A hyperbaric chamber is an enclosure in which patients are treated in gas at a pressure above atmospheric, usually with a deliberately increased percentage of oxygen.[1] Because the total pressure is raised, the partial pressure of oxygen rises too, so the chamber holds an oxygen-enriched atmosphere even when it is filled with ordinary compressed air.[2][3] Chambers range from small units for a single patient to rooms large enough for procedures on one or more patients with several attendants.[4] Their fire hazard comes from this atmosphere, in which most materials ignite at lower temperatures and with less energy, and burn and spread flame faster than in air.[5] In the United States, safety standards for chambers and hyperbaric facilities are set out in NFPA 99, as summarised in the 20th edition of the Fire Protection Handbook (2008).[3] The handbook calls for ignition and fuel controls in medical oxygen-enriched atmospheres and, for occupied oxygen-enriched spaces generally, describes rapid automatic fire suppression with water as an effective agent.[1][6]

Types and uses

The handbook describes the operation of hyperbaric chambers as a medical use of an oxygen-enriched atmosphere, in which the percentage of oxygen is typically increased on purpose. Some chambers are small and hold only one patient. Others are large enough for an operation or other procedure, with one or more patients and several attendants inside.[4] Medical air from a facility's compressed air system may also be used in chambers.[2]

The number of chambers in the United States grew during the latter part of the twentieth century. Most are in hospitals or other health care facilities and operate under NFPA 99, the US standard for health care facilities.[3] The growth brought a matching increase in freestanding hyperbaric facilities that operate independently of hospitals; these must also follow the safety codes and operational safeguards.[3] In a health care occupancy, the chamber is one of several places where oxidising gases are used near patients who often cannot be moved readily, because they depend on life-support equipment or are not mobile.[7]

Oxygen-enriched and compressed-air atmospheres also occur outside hospitals. The handbook lists underwater tunnelling and caisson work, deep-sea exploration, spaceflight and aviation among the uses of oxygen-enriched atmospheres.[8] Its table of compressed-air atmospheres relates pressure to depth: 2 atmospheres absolute corresponds to about 10 m of seawater, 3 atmospheres to about 20 m and 4 atmospheres to about 30 m.[9]

Pressure and oxygen enrichment

Pressure is the force exerted per unit area, measured in pascals.[10] Air contains about 21 percent oxygen and 78 percent nitrogen by volume.[11] An oxygen-enriched atmosphere is defined as one in which the oxygen concentration exceeds 21 percent by volume, or the partial pressure of oxygen exceeds 160 torr (21.3 kPa), or both.[8] The second part of this definition is the one that matters in a chamber. Air compressed above atmospheric pressure, 101 kPa, is itself an oxygen-enriched atmosphere, although it is less hazardous than pure oxygen.[2]

The partial pressure of oxygen is the oxygen volume fraction multiplied by the total absolute pressure. The handbook also states that, for a fixed percentage of oxygen, the minimum ignition energy varies inversely with the square of the pressure.[5] The first relation shows why compressed air counts as oxygen-enriched, and the second how strongly pressure lowers the energy needed for ignition.

pO2=xO2pEmin(p)Emin(p0)=(p0p)2

Symbol Description Unit
pO2 Partial pressure of oxygen kPa
xO2 Volume fraction of oxygen in the gas –
p Total absolute pressure in the chamber kPa
p0 Reference pressure, 1 atm (101.3 kPa) kPa
Emin Minimum ignition energy at a fixed oxygen percentage J

As a worked example, take a chamber filled with air at 3 atmospheres absolute (304 kPa). The oxygen partial pressure is 0.2095 × 304 = 63.7 kPa, about 480 torr, which matches the value in the handbook table.[9] This is three times the 21.3 kPa threshold of the definition and equals the oxygen partial pressure of a sea-level atmosphere with about 63 percent oxygen. In the handbook's simplified inverse-square trend at a fixed oxygen percentage, the relative minimum ignition energy is about one ninth of its value at 1 atmosphere; at 2 atmospheres it is one quarter.[5] The handbook calls its own description of these trends oversimplified, and adds that a minimum pressure exists below which ignition does not occur.[5]

Chart of oxygen partial pressure of air against chamber pressure, 1 to 5 atm, with the 21.3 kPa threshold and the falling ignition energy
Oxygen partial pressure of compressed air against chamber pressure, compared with the 21.3 kPa threshold of an oxygen-enriched atmosphere, and the relative minimum ignition energy at a fixed oxygen percentage.

