An intermediate-scale calorimeter (ICAL) is a fire test apparatus for flat, vertical specimens of 1 m by 1 m. The specimen is exposed to a gas-fired radiant panel while its heat release rate, mass loss and smoke production are measured.[1] It fills the gap between bench-scale tests, such as the cone calorimeter with its 100 mm by 100 mm specimen, and full-scale tests of rooms or whole products.[2][3] The larger specimen can accommodate joints, multiple layers and product irregularities that small specimens often miss.[4]

The ICAL was developed at the Weyerhaeuser company in the United States and was the first intermediate-scale instrument to receive standards support.[3][5] The method is documented in ASTM E1623 and in ISO/TR 14696, a 1999 technical report.[1][6] The heat release rate is determined with the oxygen consumption principle from gases collected in a hood.[7][1]

By 2008 the ICAL was widely used in North America to predict full-scale fire performance, but not for regulation.[4] The Single Burning Item test is described as its European counterpart.[4] Round-robin tests have shown a much larger spread between results than for the cone calorimeter.[8]

Definition

In the 2008 edition of the Fire Protection Handbook, Madrzykowski and Stroup define the ICAL as an intermediate-scale calorimeter designed to measure heat release rate, mass loss rates and visible smoke development. The specimen is a 1 m × 1 m vertically oriented, nonmelting material, tested under well-ventilated conditions. It is exposed to a uniform heat flux of up to 50 kW/m² from a gas-fired radiant panel.[1] Hirschler, in the same handbook, describes intermediate-scale calorimeter tests as tests that generate data similar to those of small-scale heat release tests, but at a scale that allows specimens representative of real products.[4]

In the SFPE Handbook, Janssens classes the ICAL among the scaled-up heat release rate calorimeters. These are larger versions of bench-scale calorimeters, in which a sample of one to several square metres is exposed to a constant or preprogrammed heat flux.[5] In this type, a large radiant gas panel and a flat specimen parallel to it stand beneath a hood and exhaust system. Janssens gives the sample size as 1 m × 1 m with a maximum irradiance of 60 kW/m².[5] The two handbooks thus agree on the principle and the specimen size but quote different maximum heat fluxes, 50 and 60 kW/m².[1][5]

In 2002, Babrauskas described intermediate-scale calorimetry as the newest experimental technology for determining the heat release rate.[3] The term intermediate refers to the size of the specimen. Laboratory calorimeters test specimens from 100 mm up to 1 m across, while large-scale calorimeters burn whole items or rooms, and some can handle tens of megawatts.[9][7]

Specimen outlines to scale: a 0.1 m cone square, a 1 m ICAL square, the 1.5 m high SBI corner wings and a 1.22 by 2.08 m facade specimen.
Specimen sizes drawn to the same scale: cone calorimeter (0.1 m × 0.1 m), ICAL (1.0 m × 1.0 m), Single Burning Item test wings (1.5 m high, 0.5 m and 1.0 m wide) and the Canadian facade calorimeter (1.22 m × 2.08 m). The ICAL specimen has 100 times the area of the cone specimen.

The need for this middle scale follows from the limits of small specimens. Laboratory calorimeters often do not represent the performance of a material in real life. They do not test the sizes found in most fire scenarios, and their results can be influenced by how close the specimen edges are to the centre of the flame zone.[10] Small-scale tests also include little or no consideration of geometry. Intermediate-scale and large-scale calorimeters attempt to provide a more realistic scenario.[10] Full-scale reference tests, such as a room corner test, are expensive, so it is impractical to test every material in every configuration.[10]

Development and standards

Various earlier attempts at intermediate-scale calorimetry had been made, but the ICAL developed at Weyerhaeuser was the first instrument to receive support from a standard.[3] Its development was published by Urbas and Luebbers in 1995. Urbas and Shaw reported in 1993 on testing wall assemblies in the ICAL.[11] According to Janssens, the device was developed in the United States primarily to evaluate the heat release rate of construction assemblies.[5]

The method was standardised by ASTM International as ASTM E1623, with a 1994 edition cited in the 2008 Fire Protection Handbook.[12] The International Organization for Standardization published it as ISO/TR 14696 in 1999.[6] In the handbook's table of equivalent fire test standards, ASTM E1623 and ISO/TR 14696 appear on the same line, among the bench-scale and intermediate-scale tests for heat and smoke release.[13]

