Powder coating is the application of an organic coating as a dry powder, which is usually charged electrostatically, held on a grounded workpiece and melted into a continuous film in an oven.[1] Unlike liquid spray finishing, the process uses no organic solvents and leaves no readily ignitable residues, and it produces no flammable vapours.[1][2] Its hazard lies in the powder itself. Combustible organic powders burn vigorously when suspended in air and can explode when confined, so powder coating is still classed as a hazardous process.[2]
A cloud of coating powder needs much more energy to ignite than a solvent vapour, and powder lying on parts, walls or floors is not readily ignitable.[2] The most serious events are explosions of the powder collector that recovers overspray, and secondary explosions of powder that has escaped into the building.[3][4] Protection therefore rests on several measures. Powder concentrations in ducts are kept well below the explosible range, and sparks of static electricity from ungrounded objects are controlled. Fast flame detection triggers automatic shutdown, and confined volumes are vented or eliminated.[3][4] The Fire Protection Handbook (2008) treats powder coating together with liquid spray finishing and describes US practice around 2007.[1]
Process and equipment
In the usual process the powder is first suspended in air and then charged by a direct-current supply. The handbook gives 60 to 120 kV for this supply in one place and 30 to 100 kV for powder power supplies in another.[1][5] The charged powder is directed at the grounded workpiece and held there by electrostatic forces until it passes through a process oven, where it melts into a continuous coating.[1] The curing step links the process to the Industrial oven and furnace.
Most powder is applied with spray guns, which are fed with a mixture of powder and air through a single tube. Corona-type guns receive high voltage through a separate cable. Inside the gun, the charging circuit is connected to the electrode through a 75 to 250 MΩ resistor, and a faint blue glow called a corona forms at the electrode tip. Particles are charged as they pass through it.[5]
Tribocharging guns need no external high voltage, because the powder is charged by friction between fast airborne granules and the inner surfaces of the gun.[5] Guns with an integrated power supply have no high-voltage cable and run on a light cable carrying about 12 V. For handguns each gun has its own supply, which is energised only while the trigger is pulled.[5]
A device called a feeder mixes powder with air and supplies the guns. The powder is held in a fluidised bed or in a hopper with a cone-shaped bottom, and one feeder may serve several guns with a separate ejector for each.[5] Epoxy is the most common coating powder; others include acrylic, polyester, vinyl, nylon, butyrate, polyolefin and alkyd. Powders arrive in containers of 11.34 to 453.6 kg (25 to 1000 lb).[5]
Small workpieces, less than about 102 mm (4 in.), and long ribbons or cables can be coated in an electrostatic fluidised bed. Air flowing up through a porous floor makes the powder behave like a liquid, electrodes charge it, and grounded workpieces passing above collect a coating.[1] In a non-electrostatic variant, the workpiece is preheated well above the melting point of the powder and then dipped into a fluidised bed or sprayed. The powder melts on contact and is cured afterwards in an oven.[1][6] Fluidised beds usually have a peripheral exhaust that captures escaping grains before they spread into the factory.[6]
Booths and powder recovery
Almost all powder spraying takes place in booths that are more tightly enclosed than those for liquid coatings and let much less overspray escape.[2] A common arrangement is a Spray booth with a hopper bottom, through which exhaust air is drawn into a duct leading to a powder collector. A cloth or fabric filter in the collector separates the powder, which falls into a hopper and is returned to the feeder.[7] A cyclone between booth and collector may remove larger particles first. The collector is a type of Dust collector, and its confined interior is where the explosion hazard concentrates.[7][3]
A more recent design integrates booth and powder recovery in one structure. Cartridge filters and the exhaust fan are built into the booth, the connecting duct is eliminated, and the recovered powder is pumped pneumatically straight back to the feeders.[8] According to the 2008 handbook this arrangement had become dominant in new installations over the preceding three decades, and many booths had walls and roofs of flame-retardant plastic.[6] Pipe coaters, with a ring of automatic guns around a conveyor, coat preheated pipes and structural steel and use a similar exhaust and recovery system.[6]

To keep powder inside, the booth needs an effective capture velocity at all openings. Scarbrough (2008b) gives minimum average velocities of about 18 m/min (60 ft/min), or 0.3 m/s. Interlocks should allow the application equipment to run only while the ventilation runs, and the electrostatic supply only while powder is actually being applied.[3][9] Hose and pipe connections of the pneumatic transfer equipment should be checked routinely. A connection that breaks in operation can blow powder into the workroom.[2]
Why powder is a hazard
A powder particle is a solid fuel. Solids burn indirectly: they must first be heated until they release flammable gases, which then burn in the flame.[10] For dust clouds, Zalosh (2002) explains that the minimum explosible concentration (MEC) falls as particles get smaller, down to a limiting size. Above that size the reaction is limited by the release of volatiles from the particle surface.[11] A fine powder can therefore form an explosible cloud at a lower concentration, the starting point of a Dust explosion.
