Gas appliance venting is the removal of the combustion products of gas-fired appliances to the outdoors through a chimney, gas vent or other venting system, often via a vent connector.[1][2] A good venting system carries the flue gases safely to the outdoors, protects the building from their heat and resists the condensate that they can form.[3][4] When a vent fails, combustion products may spill indoors; if combustion is incomplete, those products can contain dangerous carbon monoxide (CO).[1] In the United States, CO accumulation is generally caused by faulty heating appliances, too little make-up air, or chimneys and vents that are blocked, badly designed, badly installed or missing.[5] In the 2008 handbook, NFPA 54, the National Fuel Gas Code, sorts vented appliances into four categories by vent pressure and vent gas temperature.[4] Fan-assisted and condensing appliances developed in the 1970s and 1980s brought new vent-design requirements because their flue gases are cooler and more likely to condense.[3]

Purpose and principles

Combustion is complete when all of the fuel is oxidised by the air supplied to it, and gas appliances operate with some excess air because perfect combustion is impractical.[6] Incomplete combustion in a fuel-burning device can produce hazardous carbon monoxide. It usually results from an inadequate air supply, insufficient mixing of air and gas, or a temperature too low to sustain combustion.[6]

For methane, the main component of natural gas, complete combustion consumes two molecules of oxygen per molecule of fuel and forms one molecule of carbon dioxide and two of water.[7][8] With air containing 21 % oxygen, a stoichiometric calculation with no excess air gives about 9.5 volumes of air per volume of methane and wet flue products that are about 19 % water vapour by volume.[9] Excess air and dilution change that fraction. Water vapour in the flue products contributes to the condensation problems of modern vents.[3]

The 2008 handbook describes natural gas as the most commonly used gas fuel in the United States and liquefied petroleum gas as popular in sparsely settled areas and recreational vehicles.[8] Injection burners, in which a jet of gas draws primary air into the burner, are common in residential and commercial gas appliances.[8] As summarised in the 2008 handbook, NFPA 54 specifies which gas appliances must be vented. Generally, larger heating appliances such as boilers and furnaces need venting, whereas smaller appliances such as listed cooking stoves and hot plates do not.[10] Several unvented appliances in one space may still need venting if their aggregate input exceeds 0.2 kW/m³ (20 Btu/h per ft³) of the space.[11] A space of 30 m³ thus reaches this threshold at about 6 kW of total input.

Venting works together with the supply of air. Rooms such as furnace and boiler rooms need a means of supplying air for combustion and ventilation, and NFPA 31 and NFPA 54 give recommendations because no universal formula exists.[1] A chimney or vent connector is the pipe or breeching that joins an appliance to its chimney or vent, unless the chimney or vent is attached directly to the appliance.[1] In the 2008 handbook, the installation, alteration and repair of gas appliances and gas piping is reserved for qualified agencies fully experienced in this work.[12]

Natural draft and the draft hood

Traditional gas appliances rely on natural draft. Before the 1980s, most gas furnaces had an atmospheric burner, a heat exchanger and a draft hood at the outlet. The mixture of flue gas and dilution air was drawn up the chimney or vent by the buoyancy of the warm gases.[3] This buoyancy is a form of the stack effect: a warm gas column is lighter than the surrounding cold air, and a vertical duct strengthens the effect because the gas cannot mix sideways.[13] The available draft can be estimated as the pressure difference between a cold air column and a warm gas column of the same height. The density of air and flue gas follows approximately from their absolute temperature.[14]

Δp≈g⋅h⋅(ρa−ρg),ρ≈353T

Symbol Description Unit
Δp Draft, the pressure difference that drives the flow Pa
g Acceleration due to gravity, 9.81 m/s²
h Height of the vent from the appliance to the outlet m
ρa, ρg Density of outdoor air and of the vent gas kg/m³
T Absolute temperature of the gas concerned K

The estimate assumes gases near atmospheric pressure, air-like flue-gas density and a vent filled with gas of uniform temperature; it omits flow resistance and wind.[14] Draft hood appliances such as furnaces, water heaters and boilers must pass spillage tests with only 1.5 m (5 ft) of vent height. Wall furnaces need a vent outlet at least 3.7 m (12 ft) above the floor.[15] With outdoor air at 20 °C (1.20 kg/m³) and a mean vent gas temperature of 150 °C (0.83 kg/m³), a 1.5 m vent gives Δp ≈ 9.81 × 1.5 × 0.37 ≈ 5.4 Pa. A 3.7 m vent gives about 13 Pa.

