An industrial oven and furnace is an enclosed heating chamber in which industrial materials are baked, dried, cured, annealed, melted or otherwise heat-treated. The heat comes from gas or oil burners, electric heaters, steam or a heat transfer fluid. The Fire Protection Handbook (2008) treats ovens, furnaces, dryers, kilns and related plant together as heat utilisation equipment, whose hazards come both from the heat source and from the materials being processed.[1] There is no sharp boundary between an oven and a furnace. An industry rule of thumb calls equipment running below about 540 °C (1000 °F) an oven, but coke ovens run above 1093 °C (2000 °F).[2]

The main fire and explosion danger is a flammable mixture inside the enclosure, formed either by unburned fuel or by solvent vapours released from the work. In the United States, NFPA 86, Standard for Ovens and Furnaces, as summarised in the 2008 handbook, divides such equipment into Classes A to D. Its protection rests on safety ventilation, combustion safeguards, explosion relief vents and trained operators.[2][3][4] The values in this article describe US practice as printed in the 2008 handbook, not current or universal requirements.

Classification and types

The handbook quotes the NFPA 86 classification by hazard. A Class A oven or furnace operates at approximately atmospheric pressure and contains a potential explosion or fire hazard from flammable volatiles or combustible material that is processed or heated in it.[2] Typical sources of such volatiles are paints, powders and finishing processes, dipped or coated materials, wooden or plastic pallets and packaging, and resin curing or polymerisation that releases flammable residues.[5] Curing ovens downstream of finishing lines are generally classified as continuous Class A ovens.[6] Ovens for powder coating and for the drying of dip-coated parts belong to the same group.[5]

A Class B oven or furnace also operates at about atmospheric pressure, but no flammable volatiles or combustible material are heated in it. A Class C furnace uses a flammable or other special atmosphere for the treatment of the work, and includes integral quench and molten salt bath furnaces. A Class D furnace is a vacuum furnace operating below atmospheric pressure at temperatures from above ambient to over 2760 °C (5000 °F). During gas quenching its pressure may rise to over 7 bar (100 psig).[5] A 2004 report of the US Nuclear Regulatory Commission lists separate 1999 editions of NFPA 86, NFPA 86C for special-atmosphere furnaces and NFPA 86D for vacuum furnaces.[7]

Decision chart sorting ovens and furnaces into NFPA 86 Classes A, B, C and D by pressure and atmosphere
Classes of ovens and furnaces under NFPA 86 as summarised in the 2008 handbook.

Ovens and furnaces are also grouped by how the work moves. In a batch oven, also called an "in and out", intermittent or periodic oven, the work stays in one position at a nearly constant temperature and leaves through the opening by which it entered. In a continuous oven the work travels through the chamber on a conveyor or rollers, sometimes through zones held at different temperatures; the rotating hearth furnace is a common variant.[5]

Heating systems

Heat can come from gas-fired burners, oil-fired burners, electric heating, steam coils or a heat transfer fluid system.[8] In a direct-fired oven the products of combustion enter the work chamber and touch the work. In an indirect-fired oven the heat arrives by radiation from tubes or by air that passes over heated tubes, so a dangerous fuel-air mixture cannot readily fill the work space. Vapour explosions from a drying process remain possible in both types.[8]

Two oven cross-sections: direct-fired with flue gas in the work chamber, and indirect-fired with gastight radiator tubes
Direct-fired and indirect-fired external oven heaters.

Furnaces use similar arrangements with their own names. Combustion products that rise from under the hearth define an underfired furnace. Products passing over a bridge wall from a side chamber define a side-fired furnace, and products entering through a perforated arch an overfired furnace. In a reverberatory furnace an arched roof deflects the combustion products onto the hearth, and in a muffle furnace a metal or refractory muffle separates them from the work.[8]

Electric ovens and furnaces use one of five principles: resistance, infrared, induction, arc or dielectric heating, the last at frequencies of generally 3 MHz or more.[9][10] Unenclosed "ovenless" electric systems also exist. The handbook advises an enclosure where they drive off flammable, toxic or corrosive vapours, but systems below 100 kW may be excluded if the area ventilation is adequate.[10] Steam coils should run at the lowest pressure that gives the required drying temperature and must not sit where paint drippings or lint can collect on them.[10]