The energy needed to ignite a cloud of coating powder is 100 to 1000 times higher than that needed for flammable vapours.[2] For combustible dusts in general, Schwab (2008c) reports that most measured minimum spark ignition energies lie between 10 and 40 mJ. Most flammable vapours need 0.2 to 10 mJ, which leads to a general rule that dusts need 20 to 30 times the energy of vapours.[12] The two handbook chapters thus give different ratios, one for coating powders and one for dusts in general. The Minimum ignition energy of a given dust is measured with a spark in a 1.2 L tube, and capacitive sparks need more energy than longer inductive sparks.[13]
Test data for epoxy resin, the most common coating powder, appear in both handbooks. A sample with a median particle size of 26 µm had an MEC of 30 g/m³, a minimum cloud ignition temperature of 510 °C and a maximum explosion pressure of 7.9 bar(g). Its KSt value was 129 bar·m/s, and as a layer it melted rather than glowed.[11] KSt, the deflagration index, is the maximum rate of pressure rise multiplied by the cube root of the test vessel volume.[14]
The table in the handbook dust chapter gives the same values for epoxy resin. For polyester powder it lists a maximum explosion pressure of 10.1 bar(g) and an index of 194 bar·m/s.[15] Scarbrough (2008b) asks for pressure relief vents on the collector to prevent its rupture in an explosion.[3]
Ignition sources and static electricity
In the United States, electrical equipment in a powder coating Division 1 area should, as described in the 2008 handbook, be listed for Class II, Division 1 locations. In the Division 2 area, wiring and apparatus should be dust-tight and have no hot surfaces. Explosionproof equipment listed only for Class I (gas and vapour) locations is not appropriate.[3] Class II, Division 1 covers locations where combustible dust is in the air in normal operation in quantities that can form explosive or ignitable mixtures.[16] Class II equipment is dust-ignitionproof: it keeps dust out and must not overheat under a dust layer, but it is not built to resist an internal explosion.[17]
Static electricity on electrically isolated conductive objects is a major potential cause of fires in electrostatic powder coating. Metal workpieces on hangers that do not ground them pass through the spray zone while discharging hot sparks. Ungrounded metal blowpipes or wands used for booth cleaning can be charged by friction and ignite the powder being blown off the floor.[3] Some application equipment itself sparks when a grounded object comes too close, so grounded objects must be kept further from the charged elements than twice the sparking distance. Sparks during use may be traceable to poor racking of parts or swinging conveyor racks.[3]
Not every discharge can ignite powder. Brush discharges, which can ignite gases and vapours, cannot ignite common dusts; spark discharges and propagating brush discharges can.[18] A propagating brush discharge comes from a thin insulating layer, less than 6 mm thick, backed by a conductive surface on which an intense charge has been stored.[19] Exactly this has ignited powder clouds inside thin-walled non-conductive transfer hoses. It has also happened in grounded metal ducts of dust collectors where thermoplastic powder had impact-fused into a non-conductive coating at an elbow or wye.[3][20] Grillwork at duct intakes and magnets for tramp metal reduce mechanical sparks from fallen parts, and hot work permits and a smoking ban complete the controls.[3]
The energy of a spark from an isolated conductor is , so the voltage at which a conductor of capacitance can release the energy is .[18][13] In Zalosh's example, an ungrounded silo of 500 pF holding a powder that needs 50 mJ for a capacitive spark becomes dangerous at about 14 kV.[13] Applying the same equation to a 500 pF conductor and the 10 to 40 mJ range for dusts gives 6.3 to 12.6 kV. For a vapour needing 0.25 mJ, only 1.0 kV would suffice.[21] Powder guns work at tens of kilovolts, and poorly grounded workpieces in the spray zone are known to discharge hot sparks.[5][3]
Keeping the duct below the explosible range
To stop a booth fire from spreading through the ductwork, the ventilation is usually arranged to keep the powder concentration in the duct below one-half of the MEC.[3] The MEC is determined in a closed test vessel. The US standard ASTM E1515 uses a 20 L vessel with a 2500 J or 5000 J pyrotechnic igniter, and the result depends on igniter energy and turbulence.[11] In steady operation the dust concentration in a duct equals the mass flow of powder carried into it divided by the volume flow of air.[13]
| Symbol | Description | Unit |
