An incinerator is an engineered furnace that treats and disposes of waste by high-temperature combustion.[1] Properly designed and operated systems can reduce the weight and volume of most municipal, commercial and institutional solid waste by as much as 95 %. Incinerators destroy pathological and biomedical waste at hospitals and research facilities, as well as hazardous and toxic industrial waste.[1] Larger wastewater treatment plants often incinerate their sewage sludge.[2]

For fire safety the process cuts both ways. Prompt destruction reduces the amount of combustible waste stored in a building, but an incinerator room brings together stored waste, flames, hot flue gases, hot ash and an auxiliary fuel supply.[1] In the United States the installation is governed largely by NFPA 82, Standard on Incinerators and Waste and Linen Handling Systems and Equipment. The 20th edition of the NFPA Fire Protection Handbook (2008) summarises its provisions for waste charging, ash removal, chimneys and air supply.[3][4][5] Among the main design variables are temperature, residence time, turbulence and the air supply, which typically amounts to 10 to 20 kg of air per kilogram of waste.[4][6]

Definition and types

Doucet and Gilyeat (2008) define incineration as an engineered process that uses high-temperature combustion for the treatment and disposal of waste. Older incinerators were little more than single-chamber fireboxes with uncontrolled burning, notorious for smoke and odour. The handbook states that properly designed, constructed and operated modern systems can be completely fire safe.[1]

Three basic types are used for solid waste in industrial, institutional and commercial facilities.[1] A multiple-chamber incinerator has a primary chamber, in which the waste burns out, and one or more secondary chambers, in which combustibles carried in the flue gas are burned. It runs with 200 to 300 % excess air and is now used almost only for pathological waste such as animal carcasses.[1] A controlled-air incinerator works in two stages. Waste in the primary chamber burns under starved-air, or oxygen-deficient, conditions, and the smoke and volatile gases then burn in a secondary chamber with 100 to 200 % excess air. Most solid waste incinerators built in the 30 to 40 years before 2008 were of this type.[1]

Cross-section of a two-chamber controlled-air incinerator with mechanical loader, starved-air primary chamber, secondary chamber, burners and stack
Controlled-air incinerator. Waste burns with too little air in the primary chamber; its smoke and volatile gases burn out with 100 to 200 % excess air in the secondary chamber above.

A rotary kiln is an inclined cylindrical chamber that turns slowly on its axis. The rotation tumbles the waste and moves the ash to the discharge end, and a separate secondary chamber burns the flue gas combustibles.[1] Kilns accept solids, sludges, liquids and fumes and are used mainly for hazardous and mixed waste.[1][7] In a multiple-hearth incinerator, used almost only for sludge, rotating rabble arms push the sludge across a vertical stack of refractory hearths. A fluidised-bed incinerator injects the waste into a hot bed of sand that a high-pressure blower keeps in suspension.[7]

Liquid injection incinerators burn atomised liquid waste in suspension, and gaseous waste is burned in flares, thermal burners or catalytic burners.[7][8] Industrial vapour incinerators, which include direct-flame afterburners and catalytic units, destroy process exhaust vapours, for example from ovens.[9] Table 1 gives the operating ranges listed in the handbook for the main industrial types.[7]

Table 1. Industrial waste incinerators (Doucet and Gilyeat, 2008, p. 11-21)
Type Typical waste Combustion temperature Residence time
Rotary kiln Most organic wastes; solids and sludges, also liquids and gases 815–1650 °C (1500–3000 °F) Several seconds to several hours
Multiple hearth Most organic wastes, largely sewage sludge 760–980 °C (1400–1800 °F) Up to several hours
Liquid injection Pumpable liquids and slurries only 650–1650 °C (1200–3000 °F) 0.1–1.0 s
Fluidised bed Most organic wastes; ideal for liquids 760–870 °C (1400–1600 °F) Seconds for gases and liquids, longer for solids
Pyrolysis Mainly as fuel; solids and sludges 480–815 °C (900–1500 °F) Normally 12–15 min