Pressure alone does not decide the hazard. The degree of fire hazard varies with the oxygen concentration, the diluent gas and the total pressure. A mixture of 4 percent oxygen in nitrogen or helium at 12 atmospheres (1,216 kPa) does not support the combustion of paper, even though its oxygen partial pressure is 365 torr (48.7 kPa).[9] The table also shows how little oxygen is needed at depth for a normal partial pressure of 160 torr: 6.9 percent at 3 atmospheres and 4.2 percent at 5 atmospheres.[9]

Ignition and burning at elevated pressure

Raising the oxygen level or the total pressure makes ignition easier and burning faster. An increase in pressure generally broadens the flammability range of gases and vapours.[12] For solids, the handbook reproduces hot-plate ignition temperatures from NFPA 53 (2004). Cotton sheeting in air ignites at 465 °C at 1 atmosphere, 385 °C at 3 atmospheres and 365 °C at 4 atmospheres; in pure oxygen the values are 360, 340 and 325 °C.[13] Paper drapes in air ignite at 470 °C at 1 atmosphere and 405 °C at 4 atmospheres.[13] Experiments by Alvares and Martin, as summarised in the SFPE Handbook, showed that higher oxygen content or pressure dramatically shortens the time to radiant ignition of cellulose and lowers the surface temperature at ignition.[14]

Line chart of hot-plate ignition temperature against total pressure for cotton sheeting and paper drapes in air and in pure oxygen
Minimum hot-plate ignition temperatures of cotton sheeting and paper drapes in air and in 100 percent oxygen at 1 to 4 atmospheres.

The rate of flame spread is the single most important property for fire development in an oxygen-enriched atmosphere. It increases with the oxygen concentration at constant pressure and with the total pressure at a constant oxygen percentage, and it is much greater upwards than sideways or downwards.[15] Measurements on strips of filter paper held at an angle of 45 degrees illustrate the effect. In compressed air the burning rate was about 1.1 to 1.2 cm/s at 1 atmosphere, 1.8 cm/s at 4.03 atmospheres and 3.1 to 3.3 cm/s at 10.09 atmospheres. In nearly pure oxygen at 1 atmosphere it was 4.19 cm/s.[16] Averaged per pressure, these values mean that compressed air at about 4 atmospheres burns paper roughly 1.6 times as fast as air at sea level, and pure oxygen about 3.6 times as fast.

Scatter chart of burning rate of filter paper strips against total pressure in compressed air, with a single point for pure oxygen at 1 atmosphere
Burning rates of filter paper strips at 45 degrees in compressed air from 1 to 10 atmospheres, with the rate in 99.6 percent oxygen at 1 atmosphere for comparison.

Flames are also hotter when more oxygen is available. A guide of the US Nuclear Regulatory Commission, NUREG-1805, compares the hottest part of a Bunsen burner flame, about 1,600 °C, with that of an oxygen-acetylene torch, about 3,500 °C. It notes that any increase in the oxygen supply, including an oxygen-enriched atmosphere, gives higher temperatures than combustion in a normal atmosphere.[17] In the oxygen-index tests discussed by the handbook, many common materials ignite and burn in as little as 16 percent oxygen, while fluorocarbon plastics did not propagate flames even in 100 percent oxygen.[18]

Textiles show the same trends. A high-temperature nylon fabric (Nomex) kept its flame-retardant qualities in compressed air at about 400 kPa gauge pressure (59 psig, or roughly 5 atmospheres absolute). At that pressure and oxygen concentrations of 40 percent and above it did burn, though much more slowly than untreated fabrics.[19] In the separate hot-plate tests the same fabric ignited above 600 °C in air up to 3 atmospheres absolute, but at 470 °C in pure oxygen at 4 atmospheres absolute.[13]

Ignition sources and materials

The handbook lists the potential ignition sources in hospital oxygen-enriched atmospheres. They include electrosurgical units, lasers, fibreoptic light sources, heat of adiabatic compression of gases, electric and friction sparks, heated objects, static electricity, short circuits and defibrillators.[1] Fire prevention therefore aims at redundancy, so that no fire or explosion occurs even if one safety element fails or is omitted.[1] Cylinder valves should be opened slowly, so that compression heating stays low. Aluminium can burn under oxygen enrichment and high pressure, and brass regulators are preferred to aluminium ones.[1]

The fuels in such atmospheres include mattresses, sheets and drapes, patient hair, anaesthesia and respiratory equipment, cleaning solutions, rubber gloves, oxygen tubing and masks, gauze and the intestinal gases hydrogen and methane. Cylinders, regulators and pipelines carrying compressed air, oxygen or nitrous oxide must be cleaned for that service and kept free of hydrocarbon contaminants such as solvents and lubricants.[1] The gas supply itself is part of the hazard. Cylinders exposed to fire can vent or explode, so most hospitals pipe their gases from remote sources through a medical gas system built to NFPA 99.[20][21]