The ICAL belongs to a family of scaled-up calorimeters. The oldest is the Factory Mutual Construction Materials Calorimeter, in which a 1.22 m × 1.22 m specimen faces down into a furnace with a maximum heat flux of 150 kW/m².[5] A calorimeter of the ICAL type was developed in Canada for facade systems. It exposes specimens of 1.22 m × 2.08 m to a maximum irradiance of 30 kW/m².[5] Hirschler treats the ICAL and the Single Burning Item test as North American and European versions of the same intermediate-scale concept.[4]

Apparatus and measurements

The main components of the ICAL are a radiant panel with radiant heat units and a sample holder with a top cap. Wire igniters, a water-cooled supporting frame, a weighing platform on a trolley and a collection hood with a gas sampling port complete the apparatus.[1] The panel is gas-fired and delivers a uniform heat flux to the specimen face.[1][4]

Side view of the ICAL: vertical radiant panel facing a 1 m square specimen on a weighing platform, with wire igniters and a hood above.
The intermediate-scale calorimeter (ICAL): a vertical gas-fired radiant panel heats a 1 m × 1 m specimen on a weighing platform; a collection hood above captures the combustion products for oxygen consumption calorimetry.

If combustion products from a gas-fired panel enter the measurement exhaust, the panel's oxygen consumption can exceed that of the specimen. Changes in panel flow can then distort the measured heat release rate; a separate heater exhaust avoids this baseline problem.[14]

The heat release rate is determined by oxygen consumption, which has been implemented in a number of intermediate-scale and large-scale calorimeters.[7] All combustion products must be collected and removed through an exhaust duct. The flow rate and the composition of the gases are measured far enough downstream for the gases to be well mixed.[15] The weighing platform gives the mass loss rate, and the hood gives the visible smoke development.[1] Hirschler lists the results as heat and smoke release, ignitability and flame spread across the specimen surface.[4]

The ICAL also serves as a quantitative ignition test. The specimen is exposed to a known heat flux from the radiant panel, and the time to ignition is measured.[16] Urbas used an infrared pyrometer to measure the surface temperature of wood specimens in an intermediate-scale calorimeter. This is more practical than holding a thermocouple against a receding char surface. The sensor responds between 8 and 12 µm, where the flame is transparent and soot radiation is negligible.[17] The surface emissivity must still be known, because a pyrometer measures both emitted and reflected radiation.[17]

Heat release rate and scale

The oxygen consumption method rests on Huggett's finding that about 13.1 kJ of heat is released per gram of oxygen consumed, to within ±5 %.[18] The heat release rate then equals this constant times the mass of oxygen removed per second, the oxygen flowing in with the air minus the oxygen leaving in the exhaust.[15]

Q˙=E(m˙aYO2a−m˙eYO2e)

Heat release rate measured in laboratory calorimeters is usually expressed per unit exposed surface area of the specimen, in kW/m².[10] The total heat release rate is the product of this value and the exposed area.

Q˙=q˙″A

Symbols
Symbol Description Unit
Q˙ total heat release rate kW
E heat released per mass of oxygen consumed, about 13,100 kJ/kg
m˙a, m˙e mass flow rate of combustion air and of exhaust gas kg/s
YO2a, YO2e mass fraction of oxygen in the combustion air (0.232 in dry air) and in the exhaust gas –
q˙″ heat release rate per unit exposed area kW/m²
A exposed specimen area m²

Janssens and Urbas compared nine wood products in the cone calorimeter and in an intermediate-scale calorimeter. A 100-fold increase in specimen area raised the heat release rate by only 10 %.[14] The effect is modest because flame heat feedback hardly depends on sample area in the vertical orientation, especially for materials with weakly luminous flames such as wood.[14] Babrauskas likewise reports that systematic differences between the two apparatus were surprisingly small, despite the tenfold difference in linear dimension. He notes that vertical specimens have thin flames, which vary little with scale.[19]

Smaller steps in size show similar trends. Nussbaum and Östman tested 13 materials at 0.1 m × 0.1 m and 0.2 m × 0.2 m. The larger size slightly shortened piloted ignition times and raised the average heat release rate per unit area over the first minute by about 12 % at exposures above 25 kW/m².[14] A larger specimen does, however, need a larger and more powerful heater to keep the irradiance uniform.[14]

Worked example. Suppose a wood panel gives an average heat release rate of 100 kW/m² in the cone calorimeter. At incident fluxes of 50 to 75 kW/m², values below 50 to 100 kW/m² often indicate a relatively low flammability hazard.[10] The cone specimen measures 0.1 m × 0.1 m, an area of 0.01 m², so it releases only 1 kW.[2]

The ICAL specimen of 1.0 m × 1.0 m has 100 times that area.[3] If the heat release rate per unit area rises by 10 %, as Janssens and Urbas found for wood, the ICAL records about 110 kW/m².[14] Over 1 m² this is a total of about 110 kW, against 1 kW for the cone specimen.