Combustion in an incinerator

Pyrolysis is the decomposition of a material by heating, in which large molecules break down into smaller ones and release combustible gases. It needs no oxygen, but the combustion of those gases does.[10] Solid waste therefore burns in two steps: the solid decomposes, and the released gases burn in the flames.[11] A pyrolysis unit heats waste without oxygen, distils off the volatiles and leaves ash and char, and the volatiles are burned in a separate chamber with excess air.[6] Controlled-air incinerators, with their starved-air primary chamber, are also called pyrolytic incinerators.[1]

Gore Willse (2008a) describes complete, or stoichiometric, combustion as the state in which all of the fuel is oxidised by the air supplied. Air left over is excess air, and practical burners run with some of it. Primary air enters with the fuel, and secondary air is supplied to the combustion zone.[12] Incomplete combustion can produce hazardous carbon monoxide and usually results from too little air, poor mixing or a temperature too low to sustain combustion.[12] Boiler designers summarise the requirements as the three Ts of combustion: time, temperature and turbulence.[13]

The equivalence ratio is the actual fuel-to-air mass ratio divided by the stoichiometric one. Values below 1 mean a fuel-lean, well-ventilated fire, and values above 1 a fuel-rich fire that favours carbon monoxide.[14] In the compartment-fire studies summarised by Gann and Bryner, carbon monoxide yield is typically less than 0.01 below an equivalence ratio of about 0.5. It levels off at about 0.2 kg per kilogram of fuel above about 1.5. These are not incinerator emission factors.[14] An oxygen-deficient primary chamber thus works on the fuel-rich side, and the secondary chamber with excess air burns out its smoke and volatile gases.[1] Halogenated plastics also release acid gases: hydrogen chloride forms during pyrolysis even without flaming and is released from PVC at about 225 to 275 °C.[14]

Fire and explosion hazards

Doucet and Gilyeat (2008) list the hazards inherent in incineration. They are combustible, sometimes highly volatile waste; high-temperature flaming combustion; ducting of hot gases; hot ash; and the fuel and combustion systems. Safety therefore depends on layout, waste flow patterns, operation and maintenance as well as on sprinklers and fire-rated rooms.[1]

The equipment works under severe conditions: widely fluctuating temperatures, thermal shock from wet waste, slagging and spalling of the refractory, acid attack and abrasion.[1] Explosions inside the chambers can be caused by aerosol cans, and Mattern (2008b) adds mercury batteries and other pressurised containers.[1][15] Cracks or distortions could let flames and hot gases escape into the building, so the units must be built to resist these conditions.[1][16]

Severson (2008) lists the principal operating hazards. These are overheating from feeding much volatile material or waste with a higher heat of combustion, structural failure from overheating or corrosion, and acid corrosion or failure of the scrubber.[17] Burning a flammable solvent in a waste mixture might also release a toxic pesticide, or its combustion products, to the atmosphere.[18] Vapour incinerators have been damaged by fires in the ducts between the process and the incinerator, by explosions of vapours accumulated before or during start-up and by overheating. Causes included poor duct cleaning, incomplete prepurging, operator error and faulty controls.[9]

Ash remains a hazard after it leaves the furnace. Hot ash with partly burned items can ignite when exposed to room air during cleanout, and quenched residues in ash carts may still ignite spontaneously when disturbed.[4] Smouldering in a fuel layer becomes nearly steady when air is forced through it, a configuration that Ohlemiller (2002) notes in some incinerators and coal burners.[19]

Design and installation requirements

Casings normally accessible to personnel must be insulated or shielded so that their surface does not exceed 71 °C (160 °F).[16] Metal handles of operating doors may rise by no more than 22 K (40 °F), and non-metallic handles by no more than 33 K (60 °F). Each incinerator needs an explosion-relief door or panel with an effective area of 0.0929 m² per 2.83 m³ (1 ft² per 100 ft³) of primary chamber volume.[16] All parts, including chambers, breechings and ash areas, must be accessible for inspection and repair.[16]

Clearances to combustible materials keep exposed combustibles below dangerous temperatures and were set by testing laboratories and field experience.[20] Table 2 gives the standard clearances for incinerators, which apply unless a listed appliance shows otherwise.[21] For brick-encased commercial units, the clearance above may be reduced to 914 mm (36 in.) and those at the sides and rear to 457 mm (18 in.). Domestic units need at least 1219 mm (48 in.) above the charging door.[22]