Fire and explosion hazards

The 2008 handbook names the prevention of overheating, and of any accumulation of a gas or vapour-air mixture in the explosive range, as the principal method of preventing fire or explosion.[1] Fires in nearby combustibles are prevented by insulation and separation, and overheating by temperature controls. Explosions require a flammable vapour-air mixture from gas or oil fuel or from volatiles released by the material being dried.[2] The underlying idea of a mixture between its lower and upper flammability limits that is ignited inside a confining enclosure is the general description of a gas or vapour explosion.[11]

Fuel hazards arise in three phases, each of which needs its own procedure: lighting off, firing and shutting down.[10] During firing, a mixture velocity that is too high blows the flame off the burner, while one that is too low lets it flash back. A partial failure of combustion air gives an over-rich flame and incomplete combustion; the ignitable products can later be diluted by air into the flammable range inside the oven or ductwork and explode.[3] After shutdown, fuel from open or leaking manual valves, or from safety shutoff valves that do not close tightly, can accumulate and be ignited by hot refractory during the next start-up.[3] Fuel oil must be atomised to burn well, and improper oil temperature, high viscosity or water in the line can cause an unstable flame and flame failure.[3]

Class C furnaces add the hazard of the special atmosphere. Hydrogen, dissociated ammonia, incompletely burned hydrocarbon gas, carbon monoxide and methane form flammable atmospheres, while inert atmospheres of carbon dioxide, helium, argon or nitrogen pose no special fire hazard but can be a health hazard.[4] The danger is greatest at three moments: when the flammable atmosphere replaces air at the start, when air is readmitted at the end, and when the atmosphere supply fails and air can enter.[4] Vacuum furnaces share these hazards and add their own, such as explosions from water leaking out of heating elements or jackets and the explosion of diffusion pump oil when air enters a hot pump.[12]

The explosion hazard of solvent ovens rises with temperature, because the lower flammable limit (LFL) of a vapour falls as the mixture is heated. A table in the handbook gives, for example, an LFL for toluene of 1.17 % by volume at room temperature, 0.99 % at 100 °C and 0.82 % at 200 °C.[13] Beyler explains this with a nearly constant adiabatic flame temperature of about 1600 K at the LFL for most fuels containing carbon, hydrogen and oxygen. In his worked example the LFL of propane falls from 2.1 % at 20 °C to 1.8 % at 200 °C.[14] He adds that the approach fails near or above the autoignition temperature, where reactions start before the flame.[14] The handbook table marks several of its highest-temperature values with a note on rapid thermal decomposition and oxidation in the mixture.[13]

Safety ventilation

Safety ventilation dilutes solvent vapour with fresh air and carries it outdoors. The handbook states that ventilation and controls keeping the flammable vapour content below 25 % of the LFL prevent explosions and fires.[2] A waste-handling chapter of the same handbook gives the range for oven and furnace vapours as below 50 %, and usually less than 25 %, of the lower explosive limit (LEL), a synonym of the LFL.[15][16] Mechanical ventilation to outdoors is required on all ovens that release flammable or toxic vapours and on direct-fired gas or oil ovens. Ovens that never release such vapours and are heated indirectly, electrically or by steam need no safety ventilation.[17] Failure of the ventilation fan shuts down the heating system and the conveyor of a continuous oven.[18]

For continuous conveyor ovens the handbook's general rule is at least 283 m³ (10,000 ft³) of fresh air at 21 °C (70 °F) for each 3.79 L (1 gal) of common solvent. One gallon of common solvent forms roughly 71 m³ (2500 ft³) of the leanest explosive mixture. The rule applies a factor of four because part of the air bypasses the zone where the vapour is released.[17] For batch ovens baking dip-coated metal, experience supports about 10.7 m³/min (380 ft³/min) at 21 °C for each 3.79 L of flammable volatiles in the batch. The handbook warns that work of low mass, such as paper or textiles, and coatings with highly volatile solvents can give peak evaporation rates beyond this estimate.[17] NFPA 86, as described by Cholin, allows lower airflow rates where a system monitors the vapour concentration in the ventilation air, which makes that monitoring system part of the fire protection of the oven.[19]