At the same imposed flux of 50 kW/m², the 1 m² ICAL specimen face receives 50 kW of incident radiant power; the 0.01 m² cone specimen receives 0.5 kW. These are flux × area at the specimen, not the gas or electrical input to the heaters. The cone heater, for example, has a 5 kW electrical element.[2] A larger specimen requires a more powerful heater to keep the incident flux uniform.[14]

Applications

The ICAL is used where bench-scale specimens cannot represent the product. Small-scale tests are often unable to deal with joints, multiple layers and product irregularities.[4] The 1.0 m × 1.0 m specimen allows complex or highly nonhomogeneous constructions to be tested.[3] Shaw notes that, because of its specimen size, the ICAL can measure the heat release of assemblies as well as materials.[20]

Shaw reports that the cone calorimeter and the ICAL are being used successfully to distinguish the burning rate characteristics of fire-retardant-treated wood and untreated wood products.[20] Unpublished Weyerhaeuser data in his chapter, measured at an irradiance of 50 kW/m², illustrate the effect. Southern yellow pine plywood had an average peak heat release rate of 237 kW and an average of 156 kW. Fire-retardant-treated plywood had 151 kW and 55 kW. The table does not name the apparatus.[21] The treatment thus lowered the peak by 36 % and the average by 65 %.

Paired bars: untreated plywood 237 kW peak and 156 kW average, fire-retardant-treated plywood 151 kW peak and 55 kW average.
Average peak and average heat release rate of untreated and fire-retardant-treated southern yellow pine plywood at an irradiance of 50 kW/m² (unpublished Weyerhaeuser data; the source does not name the apparatus).

In North America, the ICAL test was by 2008 used extensively as a predictor of full-scale fire performance, but not for regulatory purposes, "or at least not yet".[4] ICAL data can also feed fire models, but Babrauskas notes that they are still not full scale. Some additional analysis is therefore needed before the test data can be used in fire modelling.[3]

In the European Union, the Single Burning Item test fills the regulatory role. It was developed to regulate building products and feeds the European classification of construction products in EN 13501-1, the Euroclass system.[4][22] In the SBI, two specimens 1.5 m high and 0.5 m and 1 m wide form a corner and are exposed to a propane burner of about 30 kW.[4][7] The ICAL instead uses a flat specimen and a radiant panel, so its exposure is set by the panel rather than by a burner flame.[4] Madrzykowski and Stroup question whether the SBI reproduces the ISO 9705 room test, as intended, because its burner gives a rather small heat flux on the specimen. Sandwich panels with a metal facing and a combustible core have not given the same result in the two tests.[7]

Limitations and uncertainty

The main limitation found in round-robin testing is the spread of results. Babrauskas lists 95 % confidence limits from round robins for four heat release rate apparatus, with repeatability and reproducibility values given separately.[8] Hirschler notes that consistency of test outcomes within and between laboratories is an ongoing topic of debate.[23] Drysdale explains that the burning rate is very sensitive to the heat fluxes that drive it. This is why reproducibility is a major problem in fire experiments, particularly in standard tests.[24]

95 % confidence limits of heat release rate test apparatus from round robins[8]
Apparatus Year Laboratories Levels Peak HRR, repeatability (%) Peak HRR, reproducibility (%) Total heat released, repeatability (%) Total heat released, reproducibility (%)
Cone calorimeter 2000 4 16 17 23 8 15
ICAL 1999 3 8 56 67 72 118
Single Burning Item 1997 16 30 38 54 47 71
Room calorimeter 1994 12 5 65 79 25 41

For peak heat release rate, the ICAL repeatability value is about 3.3 times that of the cone calorimeter. For total heat released it is about 9 times larger. The ICAL round robin involved only three laboratories and eight levels, against 16 laboratories for the SBI.[8]

Grouped bars of repeatability and reproducibility for cone, ICAL, SBI and room calorimeter; ICAL reaches 56 and 67 % for peak and 72 and 118 % for total heat.
95 % repeatability (r) and reproducibility (R) values from round robins for four heat release rate apparatus, for peak heat release rate (left) and total heat released (right).