Plan and elevation of a domestic and a commercial incinerator with dimensioned clearances to combustible walls and ceiling
Standard clearances from incinerators to combustible material in US practice around 2008, unless a listed appliance shows otherwise.
Table 2. Standard clearances from incinerators to combustible material (Gore Willse, 2008a, pp. 10-29–10-30)
Incinerator Above top From front From back From sides
Domestic type 914 mm (36 in.) 1219 mm (48 in.) 914 mm (36 in.) 914 mm (36 in.)
Commercial-industrial, all sizes 1220 mm (48 in.) 2440 mm (96 in.) 910 mm (36 in.) 910 mm (36 in.)

Incinerators and their waste and residue handling systems must be placed in a separate fire-rated room with fire-rated opening protectives, which may also house the building heating equipment.[5] Kampmeyer (2008) notes that incinerator rooms are often separated by 2 hour rated construction.[23] In New York City, both the 1968 and the 2003 building codes required Class A or B interior finish in incinerator combustion rooms. This is a flame spread rating of 0 to 75 as defined in ASTM E84.[24]

Chimneys and breechings must follow NFPA 82 and NFPA 211. Those for hot flue gases should be refractory-lined and insulated, and those for the wet gases downstream of a scrubber must resist acidic corrosion.[4] An incinerator chimney may serve no other purpose, and it may be connected to a boiler chimney only if it is built and controlled for both services.[4] Spark arresters are required on incinerators, typically wire mesh with openings of about 13 mm (½ in.).[25] Draft hoods, a standard feature in gas appliance venting, are not required on incinerators.[26]

Most incinerators fire natural gas or distillate fuel oil in auxiliary burners. These provide ignition, warm-up and temperature control and should have automatic ignition and flame safeguards.[4] Wiring within about 0.3 m (1 ft) of a casing should have high-temperature insulation, and control panels should be at least about 0.9 m (3 ft) away.[5] Confined incinerator rooms need an air-supply louver or blower for combustion air and for ventilation air that removes heat radiated from the casings.[4][5] In health care buildings this air should be taken from, and discharged to, the outside.[27]

Waste charging and ash removal

Charging has a particularly high fire hazard potential, because loading opens a direct path between flaming combustion and the building.[16] Manual loading through a charging door has mostly been used on small and batch-loaded units, and many US states no longer accept it because of air pollution.[16][3] Where it is allowed, the opening should be at least 610 mm × 610 mm (24 × 24 in.), the door should latch positively, and an interlock should stop the primary burners when it opens.[3]

Mechanical loaders are almost always used above about 136 kg/h (300 lb/h). NFPA 82 requires charging controls that prevent flames, combustion gases and heat from escaping during loading, which in effect calls for a mechanical loader unless the unit is batch-loaded.[3] In a hopper and ram loader, the hopper cover closes, the fire door opens, a ram pushes the waste in and withdraws, and the fire door closes before the cover reopens. Because one door is always shut, the loader works as an airlock.[3]

Six-step sequence of a hopper and ram incinerator loader showing that the hopper cover and the fire door are never open at the same time
Loading cycle of a hopper and ram loader. Because the hopper cover and the fire door are never open together, the loader works as an airlock between the furnace and the room.

Two faults need attention. Waste lodged under the fire door can stop it closing, ignite and spread fire back into the hopper, so the door should be closed by power, not gravity. The hot ram face can also pick up melting plastic bags and carry burning material back, so the ram should be water-cooled or quenched after every stroke.[3] Recommended extras are a flame scanner, a high-temperature sprinkler over the hopper independent of the room sprinkler system, and an emergency switch that injects the hopper contents at once.[3][4]

Almost all incinerators burning more than about 454 kg/h (1000 lb/h) have automatic or semiautomatic ash removal.[4] Water should not be sprayed into the furnace to quench ash, because thermal shock damages the refractory. NFPA 82 requires the ash removed during cleanout to be quenched or contained, for example by water sprays, a wet quench pit or a special enclosure.[4] Ash carts should be stored in a fire-rated area away from waste.[4]