Where the solvent and the evaporation rate are known, the dilution air can be calculated. The volume of vapour from one litre of liquid follows from the specific gravity of the liquid and the vapour density relative to air. The air needed to bring this vapour just down to the LFL follows from the fraction of air in a limit mixture.[16] The design air flow multiplies this by the evaporation rate and by the factor of four. It is then corrected to oven temperature, because gas volume is proportional to absolute temperature.[17]

Vv=0.83SGVD Va=Vv100−LFLLFL Qoven=4r˙VaTovenT0

Symbol Description Unit
Vv Volume of vapour produced by one litre of liquid solvent m³/L
SG Specific gravity of the liquid (water = 1) –
VD Vapour density of the vapour (air = 1) –
Va Volume of air that dilutes the vapour of one litre to the LFL m³/L
LFL Lower flammable limit at the relevant temperature % by volume
r˙ Solvent evaporation rate in the oven L/min
Qoven Ventilation air flow at oven temperature, with a factor of four m³/min
Toven, T0 Absolute oven temperature and absolute fresh-air temperature K

The constant 0.83 is the SI counterpart of the factor 111 in the US form. The handbook derives that factor from the weight of a gallon of water (8.33 lb) and of a cubic foot of air (0.075 lb).[16] Acetone has a specific gravity of 0.792, a vapour density of 2 and a flammable range of 2.6 % to 12.8 %. The handbook finds 0.33 m³ of vapour per litre and about 37 volumes of air per volume of vapour, so diluting one litre to the LFL takes 12.2 m³ of air.[16]

As a worked example, suppose a continuous oven at 149 °C (422 K) evaporates 2 L/min of acetone, with fresh air at 21 °C (294 K). The air flow to reach the LFL is 2 × 12.2 = 24.4 m³/min at 21 °C, and the factor of four raises this to about 98 m³/min. Correcting to oven temperature gives 98 × 422/294 ≈ 140 m³/min of exhaust, at a concentration of about 26 % of the room-temperature LFL. The general rule of 283 m³/min per 3.79 L/min would have demanded about 150 m³/min at 21 °C, which shows the margin the rule contains for acetone. The same temperature ratio appears in the handbook's own example, where 283 m³ of fresh air at 21 °C becomes 406 m³ at 149 °C.[17]

The calculation is only as good as its inputs. The handbook stresses that solvent characteristics, oven type, the material, the oven temperature and the effect of temperature on the LFL must all be considered.[17] For acetone the tabulated LFL drops from 2.67 % at room temperature to 2.40 % at 100 °C, which raises the required air by about 12 %.[13] In practice a substantial excess of air is applied because the atmosphere in an enclosure is never uniform.[13]

Line chart of lower flammable limit against temperature for five solvents, all falling as temperature rises
Lower flammable limit of five solvents at elevated temperature.

Low-oxygen ovens take the opposite route. They evaporate solvent in an inert carrier gas whose oxygen content is held below that needed for combustion, for some solvents about 8 % oxygen including a safety factor of about 3 %, which requires oxygen analysers.[17] A bleed stream of typically 1 % of the recirculated gas passes through a solvent recovery unit, where the solvent is condensed, before the stripped inert gas returns to the oven.[4]

Combustion safeguards and supervisory controls

The handbook states that every oven or furnace that processes flammable materials or burns combustible fuel needs listed supervisory devices to ensure preventilation, ventilation during operation and safe operating conditions.[3] Before an ignition source is introduced, possible accumulations of unburned fuel are purged, burners are lit promptly with substantial igniters, and the purge is repeated before any further attempt.[10]

Full supervision of a gas- or oil-fired oven may require four steps in sequence. All fuel valves are proved closed and tight, and ventilation is established. The pilot is lit only after the preventilation period, and the main fuel valves open only after a combustion safeguard proves the pilot flame and correct fuel and air pressures.[3] If the main flame is not established promptly, the safety shutoff valve closes and the full cycle starts again. This flame-proving function is described under Flame safeguard.

Flowchart of oven start-up: valves proved closed, ventilation, preventilation, pilot, flame proved, main valves open
Supervised start-up sequence of a gas- or oil-fired oven.