At the 38 °C lower-end flue gas temperature cited for a condensing appliance, the same 1.5 m vent would generate only about 1 Pa of buoyancy pressure without its required mechanical venting.[16] The vent gas temperatures in this example are illustrative values. For comparison, residential oil burners are designed for a draft of 10 to 15 Pa, and forced-draft boilers may run their chimney at 120 to 370 Pa above atmospheric pressure.[15]

Line chart of natural draft in pascals against mean vent gas temperature for vent heights of 1.5 and 3.7 metres, staying below about 17 Pa
Natural draft of a vent against mean vent gas temperature, from Δp = g h (ρa − ρg) with ρ = 353/T and outdoor air at 20 °C.

The draft hood protects the appliance from variations in this weak draft. It is built into the appliance or forms part of the vent connector.[17] It lets the flue gases escape readily if there is no draft, a backdraft or a blockage beyond the hood. It also prevents a backdraft from entering the appliance and neutralises the stack action of the chimney or vent.[17] For gas appliances with draft hoods, chimney draft therefore has very little influence on combustion, and the chimney serves only as a conduit for the combustion products.[15] Draft hoods are generally required on vented appliances, except for direct-vent appliances and units with power burners or mechanical forced venting.[17]

Section through a gas furnace with draft hood, vent connector and Type B vent rising through a roof, with flue gas, dilution air and spill paths
A natural-draft gas venting system with draft hood, vent connector and Type B vent.

Vent types

Vents are laboratory-tested, factory-built units for venting fuel-burning appliances, and each type has a specific use.[2] The handbook's vent selection chart, summarised in the table, shows which vent serves which appliance.[2][3] Single-wall metal pipe must be made of galvanised sheet steel of at least 0.51 mm (No. 20 gauge) or another noncombustible, corrosion-resistant material.[3] Its use is restricted to runs directly from the appliance space through the roof or an exterior wall. It may not start in or pass through an attic or other concealed space, nor through any floor or ceiling.[16] For metal chimneys, the handbook stresses corrosion-resistant metal when the gases are at or below 177 °C (350 °F), because exposed outdoor sections may fall below the dew point and condense continuously.[15]

Vent type Used for
Type B gas vent Listed gas appliances with draft hoods and other Category I appliances listed for Type B vents, such as furnaces, boilers, water heaters and room heaters
Type BW gas vent Listed vented gas wall furnaces
Type L vent Oil appliances listed for Type L vents, and gas appliances listed for Type B vents
Special gas vent Listed Category II, III and IV gas appliances, as specified by the appliance manufacturer
Pellet vent Listed pellet-burning appliances
Single-wall metal pipe Residential and low-heat gas appliances with draft hoods, and incinerators used outdoors; not solid-fuel appliances
Plastic pipe (PVC) Category IV appliances, within the limits of the manufacturer's instructions

Efficiency and venting categories

Older gas furnaces with draft hoods typically reached an annual fuel utilisation efficiency (AFUE) of 65 to 75 %.[3] The 2008 handbook states that the United States National Appliance Energy Efficiency Act of 1987 required a minimum of 78 % and that most standard furnaces of that period achieved 78 to 83 %.[3] To reach this, the standing pilot was replaced by intermittent ignition, the draft hood was mostly eliminated and a small fan was added at the flue outlet.[3] High-efficiency condensing furnaces exceed 90 % by cooling the flue gases below their dew point in a second heat exchanger.[3]

These changes altered the vent conditions. Lower heat loss and lower gas flow make the vent cooler and reduce the available draft. Without dilution air, the humidity and dew point of the vent gases rise, and the vent stays wet with corrosive condensate for longer.[3] A fan at the appliance outlet also makes pressurisation of the vent more likely. The vent must then be designed for positive pressure, or sized and configured so that pressurisation cannot occur.[3]

NFPA 54 therefore defines four categories of vented gas appliances.[4] Category I appliances operate with a nonpositive vent static pressure and a vent gas temperature that avoids excessive condensate in the vent. Category II appliances also have a nonpositive vent pressure, but a vent gas temperature that may cause excessive condensate.[4] Category III appliances operate with a positive vent pressure and avoid excessive condensate, while Category IV appliances have a positive vent pressure and may cause excessive condensate.[4] The category can be determined only in the laboratory under the relevant ANSI test standard, and it is shown on the rating plate.[4]

Two by two matrix of gas appliance venting categories I to IV by vent pressure and condensate, with the vent type each needs
The four venting categories of gas appliances in NFPA 54 and the vents they need.