Air supply and explosion relief calculations

The stoichiometric air requirement is the mass of air needed to burn one kilogram of fuel completely. Drysdale (2002) shows that the heat released per gram of air consumed is roughly constant, about 3 kJ/g, for most fuels.[28] Dividing the heat of combustion by this value gives the stoichiometric air-to-fuel ratio. The excess air and the equivalence ratio follow from the air actually supplied, while the relief and louver areas grow in proportion to chamber volume and total heat input:

rst=ΔHcΔHc,airEA=rarst−1ϕ=rstra Av=0.0328VpAl=550Q˙

Symbol Description Unit
rst Stoichiometric air-to-fuel mass ratio kg air/kg fuel
ra Air actually supplied per unit mass of waste kg air/kg waste
ΔHc Heat of combustion of the fuel kJ/g
ΔHc,air Heat released per unit mass of air consumed kJ/g
EA Excess air (multiply by 100 for per cent) –
ϕ Equivalence ratio –
Av Effective area of the explosion-relief door or panel m²
Vp Volume of the primary combustion chamber m³
Al Free area of the outside-air louver mm²
Q˙ Total heat input kW

The constant 0.0328 m²/m³ is the handbook rule of 0.0929 m² per 2.83 m³. The constant 550 mm²/kW converts the louver rule of 1 in.² of free area per 4000 Btu/h, or 645 mm² per 1.17 kW.[16][5] The heat released per unit mass of air is not constant for every fuel: carbon monoxide (4.10 kJ/g) and ethyne (3.65 kJ/g) are clear exceptions.[28] For most combustible materials the stoichiometric ratio lies between 3 and 16 kg of air per kilogram.[29]

For cellulose, with 16.09 kJ/g and 3.15 kJ per gram of air, the stoichiometric ratio is 16.09 / 3.15 = 5.1 kg of air per kilogram.[28] Introduction to Fire Safety Engineering gives a similar result: about 1.25 kg of oxygen per kilogram of cellulosic fuel, divided by 0.232 kg of oxygen per kilogram of dry air, is 5.4 kg of air.[30][31] Polyethylene needs 43.28 / 2.93 = 14.8 kg.[28] The handbook's 10 to 20 kg of air per kilogram therefore means about 96 to 290 % excess air for cellulose-like waste, or an equivalence ratio of 0.51 to 0.26. This is the same order as the excess air quoted for the incinerator types.[1][4] Moisture and ash in real waste lower the demand and plastics raise it, so the result is a check, not a design value.

Line chart of equivalence ratio against air supply per kilogram of waste for cellulose and polyethylene, with the 10 to 20 kg per kg band shaded
Equivalence ratio against air supply for cellulose and polyethylene. The shaded band is the 10 to 20 kg of air per kilogram typical of incinerators; above the line at 1 the burning is fuel-rich.

As a worked example, take an incinerator burning 454 kg/h (1000 lb/h) of waste.[4] At 10 to 20 kg of air per kilogram, it needs 4540 to 9070 kg/h, or 1.26 to 2.52 kg/s, of combustion air. With an air density of 353/T, about 1.2 kg/m³ at 20 °C, this is 1.05 to 2.09 m³/s.[32] Estimating the heat input with dry cellulose gives 454/3600 × 16.09 MJ/kg ≈ 2030 kW. On this assumption, without auxiliary fuel input, the louver needs 550 × 2030 ≈ 1,120,000 mm², rounded up to 1.2 m² of free area; actual sizing must use total heat input, including auxiliary burners.[5][28] For an assumed primary chamber of 3.0 m³, the relief area is 0.0328 × 3.0 = 0.098 m², rounded up to 0.10 m².[16]

Applications and fire experience

Severson (2008) describes incineration as the preferred treatment for AIDS-contaminated and combustible infectious waste, reducing the volume for disposal by up to 95 % and removing its infectious hazard when properly operated.[33] The residual ash can still require hazardous-waste disposal.[34] Industrial plants incinerate hazardous waste and waste solvents, using an auxiliary gas or oil burner to hold the destruction temperature and usually a scrubber for acid gases.[35] Davenport (2008) notes that US standards for hazardous waste require incinerators to achieve 99.9 % destruction efficiency.[36] Waste with halogenated aromatic compounds needs at least 1204 °C (2200 °F).[8]