For components and materials, the handbook recommends a systematic oxygen compatibility assessment. It starts from the most severe operating conditions, assesses the flammability of the materials and the likely ignition mechanisms, and traces the kindling chain by which a small fire could breach the system. It then judges the possible loss of life and function, and records and reviews the result.[16] The ignition mechanisms of concern include rapid pressurisation, flow friction, particle and mechanical impact, static discharge and electrical arcs.[5]

Fire suppression

Fire extinguishing systems for oxygen-enriched atmospheres must meet requirements beyond those of conventional systems. The causes are easy ignition, faster flame spread and burning intensity, and the flammability of materials that are flame-resistant in air.[6] The handbook states that these requirements cannot be met by simply extending traditional techniques, and that emergency personnel need special training. Extinguishants must act rapidly, be non-toxic and produce no toxic or corrosive decomposition products.[6] Fixed systems should actuate automatically within 1 second of a detectable flame, with manual actuation as well. A manual water hose of at least 13 mm (½ in.) inside diameter, with a nozzle pressure at least 345 kPa (50 psi) above ambient, is usually provided in occupied areas.[6]

Water has proved effective when applied in sufficient quantity. In the handbook's cited test condition, a spray density of 50 L/min per m² (1¼ gpm/ft²) applied for 2 minutes extinguishes cloth burning in 100 percent oxygen at atmospheric pressure. This amounts to about 100 L per m² in that test, not a design criterion established for every chamber.[6] The water must reach the whole protected space at the minimum density selected for the application, and penetrate deep enough to extinguish fires in layered materials such as clothing.[6] In a chamber at 3 atmospheres absolute, the 345 kPa hose margin means a nozzle pressure of at least about 650 kPa absolute.

Illustrative cross-section of a multiplace hyperbaric chamber with water spray nozzles, flame detector, hand hose, and gas supply piped from outside
Illustration applying general 2008 handbook guidance for occupied oxygen-enriched spaces to a multiplace chamber; the cited water-spray density was tested on cloth in pure oxygen at atmospheric pressure and is not a chamber design criterion.

One way to deliver such water spray is a deluge system. Its open sprinklers or nozzles have no heat-sensitive elements, and a deluge valve opened by a separate detection system admits water to all of them at once.[22] Where extremely fast response is needed, the piping can be prefilled with water up to the open heads, which are closed by blow-off caps; this is sometimes called a "hot" deluge system.[23] The pilot-actuated nozzle of ultra-high-speed water spray systems was first called the "aerospace" nozzle because of its use in hyperbaric chambers for the space programme. Each such nozzle works like its own wet-pilot-actuated deluge valve.[24] NFPA 15 defines an ultra-high-speed water spray system as one that starts discharging water within 100 milliseconds of detection.[25]

Among other agents, Halon 1301 has proved effective in oxygen-enriched atmospheres, but halogenated agents are restricted by the Montreal Protocol.[6] Carbon dioxide and nitrogen act as diluents and must be restricted in occupied areas.[6] Such gases slow or stop a fire at the price of oxygen depletion, which exposes anyone nearby to asphyxiation.[20] Carbon dioxide, for example, extinguishes by lowering the oxygen content below the 15 percent needed for diffusion flames, and it is lethal at extinguishing concentrations.[26][27] Fire blankets of Nomex, wool or fibreglass should not be relied on, and dry chemical agents are ineffective in compressed air because burning continues in gas pockets.[6][2] Electrical equipment that is burning must first be de-energised and can then be extinguished with water.[2]

Building design and evacuation

Patients in health care facilities often cannot be moved readily, so a fire is more dangerous to them than in other environments.[7] Building regulations also take this into account. In New Zealand, Verification Method C/VM2 (second edition, 2025) names the hyperbaric chamber among spaces whose occupants, undergoing treatment, stay in place or evacuate to a place of safety inside the building.[28] These spaces must comply with the C/VM2 definition of a place of safety. Because they are usually climate controlled, the design of smoke detection and air handling smoke control needs special care.[28]

C/VM2 defines a place of safety inside a building by four conditions. It must be enclosed by fire separations able to withstand burnout at the fire source, in a building with automatic sprinklers to NZS 4541 or NZS 4515. It must also be designed for the intended number of people and have enough means of escape to a safe place outside.[29] For the United States, the handbook refers to NFPA 99 for the safety standards of chambers and hyperbaric facilities.[3]