The category sets the type of vent. Categories III and IV need vents that withstand positive pressure and are sealed against leakage, while Categories I and II rely on natural draft through a vertical vent.[4] Categories II and IV need corrosion-resistant vents that contain and dispose of condensate, and few if any Category II appliances are on the market.[4] Category I appliances use conventional systems, mainly Type B vents and masonry chimneys. Masonry chimneys heat up slowly and often have to be relined with aluminium or stainless steel to limit condensation.[4] Category III and IV appliances can typically vent horizontally through a side wall, with the materials, sizes and joint sealants specified by the manufacturer.[16]

Vent sizing changed in the 1990s. NFPA 54 has provided sizing tables since the 1950s, originally for draft hood appliances and based only on the maximum capacity that prevents spillage.[4] Research, much of it sponsored by the Gas Research Institute, added a minimum vent capacity. A vent that is too large for the connected input warms up slowly and stays wet for longer, which may corrode it.[4] The acceptable vent size therefore lies between a minimum and a maximum, and for some combinations of appliance and vent geometry no acceptable size exists.[4]

Installation: clearances, termination and separation

Vents and connectors must keep a clearance to combustibles.[1] In the 2008 handbook, which reproduces the NFPA 211 table, a single-wall connector from a listed gas appliance with a draft hood that is suitable for a Type B vent needs 152 mm (6 in.). Boilers and furnaces with listed gas burners and draft hoods need 229 mm (9 in.), and gas appliances without draft hoods need 457 mm (18 in.).[18] Listed Type B and other vents follow the clearances of their listing.[16] Where single-wall pipe from an appliance listed for a Type B vent passes through a combustible roof, it needs a noncombustible thimble at least 100 mm (4 in.) larger in diameter. The thimble extends 457 mm (18 in.) above and 152 mm (6 in.) below the roof, with the annular space open below and closed above.[17]

The outlet must stand high enough above the roof. The commonly cited rule in the handbook requires a gas vent or Type L vent to end at least 0.61 m (2 ft) above the roof, against 0.92 m (3 ft) for a chimney.[15] An outlet less than 3.1 m (10 ft) from a ridge, wall or parapet must also be at least 0.61 m above it.[15] Because airflow over a building creates eddy zones on the lee side, these dimensions are sometimes not enough, as the many special vent caps and chimney extensions show.[19]

Vents that pass through floors of buildings that require protection of vertical openings must be enclosed. The enclosing walls need a fire resistance rating of at least 1 hour in buildings of less than four storeys and at least 2 hours in taller buildings.[17] The handbook lists this requirement under firestopping. One appliance per flue gives the best operation, although two or three gas appliances may share a masonry chimney flue at one level if the sizes follow the capacity tables in NFPA 54.[20]

Gas appliances also change the life of masonry chimneys. Condensation of flue gas moisture in a masonry chimney serving low-temperature gas appliances can disintegrate the mortar and leave the chimney weak and easily toppled.[19] Liners listed for Category I gas appliances are often aluminium and unsuitable for other residential appliances, so NFPA 54 and NFPA 211 require a warning notice near the chimney inlet.[21] A solid-fuel appliance connected to such a liner would expose it to temperatures for which it is not designed, and creosote deposits from wood burning are the fuel of a chimney fire.[21][22]

Spillage, backdrafting and carbon monoxide

Modern buildings can make venting harder. The 2008 handbook describes tighter houses that admit less air through infiltration, while attic fans, down-draft cooking ranges and other exhaust devices remove more air than can easily be replaced.[1] The building then becomes depressurised. If the pressure drop in the building exceeds the draft of the chimney or vent, flue gases and air are drawn down through the venting system into the building. This is called backdrafting.[1] If combustion is not complete, carbon monoxide can then reach dangerous concentrations indoors.[1]

House section: exhaust fans remove air, outdoor air is drawn down a gas vent, CO spreads indoors and a CO alarm sits in the hallway
Backdrafting in a depressurised house and the measures described in the 2008 handbook.