Wastewater treatment plants burn sludge mostly in multiple-hearth or fluid-bed units, and the ash can be toxic.[2] Municipal solid waste is burned either with little processing, in mass burn plants, or after processing into refuse-derived fuel.[37][38] Shredders that prepare such fuel can explode, usually from dust ignited by tramp metal.[38]

Fire statistics treat most incinerator fires as confined fires. In the US National Fire Incident Reporting System (NFIRS) version 5.0, incident type 115 covers incinerator overload or malfunction. Confined fires are small, generally stay within a noncombustible container and allow abbreviated reporting.[39][40] The reported number rose from 8 in 1999 to 492 in 2003, about 0.2 % of reported structure fires. These are raw counts that grew as departments adopted version 5.0, not national estimates.[41]

National estimates for US industrial and manufacturing properties in 1999 to 2002 give about 100 confined incinerator fires a year, 1 % of all fires in these properties.[42] These caused no civilian deaths, 3 civilian injuries and about US$2 million in direct damage. The values are projections from fires reported to municipal fire departments, so fires handled only by industrial fire brigades are excluded.[42]

Limits and misconceptions

Some older gravity waste chute systems discharged straight into an incinerator, and some chutes even served as its chimney. Under NFPA 82 as summarised in 2008, chutes may not discharge directly into an incinerator, and automatic transfer from a chute terminal room is not recommended.[43] Outdoor rubbish should be kept at least 15 m (50 ft) from ignition sources such as incinerators.[44][45]

Incineration does not make every waste harmless. Only organic constituents are destroyed by combustion or pyrolysis.[46] Ash and scrubber sludge must be disposed of off site, ash may need testing for heavy metals, and hazardous residues go to a permitted facility.[34] Catalytic units cannot oxidise silicones, chlorine compounds or metallic fumes such as tin, mercury and zinc.[47] No single chimney lining material suits all operating conditions and waste types.[4]

The requirements above are US practice as summarised in the 20th edition of the Fire Protection Handbook (2008), which does not name the NFPA 82 edition. They are not universal and may differ from current editions and from rules in other countries. The chapter adds that state and local regulations in the United States may be more stringent than federal regulations or standards.[48]

See also

Notes

  1. ↑ 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 1.10 1.11 1.12 1.13 1.14 1.15 Doucet and Gilyeat (2008), p. 11-6.
  2. ↑ 2.0 2.1 Wheeler (2008), p. 9-148.
  3. ↑ 3.0 3.1 3.2 3.3 3.4 3.5 3.6 Doucet and Gilyeat (2008), p. 11-8.
  4. ↑ 4.00 4.01 4.02 4.03 4.04 4.05 4.06 4.07 4.08 4.09 4.10 4.11 4.12 4.13 Doucet and Gilyeat (2008), p. 11-9.
  5. ↑ 5.0 5.1 5.2 5.3 5.4 5.5 Doucet and Gilyeat (2008), p. 11-10.
  6. ↑ 6.0 6.1 Doucet and Gilyeat (2008), p. 11-20.
  7. ↑ 7.0 7.1 7.2 7.3 Doucet and Gilyeat (2008), p. 11-21.
  8. ↑ 8.0 8.1 Doucet and Gilyeat (2008), p. 11-22.
  9. ↑ 9.0 9.1 Ostrowski (2008a), p. 8-84.
  10. ↑ Van Rossum (2027), §3.1.
  11. ↑ Van Rossum (2027), §4.1.
  12. ↑ 12.0 12.1 Gore Willse (2008a), p. 10-9.
  13. ↑ Mattern et al. (2008), p. 10-92.
  14. ↑ 14.0 14.1 14.2 Gann and Bryner (2008), p. 6-13.
  15. ↑ Mattern (2008b), p. 11-34.
  16. ↑ 16.0 16.1 16.2 16.3 16.4 16.5 16.6 16.7 Doucet and Gilyeat (2008), p. 11-7.
  17. ↑ Severson (2008), p. 7-63.
  18. ↑ Severson (2008), p. 7-62.
  19. ↑ Ohlemiller (2002), p. 2-202.
  20. ↑ Gore Willse (2008a), p. 10-28.
  21. ↑ Gore Willse (2008a), p. 10-29.
  22. ↑ Gore Willse (2008a), p. 10-30.
  23. ↑ Kampmeyer (2008), p. 18-74.
  24. ↑ Razza and Grill (2005c), p. 24.
  25. ↑ Gore Willse (2008a), p. 10-50.
  26. ↑ Gore Willse (2008a), p. 10-46.
  27. ↑ O'Connor (2008), p. 20-152.
  28. ↑ 28.0 28.1 28.2 28.3 28.4 Drysdale (2002), p. 1-93.
  29. ↑ Janssens (2002), p. 3-44.
  30. ↑ Van Rossum (2027), §3.3.
  31. ↑ Janssens (2002), p. 3-46.
  32. ↑ Van Rossum (2027), §3.2.
  33. ↑ Severson (2008), p. 7-64.
  34. ↑ 34.0 34.1 Doucet and Gilyeat (2008), p. 11-23.
  35. ↑ Severson (2008), p. 7-66.
  36. ↑ Davenport (2008), p. 7-55.
  37. ↑ Dungan (2008b), p. 7-11.
  38. ↑ 38.0 38.1 Dungan (2008b), p. 7-12.
  39. ↑ Ahrens et al. (2008), p. 3-66.
  40. ↑ Ahrens et al. (2008), p. 3-67.
  41. ↑ Ahrens et al. (2008), p. 3-77.
  42. ↑ 42.0 42.1 Demers (2008a), p. 20-207.
  43. ↑ Doucet and Gilyeat (2008), p. 11-5.
  44. ↑ Mattern (2008b), p. 11-36.
  45. ↑ Mattern (2008b), p. 11-37.
  46. ↑ Doucet and Gilyeat (2008), p. 11-19.
  47. ↑ Ostrowski (2008a), p. 8-85.
  48. ↑ Doucet and Gilyeat (2008), p. 11-25.