The method has a defined scope. The handbook definition covers nonmelting materials, vertically oriented and well ventilated.[1] Materials that melt fall outside it. Bench-scale heat release data are always apparatus dependent, and apparatus-specific factors must be considered when data are used to predict real-scale performance.[25] The same applies to the ICAL, whose data are not full scale.[3]

Related tests and common confusions

The ICAL should not be confused with the furniture calorimeter, an open hood under which complete items such as chairs and mattresses burn on a load cell, with no radiant panel.[5] Nor is it the same as the intermediate-scale flammability apparatus of FM Global, a larger version of the fire propagation apparatus for circular samples up to 305 mm in diameter.[26] The intermediate-scale multistory test apparatus of NFPA 285, a two-storey rig for exterior wall assemblies, is also a different test.[27]

The ICAL measures reaction-to-fire properties such as ignition, heat release and smoke, and not fire resistance.[4] NUREG-1805 nevertheless lists ASTM E1623 among the "empirical standard fire-resistance tests" in its appendix on fire test standards, although the ICAL is not a fire resistance test.[28]

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 Madrzykowski and Stroup (2008), p. 2-41.
  2. ↑ 2.0 2.1 2.2 Madrzykowski and Stroup (2008), p. 2-39.
  3. ↑ 3.0 3.1 3.2 3.3 3.4 3.5 3.6 3.7 Babrauskas (2002b), p. 3-3.
  4. ↑ 4.00 4.01 4.02 4.03 4.04 4.05 4.06 4.07 4.08 4.09 4.10 4.11 4.12 Hirschler (2008a), p. 6-48.
  5. ↑ 5.0 5.1 5.2 5.3 5.4 5.5 5.6 5.7 Janssens (2002), p. 3-57.
  6. ↑ 6.0 6.1 Madrzykowski and Stroup (2008), p. 2-47.
  7. ↑ 7.0 7.1 7.2 7.3 7.4 Madrzykowski and Stroup (2008), p. 2-40.
  8. ↑ 8.0 8.1 8.2 8.3 Babrauskas (2002b), p. 3-33.
  9. ↑ Madrzykowski and Stroup (2008), p. 2-37.
  10. ↑ 10.0 10.1 10.2 10.3 10.4 Madrzykowski and Stroup (2008), p. 2-36.
  11. ↑ Urbas and Luebbers (1995) and Urbas and Shaw (1993), as cited in Babrauskas (2002b), p. 3-34, and Janssens (2002), p. 3-62.
  12. ↑ Madrzykowski and Stroup (2008), p. 2-46.
  13. ↑ Hirschler (2008a), p. 6-38.
  14. ↑ 14.0 14.1 14.2 14.3 14.4 14.5 14.6 Janssens (2002), p. 3-50.
  15. ↑ 15.0 15.1 Janssens (2002), p. 3-46.
  16. ↑ Madrzykowski and Stroup (2008), p. 2-35.
  17. ↑ 17.0 17.1 Janssens (2002), p. 3-40.
  18. ↑ Janssens (2002), p. 3-45.
  19. ↑ Babrauskas (2002b), p. 3-10.
  20. ↑ 20.0 20.1 Shaw (2008), p. 6-134.
  21. ↑ Shaw (2008), p. 6-135.
  22. ↑ Hirschler (2008a), p. 6-49.
  23. ↑ Hirschler (2008a), p. 6-39.
  24. ↑ Drysdale (2008), p. 2-19.
  25. ↑ Janssens (2002), p. 3-56.
  26. ↑ Madrzykowski and Stroup (2008), p. 2-38.
  27. ↑ Janssens (2008), p. 2-69.
  28. ↑ Iqbal and Salley (2004), p. C-15.

References

  • Babrauskas, V. (2002b). Heat release rates. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-1–3-37). National Fire Protection Association; Society of Fire Protection Engineers.
  • Drysdale, D. (2008). Physics and chemistry of fire. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-3–2-20). National Fire Protection Association.
  • Hirschler, M. M. (2008a). Concepts and protocols of fire testing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-35–6-60). National Fire Protection Association.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Janssens, M. (2002). Calorimetry. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-38–3-62). National Fire Protection Association; Society of Fire Protection Engineers.
  • Janssens, M. L. (2008). Basics of fire containment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-59–2-74). National Fire Protection Association.
  • Madrzykowski, D., & Stroup, D. W. (2008). Flammability hazard of materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-31–2-48). National Fire Protection Association.
  • Shaw, J. R. (2008). Fire-Retardant and flame-resistant treatment of cellulosic materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-129–6-139). National Fire Protection Association.