The handbook lists the main devices. Ventilation is supervised by airflow and pressure switches, fan shaft rotation detectors, damper limit switches and preventilation time-delay relays. Fuel supervision uses safety shutoff valves, flame detection units, program relays, temperature and excess temperature controllers, and continuous vapour concentration controls.[3]

The handbook's typical gas train, taken from the 2003 edition of NFPA 86, shows two safety shutoff valves in series in all three capacity bands. Between 150,000 and 400,000 Btu/h (44 to 117 kW) both valves carry visual identification, and above 400,000 Btu/h one also has proof of closure.[20] The text adds that above 117 kW two safety shutoff valves are required, with a manual plug cock and test tap downstream for leak testing.[18] In multiburner Class B furnaces, combustion safeguards with flame supervision should be applied, and zones at different temperatures may have to be treated as separate units.[4]

Gas train from supply to burner with filter, regulator, pressure switches, two safety shutoff valves and leak test valves
Typical fuel gas train with two safety shutoff valves.

The chapter repeatedly states that equipment alone cannot ensure safety. It names inadequate training, faulty design, complacency and the improper selection of combustion safeguards as causes of past failures.[1] It recommends checking the controls preferably once a week, with a more thorough test by an expert probably once a year. Operator training covers combustion, explosion hazards, ignition sources, atmosphere analysis, flammable and toxic atmosphere gases and the function of safety devices.[18] Class C furnaces depend on such procedures. During an inert gas purge the oxygen content must read below 1 % in two consecutive samples, and flammable atmosphere is admitted only with at least one zone above 760 °C (1400 °F).[21]

Explosion relief and fire protection

The handbook states that ovens which might contain flammable gas or vapour mixtures must have unobstructed relief vents, panels or doors held by explosion-relieving hardware or gravity. The panels should be light enough to move at the lowest practical pressure. The preferred ratio is 0.09 m² (1 ft²) of relief area for every 0.42 m³ (15 ft³) of oven volume, about 0.22 m² per cubic metre.[4] A 20 m³ oven would thus need about 4.4 m² of relief area. Heavy Class B furnaces often cannot be vented effectively because of the weight and strength of their walls, so preventilation and interlocks carry the protection.[4] General vent sizing methods are treated under Explosion venting.

Zalosh groups explosion protection into three approaches: preventing the flammable mixture by ventilation or inerting, eliminating ignition sources, and limiting the pressure by venting or suppression.[11] One of his worked examples concerns a large process oven fired through a fuel line 1 cm in diameter and 5 m long that contains a stoichiometric premixed fuel-air mixture. For propane a detonation cannot propagate in so narrow a line. For hydrogen a detonation in the line is possible, but it cannot pass into the oven unless the line exceeds about 20 cm. Explosion venting could therefore be a viable form of protection for the oven.[22] His venting guidelines treat enclosures that fail below about 0.1 bar (1.5 psig) as low-strength enclosures.[23]

Automatic sprinklers or water spray should be considered wherever enough combustible material is present to sustain a fire, extending into the enclosure and the exhaust ducts where needed. Carbon dioxide, foam, dry chemical or halon systems may supplement sprinklers but do not replace them.[4] A US Nuclear Regulatory Commission report notes that the decomposition of Halon 1301 under intense heat makes such systems unsuitable for an oven or furnace chamber above 260 °C (500 °F).[24] Steam smothering is generally not recommended, but where there is no alternative it may be allowed above 107 °C (225 °F) when large steam supplies are always available.[4] Frank notes that systems using industrial process steam are sometimes found in industrial ovens.[25]

Location, exhaust and related plant

Ovens and furnaces should stand where they present the least hazard, at or above grade, because basements are hard to ventilate and obstruct explosion relief.[5] The oven and its building should be noncombustible, combustibles nearby should be separated or insulated, and the spaces above and below should be ventilated to keep combustible ceilings and floors below 71 °C (160 °F). Separation from valuable stock, power equipment and sprinkler risers limits interruption after an incident.[8]

Oven exhaust can be treated in an afterburner or a catalytic unit, and catalytic heaters are widely used to save oven fuel and control emissions.[26] Direct-flame units usually run at 650 to 816 °C (1200 to 1500 °F) with a dwell time of 0.4 to 0.8 s, and concentrated streams are diluted to below 50 % of the LEL before transfer.[27] Fires in ducts between the process units and the incinerator, and explosions of vapours that accumulated in them before or during start-up, have damaged such installations.[27] Combustible deposits in heat recovery exchangers can also cause fire or explosion.[28] The design of such ducts is covered under Industrial exhaust system, and dryers, which use the same burner controls with manual restart, flame failure protection and preventilation, under Industrial dryer.[29]