References

  • Ahrens, M., Frazier, P., & Kelch, G. (2008). Use of fire incident data and statistics. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-61–3-92). National Fire Protection Association.
  • Davenport, J. A. (2008). Storage and handling of chemicals. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-43–7-55). National Fire Protection Association.
  • Demers, D. P. (2008a). Industrial occupancies. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-203–20-210). National Fire Protection Association.
  • Doucet, L. G., & Gilyeat, S. S. (2008). Waste handling and control. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-3–11-25). National Fire Protection Association.
  • Drysdale, D. D. (2002). Thermochemistry. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 1-90–1-98). National Fire Protection Association; Society of Fire Protection Engineers.
  • Dungan, K. W. (2008b). Storage and handling of solid fuels. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-3–7-13). National Fire Protection Association.
  • Gann, R. G., & Bryner, N. P. (2008). Combustion products and their effects on life safety. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-11–6-34). National Fire Protection Association.
  • Gore Willse, P. J. (2008a). Heating systems and appliances. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 10-9–10-56). National Fire Protection Association.
  • Janssens, M. (2002). Calorimetry. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-38–3-62). National Fire Protection Association; Society of Fire Protection Engineers.
  • Kampmeyer, J. E. (2008). Penetration sealing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 18-73–18-78). National Fire Protection Association.
  • Mattern, L. J. (2008b). Housekeeping practices. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-27–11-38). National Fire Protection Association.
  • Mattern, L. J., Catania, E., & Ehrlich, S. (2008). Boiler furnaces. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 10-91–10-104). National Fire Protection Association.
  • O'Connor, D. J. (2008). Health care occupancies. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-139–20-155). National Fire Protection Association.
  • Ohlemiller, T. J. (2002). Smoldering combustion. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-200–2-210). National Fire Protection Association; Society of Fire Protection Engineers.
  • Ostrowski, R. (2008a). Industrial and commercial heat utilization equipment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-71–8-92). National Fire Protection Association.
  • Razza, J. C., & Grill, R. A. (2005c). Comparison of the 1968 and current (2003) New York City Building Code provisions (NIST NCSTAR 1-1F). National Institute of Standards and Technology.
  • Severson, P. R. (2008). Hazardous waste control. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-57–7-69). National Fire Protection Association.
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.
  • Wheeler, J. F. (2008). Protection of wastewater treatment plants. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-141–9-155). National Fire Protection Association.