Limits and common misconceptions

An oxygen-enriched atmosphere does not always mean a greater fire hazard. Some enriched atmospheres burn much like air, and some cannot support combustion of normally flammable materials at all. Most of those met in practice, however, do increase the hazard.[9] The opposite belief, that a chamber filled with air rather than oxygen is safe, is also wrong: compressed air above atmospheric pressure is itself an oxygen-enriched atmosphere in which extinguishment is difficult.[2]

Helium mixtures are not a cure either. Helium delays ignition because it conducts heat better than nitrogen, but if a fire starts, flames spread faster and burn hotter.[2] Materials that are flame-resistant in air may burn in enriched atmospheres, so they must be tested under the conditions of intended use.[15][6] The quantitative data in this article come mainly from NFPA 53 tables of 2004 and older test series, summarised in a 2008 US handbook. The handbook gives no statistics or case histories of chamber fires, and the editions of NFPA 99 it refers to are not stated.[13][3]

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 1.4 1.5 Allen (2008), p. 6-194.
  2. ↑ 2.0 2.1 2.2 2.3 2.4 2.5 2.6 Allen (2008), p. 6-191.
  3. ↑ 3.0 3.1 3.2 3.3 3.4 3.5 Allen (2008), p. 6-195.
  4. ↑ 4.0 4.1 Allen (2008), pp. 6-194–6-195.
  5. ↑ 5.0 5.1 5.2 5.3 5.4 Rosales and Stoltzfus (2008), p. 9-227.
  6. ↑ 6.00 6.01 6.02 6.03 6.04 6.05 6.06 6.07 6.08 6.09 Rosales and Stoltzfus (2008), p. 9-242.
  7. ↑ 7.0 7.1 Allen (2008), p. 6-187.
  8. ↑ 8.0 8.1 Rosales and Stoltzfus (2008), p. 9-225.
  9. ↑ 9.0 9.1 9.2 9.3 9.4 Rosales and Stoltzfus (2008), p. 9-226.
  10. ↑ Van Rossum (2027), §3.2.
  11. ↑ Van Rossum (2027), §4.2.
  12. ↑ Rosales and Stoltzfus (2008), p. 9-228.
  13. ↑ 13.0 13.1 13.2 13.3 Rosales and Stoltzfus (2008), p. 9-232.
  14. ↑ Alvares and Martin (1971), as cited in Kanury (2002a), p. 2-239.
  15. ↑ 15.0 15.1 Rosales and Stoltzfus (2008), p. 9-235.
  16. ↑ 16.0 16.1 Rosales and Stoltzfus (2008), p. 9-237.
  17. ↑ Iqbal and Salley (2004), p. 3-9.
  18. ↑ Rosales and Stoltzfus (2008), p. 9-233.
  19. ↑ Stull and Chines (2008), p. 6-99.
  20. ↑ 20.0 20.1 Allen (2008), p. 6-188.
  21. ↑ Allen (2008), p. 6-190.
  22. ↑ Huggins (2008), p. 16-37.
  23. ↑ Isman (2008), p. 16-20.
  24. ↑ Gagnon (2008), p. 16-122.
  25. ↑ Gagnon (2008), p. 16-109.
  26. ↑ Iqbal and Salley (2004), p. B-46.
  27. ↑ Iqbal and Salley (2004), p. B-50.
  28. ↑ 28.0 28.1 Ministry of Business, Innovation and Employment (2025b), p. 34.
  29. ↑ Ministry of Business, Innovation and Employment (2025b), p. 68.

References

  • Allen, M. (2008). Medical gases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-187–6-196). National Fire Protection Association.
  • Gagnon, R. M. (2008). Ultra-High-Speed water spray systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 16-109–16-133). National Fire Protection Association.
  • Huggins, R. (2008). Automatic sprinkler systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 16-29–16-53). National Fire Protection Association.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Isman, K. E. (2008). Automatic sprinklers. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 16-15–16-28). National Fire Protection Association.
  • Kanury, A. M. (2002a). Flaming ignition of solid fuels. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-229–2-245). National Fire Protection Association; Society of Fire Protection Engineers.
  • Ministry of Business, Innovation and Employment. (2025b). Verification Method C/VM2: Framework for fire safety design (2nd ed.).
  • Rosales, K., & Stoltzfus, J. M. (2008). Oxygen-Enriched atmospheres. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-225–9-243). National Fire Protection Association.
  • Stull, J. O., & Chines, S. A. (2008). Fibers and textiles. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-75–6-102). National Fire Protection Association.
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.