|---|---|---|
| Mean powder concentration in the exhaust duct | g/m³ | |
| Mass flow of powder drawn into the duct (overspray not deposited on parts) | g/s | |
| Volume flow of exhaust air | m³/s | |
| MEC | Minimum explosible concentration of the powder | g/m³ |
Worked example. Assume a booth with 3 m² of openings in total and the minimum average capture velocity of 0.305 m/s (60 ft/min). The exhaust flow is then Q = 3 × 0.305 = 0.914 m³/s. For the SFPE epoxy resin dust sample, the MEC is 30 g/m³.[11] Half of that is 15 g/m³. At the assumed airflow, at most 15 × 0.914 = 13.7 g/s (0.82 kg/min) of powder may enter the duct. If an assumed 0.30 kg/min (5.0 g/s) enters, the concentration is 5.5 g/m³, or 18 % of the MEC.[22]
The example also shows why the margin matters. Doubling the powder flow doubles the concentration, and halving the airflow through fouled filters does the same. Both together raise the example to 21.9 g/m³, or 73 % of the MEC; a system designed exactly at the half-MEC limit would reach the MEC with either change alone.[22] These are the failures found in practice: collector explosions with duct concentrations above the MEC followed increases in application rate to more than double the design rate, or loss of airflow from poor filter maintenance.[4] The calculation treats the duct as uniformly mixed and steady, so local clouds at bends, hoppers and filters can be richer than the mean value. Zalosh (2002) also warns that measured dust concentrations can be deceptively low and that upset conditions can produce considerably higher ones.[11]
Some application systems must run with combustible concentrations between the booth and the collector. In that case a fire in the application area can cause an almost instantaneous collector explosion. Scarbrough (2008b) recommends either an engineered suppression system or a fire- and explosion-resistant design of the application and collection equipment.[3]
Fire and explosion protection
The handbook lists four protective aims. A fire in the spray area must be kept from reaching the powder collector, and the collector needs pressure relief vents and vent ducts. The building must be protected from heat and pressure, and sprinklers or other approved suppression must control a persistent fire.[3]
A fast flame detector in the booth is the first line. Linked to interlocks and a fast damper in the duct, it shuts off all energy supplies, including electricity and compressed air, and closes the damper within about ½ second. The sequence can be extended to discharge an inerting gas into the dust collector.[3] Speed matters because a fire lasting longer than about 15 seconds forms glowing embers that can ignite the collector regardless of the powder concentration.[3]
Field experience supports this approach. Multispectral flame detectors from one manufacturer have been monitored over millions of operating hours. Fires ignited many times, but none caused damage where the system was properly installed and maintained. Optical detectors came into use in 1974 to 1975, and before then damaging fires and explosions were common.[3] About a dozen damaging incidents since then all involved missing or bypassed detectors, unmaintained detectors, or detectors whose view of the guns was blocked. Dirty or covered lenses were also frequent, and replacement wear parts not authorised by the manufacturer led to ignition in several cases.[3][4]
Clouds of powder burn far faster in a confined space, and the inside of a conventional collector is confined. The usual protection is automatic pressure relief vents in the collector housing, which open on ignition and release the combustion products.[3] Indoors, a vent duct must lead them outside or to a safe place, and it must be short: lengths above 3 m (10 ft) are of questionable value. A collector explosion projects fire, unburned powder and molten globules from the vents and from booth openings, and venting into the building can cause a major secondary explosion.[3]
The integrated booth and collector virtually eliminates the explosion hazard, because it has no confined space in which an explosion could form. It therefore needs no explosion vent, but flame detectors are still needed with automatic guns to stop the powder feed quickly. A burning powder cloud at a gun or above a fluidised bed can usually be extinguished almost at once by turning off the feeder or the fluidising air. The feed velocity exceeds the flame speed, so flames do not travel back through the hoses even where the concentration in the hose exceeds the MEC.[4]
