Protection Association.
  • Kanury, A. M. (2002b). Ignition of liquid fuels. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-188–2-199). National Fire Protection Association; Society of Fire Protection Engineers.
  • Marburger, B. L. (2008). Business occupancies. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-105–20-113). National Fire Protection Association.
  • National Research Council of Canada, International Code Council, Department of Building and Housing, & Australian Building Codes Board. (2005). International fire engineering guidelines (2005 ed.). Australian Building Codes Board.
  • Ordile, A. M. (2008). Storage of flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-15–7-33). National Fire Protection Association.
  • Slye, O. M., Jr. (2008). Flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-197–6-208). National Fire Protection Association.
  • Szachnowicz, A. L. (2008). Educational occupancies. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-115–20-122). National Fire Protection Association.
  • Ural, E. A., & Garzia, H. W. (2008). Explosion prevention and protection. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-141–17-165). National Fire Protection Association.
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.
  • Wright, C. J. (2008a). Managing the response to hazardous material incidents. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 13-117–13-144). National Fire Protection Association.