The worked example above shows how small the buoyancy pressure can be in a short vent. Direct-vent, sealed-combustion appliances take their combustion air directly from outdoors and are essentially immune to this problem, and appliances with powered exhausts are less likely to backdraft.[1] For natural draft appliances, the handbook calls for an empirical test of draft and vent flow at installation. The test is run with exhaust fans and other appliances operating, to simulate the worst case.[1] The handbook also reports an increasing use of make-up air requirements in tight, mechanically ventilated houses.[1]

Carbon monoxide is a colourless, odourless gas. Black (2008) states that the vast majority of US deaths from CO poisoning occur in one- and two-family dwellings.[5] The same chapter cites US death certificate data showing 200 to 300 unintentional-injury deaths a year in the period described.[5]

Haemoglobin binds CO about 250 times more strongly than oxygen, and the resulting carboxyhaemoglobin (COHb) reduces the oxygen-carrying capacity of the blood.[23] In compartment-fire research, overventilated burning produced little CO, whereas fuel-rich burning produced products of incomplete combustion. In hood experiments with several fuels, CO yields rose once the equivalence ratio exceeded about 0.6; that experimental threshold is not a gas-appliance operating limit.[24] Black (2008) gives an equation for the COHb level after an exposure of t minutes to a constant CO concentration in parts per million (ppm).[25]

%COHbt=%COHb0e−t/(2398B)+218[1−e−t/(2398B)][0.0003+ppmCO1316]

Symbol Description Unit
%COHbt, %COHb0 COHb in the blood at time t and at the start of exposure %
t Exposure time min
B Constant for work effort, 0.0404 –
ppmCO CO concentration in the inhaled air ppm

For a non-smoker, the initial COHb level can be taken as 0.8 %.[26] Exposure to 400 ppm, a level at which headache and nausea appear after 1 to 2 hours, then gives about 31 % COHb after 60 minutes and about 47 % after 120 minutes.[25] Most deaths from CO in fires have been associated with COHb levels of 50 to 70 %, although both lower and higher values occur.[23] The values in the handbook table are approximate and apply to healthy adults, while children, the elderly and people with existing conditions may be more susceptible.[25] In the United States, NFPA 720 (2005) places a carbon monoxide alarm outside each sleeping area of dwellings with a fuel-burning appliance, a fireplace or an attached garage, where such alarms are required or desired.[27]

Unvented gas heaters

Gas room heaters and cooking appliances listed for unvented use are the exceptions to the venting rule.[28] Listed unvented room heaters have an oxygen depletion safety shutoff that stops the gas supply if the oxygen in the room falls below about 18 %. They may not be used in institutions such as convalescent homes.[11] Fuel-burning room heaters are not installed in sleeping quarters for transients, as in hotels and motels. Where heaters are allowed in sleeping quarters and in rooms usually kept closed, the handbook recommends direct-vent appliances.[28]

The 1996 edition of the National Fuel Gas Code allowed listed unvented wall-mounted heaters in bedrooms and bathrooms under limits. The authority having jurisdiction has to approve the installation, a bathroom heater may not exceed 1760 W (6000 Btu/h) and a bedroom heater 2930 W (10,000 Btu/h).[11] The room must also be an unconfined space with a volume of at least 4.8 m³ per kW of heater input (50 ft³ per 1000 Btu/h).[11] A bedroom heater at the 2.93 kW limit therefore needs a room of at least 14 m³, for example 5.9 m² of floor area at a ceiling height of 2.4 m. The change followed problems in the southern United States, where old unvented heaters, many of them installed before 1940, could neither be repaired nor legally replaced.[11] The standard to which these heaters are listed requires an oxygen depletion sensor to ensure adequate combustion air.[2]

Limitations and misconceptions

The category of an existing gas appliance cannot be checked on site. The handbook states that it cannot be determined reliably by field testing, and that it is part of the certification shown on the rating plate.[4] Venting arrangements that worked for older appliances are not automatically acceptable either. Combinations of input and vent configuration that were routine in the past must be carefully scrutinised for mid-efficiency, fan-assisted appliances and may be unacceptable.[4] A draft hood also does not make venting failure harmless. It relieves backdrafts at the appliance, but the gases it releases spill into the room.[17][1]

Venting is also a risk-management problem. In the causal-sequence example of Meacham (2002), a blocked ventilation opening or too much fuel on a fire leads to smoke, CO and high temperatures indoors. The countermeasures include providing an opening that cannot be obstructed and cleaning it regularly.[29] Outside the United States, rules are expressed differently. In New Zealand, Building Code clause C2.3, as reproduced in the 2013 commentary, requires fixed appliances using controlled combustion to have a low probability of creating explosive or hazardous conditions in or around the building.[30] The values and requirements in this article are those of NFPA 54, NFPA 211 and NFPA 720 as summarised in the 2008 handbook; later editions may differ.