Limits of the rules

The ventilation rules are rules of thumb with stated limits. Some solvents render more than 71 m³ of air per gallon barely flammable, so the factor of four shrinks for them.[17] The batch rule may underestimate peak evaporation from light work or very volatile coatings,[17] and the LFL values of the handbook table apply only to the listed solvents and temperatures.[13] The values in this article are those printed in the 2008 handbook, partly taken from the 2003 edition of NFPA 86, and describe US practice of that time.[20] The chapter itself concludes that heat utilisation equipment varies too widely for any single set of rules and refers designers to NFPA 86 for the detailed requirements.[29]

See also

Notes

  1. ↑ 1.0 1.1 1.2 Ostrowski (2008a), p. 8-71.
  2. ↑ 2.0 2.1 2.2 2.3 2.4 Ostrowski (2008a), p. 8-72.
  3. ↑ 3.0 3.1 3.2 3.3 3.4 3.5 3.6 Ostrowski (2008a), p. 8-77.
  4. ↑ 4.0 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 Ostrowski (2008a), p. 8-81.
  5. ↑ 5.0 5.1 5.2 5.3 5.4 Ostrowski (2008a), p. 8-73.
  6. ↑ Cholin (2008d), p. 9-19.
  7. ↑ Iqbal and Salley (2004), p. E-4.
  8. ↑ 8.0 8.1 8.2 8.3 Ostrowski (2008a), p. 8-74.
  9. ↑ Ostrowski (2008a), p. 8-75.
  10. ↑ 10.0 10.1 10.2 10.3 10.4 Ostrowski (2008a), p. 8-76.
  11. ↑ 11.0 11.1 Zalosh (2002), p. 3-402.
  12. ↑ Ostrowski (2008a), p. 8-83.
  13. ↑ 13.0 13.1 13.2 13.3 13.4 Slye (2008), p. 6-203.
  14. ↑ 14.0 14.1 Beyler (2002b), pp. 2-177–2-178.
  15. ↑ Doucet and Gilyeat (2008), p. 11-17.
  16. ↑ 16.0 16.1 16.2 16.3 Slye (2008), p. 6-202.
  17. ↑ 17.0 17.1 17.2 17.3 17.4 17.5 17.6 17.7 17.8 Ostrowski (2008a), p. 8-80.
  18. ↑ 18.0 18.1 18.2 Ostrowski (2008a), p. 8-79.
  19. ↑ Cholin (2008a), p. 14-99.
  20. ↑ 20.0 20.1 Ostrowski (2008a), p. 8-78.
  21. ↑ Ostrowski (2008a), p. 8-82.
  22. ↑ Zalosh (2002), p. 3-413.
  23. ↑ Zalosh (2002), p. 3-415.
  24. ↑ Iqbal and Salley (2004), p. B-75.
  25. ↑ Frank (2008), p. 17-34.
  26. ↑ Ostrowski (2008a), p. 8-85.
  27. ↑ 27.0 27.1 Ostrowski (2008a), p. 8-84.
  28. ↑ Ostrowski (2008a), p. 8-86.
  29. ↑ 29.0 29.1 Ostrowski (2008a), p. 8-91.

References

  • Beyler, C. L. (2002b). Flammability limits of premixed and diffusion flames. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-172–2-187). National Fire Protection Association; Society of Fire Protection Engineers.
  • Cholin, J. M. (2008a). Gas and vapor detection systems and monitors. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 14-99–14-112). National Fire Protection Association.
  • Cholin, J. M. (2008d). Woodworking facilities and processes. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-3–9-25). National Fire Protection Association.
  • Doucet, L. G., & Gilyeat, S. S. (2008). Waste handling and control. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-3–11-25). National Fire Protection Association.
  • Frank, J. A. (2008). Characteristics and hazards of water and water additives for fire suppression. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-31–17-43). National Fire Protection Association.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Ostrowski, R. (2008a). Industrial and commercial heat utilization equipment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-71–8-92). National Fire Protection Association.
  • Slye, O. M., Jr. (2008). Flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-197–6-208). National Fire Protection Association.
  • Zalosh, R. (2002). Explosion protection. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-402–3-421). National Fire Protection Association; Society of Fire Protection Engineers.