See also

Notes

  1. ↑ 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 1.10 1.11 Gore Willse (2008a), p. 10-35.
  2. ↑ 2.0 2.1 2.2 2.3 Gore Willse (2008a), p. 10-42.
  3. ↑ 3.00 3.01 3.02 3.03 3.04 3.05 3.06 3.07 3.08 3.09 3.10 3.11 Gore Willse (2008a), p. 10-43.
  4. ↑ 4.00 4.01 4.02 4.03 4.04 4.05 4.06 4.07 4.08 4.09 4.10 4.11 4.12 4.13 Gore Willse (2008a), p. 10-44.
  5. ↑ 5.0 5.1 5.2 Black (2008), p. 14-113.
  6. ↑ 6.0 6.1 Gore Willse (2008a), p. 10-9.
  7. ↑ Van Rossum (2027), §3.3.
  8. ↑ 8.0 8.1 8.2 Gore Willse (2008a), p. 10-16.
  9. ↑ Van Rossum (2027), §4.2.
  10. ↑ Gore Willse (2008a), p. 10-39.
  11. ↑ 11.0 11.1 11.2 11.3 11.4 Gore Willse (2008a), p. 10-41.
  12. ↑ Gore Willse (2008a), p. 10-17.
  13. ↑ Van Rossum (2027), §6.6.
  14. ↑ 14.0 14.1 Van Rossum (2027), §3.2.
  15. ↑ 15.0 15.1 15.2 15.3 15.4 15.5 Gore Willse (2008a), p. 10-49.
  16. ↑ 16.0 16.1 16.2 16.3 Gore Willse (2008a), p. 10-45.
  17. ↑ 17.0 17.1 17.2 17.3 17.4 17.5 Gore Willse (2008a), p. 10-46.
  18. ↑ Gore Willse (2008a), p. 10-38.
  19. ↑ 19.0 19.1 Gore Willse (2008a), p. 10-50.
  20. ↑ Gore Willse (2008a), p. 10-47.
  21. ↑ 21.0 21.1 Gore Willse (2008a), p. 10-48.
  22. ↑ Gore Willse (2008a), p. 10-52.
  23. ↑ 23.0 23.1 Gann and Bryner (2008), p. 6-14.
  24. ↑ Gottuk and Lattimer (2002), pp. 2-55–2-60.
  25. ↑ 25.0 25.1 25.2 Black (2008), p. 14-114.
  26. ↑ Purser (2002), p. 2-164.
  27. ↑ Black (2008), p. 14-115.
  28. ↑ 28.0 28.1 Gore Willse (2008a), p. 10-23.
  29. ↑ Meacham (2002), p. 5-157.
  30. ↑ Ministry of Business, Innovation and Employment (2013), pp. 14–15.

References

  • Black, A. (2008). Carbon monoxide detection in residential occupancies. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 14-113–14-117). National Fire Protection Association.
  • Gann, R. G., & Bryner, N. P. (2008). Combustion products and their effects on life safety. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-11–6-34). National Fire Protection Association.
  • Gore Willse, P. J. (2008a). Heating systems and appliances. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 10-9–10-56). National Fire Protection Association.
  • Gottuk, D. T., & Lattimer, B. Y. (2002). Effect of combustion conditions on species production. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-54–2-82). National Fire Protection Association; Society of Fire Protection Engineers.
  • Meacham, B. J. (2002). Building fire risk analysis. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 5-153–5-175). National Fire Protection Association; Society of Fire Protection Engineers.
  • Ministry of Business, Innovation and Employment. (2013). Commentary for Building Code clauses C1–C6 and Verification Method C/VM2.
  • Purser, D. A. (2002). Toxicity assessment of combustion products. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-83–2-171). National Fire Protection Association; Society of Fire Protection Engineers.
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.