Automatic sprinklers are commonly required in factory areas with powder coating and inside booths and collectors. With automatic flame detection, however, powder fires are usually out after shutdown before any sprinkler opens. For small fires that persist in booth residues, portable water extinguishers or sprinklers protecting the filter cartridges or bags have proved adequate. That finding comes from the author's unpublished experiments and fire investigations.[4]
Housekeeping, storage and secondary explosions
Powder in its shipping containers is not normally treated as a hazardous material and is stored like ordinary combustibles. Containers must still be handled with care, because a broken container can release a dust cloud.[2] Waste powder is usually packed in lined fibre drums or cartons and sent to landfill under US Environmental Protection Agency rules. If the container is baked first, the powder fuses into a solid block that cannot disperse.[2] Spills are cleaned up with an industrial vacuum approved for combustible dust. Explosions have occurred with unapproved vacuums that had open-frame universal motors and sparking commutators.[2]
Escaped powder settles on horizontal surfaces and creates the potential for a secondary explosion. A primary explosion can throw this powder into suspension, where flames or embers from the first event ignite it. If much powder is lifted, the secondary explosion can be considerably more serious than the primary.[4] The dust chapter of the handbook describes the same sequence for dusts in general, with explosions sometimes running from room to room or building to building.[23] Zalosh (2002) adds the mechanism: process equipment that cannot withstand the closed-vessel explosion pressure fails and produces a blast wave that lifts settled dust.[14] Protection rests mainly on equipment maintenance, procedures and scrupulous housekeeping to collect any powder that escapes.[4]
Scope and limits of the sources
The rules quoted here are US practice as described in the 2008 handbook, not current or universal requirements. For further safeguards the chapter refers to NFPA 33 on spray application, NFPA 68 on deflagration venting, NFPA 69 on explosion prevention and NFPA 77 on static electricity, without naming editions.[4] The adequacy of water extinguishers rests on the author's unpublished research, of which no formal consolidation has been written, and the 15-second ember threshold is given without a reference.[3][4]
The sources also differ in detail. The chapter gives two voltage ranges for powder charging, 60 to 120 kV and 30 to 100 kV.[1][5] It puts the ignition energy of powder clouds at 100 to 1000 times that of vapours, while the dust chapter's general rule is 20 to 30 times.[2][12] Neither explosibility table gives a minimum ignition energy for epoxy resin, so the worked examples use ranges rather than a value for a specific powder.[11][15]
See also
- Explosion venting
- Deflagration index
- Explosion suppression system
- Inerting
- Hazardous area classification
Notes
- ↑ 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 Scarbrough (2008b), p. 9-28.
- ↑ 2.00 2.01 2.02 2.03 2.04 2.05 2.06 2.07 2.08 2.09 Scarbrough (2008b), p. 9-35.
- ↑ 3.00 3.01 3.02 3.03 3.04 3.05 3.06 3.07 3.08 3.09 3.10 3.11 3.12 3.13 3.14 3.15 3.16 3.17 3.18 3.19 3.20 Scarbrough (2008b), p. 9-36.
- ↑ 4.00 4.01 4.02 4.03 4.04 4.05 4.06 4.07 4.08 4.09 Scarbrough (2008b), p. 9-37.
- ↑ 5.0 5.1 5.2 5.3 5.4 5.5 5.6 5.7 Scarbrough (2008b), p. 9-31.
- ↑ 6.0 6.1 6.2 6.3 Scarbrough (2008b), p. 9-33.
- ↑ 7.0 7.1 Scarbrough (2008b), p. 9-32.
- ↑ Scarbrough (2008b), pp. 9-32–9-33.
- ↑ Unit conversion based on Scarbrough (2008b), p. 9-36.
- ↑ Van Rossum (2027), §4.1.
- ↑ 11.0 11.1 11.2 11.3 11.4 11.5 Zalosh (2002), p. 3-404.
- ↑ 12.0 12.1 Schwab (2008c), p. 6-144.
- ↑ 13.0 13.1 13.2 13.3 Zalosh (2002), p. 3-405.
- ↑ 14.0 14.1 Zalosh (2002), p. 3-409.
- ↑ 15.0 15.1 Schwab (2008c), p. 6-146.
- ↑ Milatovich (2008), p. 8-170.
- ↑ Milatovich (2008), p. 8-172.
- ↑ 18.0 18.1 Scarbrough (2008a), p. 11-61.
- ↑ Scarbrough (2008a), p. 11-67.
- ↑ Scarbrough (2008a), p. 11-65.
- ↑ Calculation with values from Scarbrough (2008a), p. 11-61; Schwab (2008c), p. 6-144; and Zalosh (2002), p. 3-405.
- ↑ 22.0 22.1 Calculation with values from Scarbrough (2008b), p. 9-36, and Zalosh (2002), pp. 3-404–3-405; the opening area and powder flow are assumed values.
- ↑ Schwab (2008c), p. 6-141.
References
- Milatovich, R. M. (2008). Electrical systems and appliances. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-127–8-173). National Fire Protection Association.
- Scarbrough, D. R. (2008a). Control of electrostatic ignition sources. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-59–11-68). National Fire Protection Association.
- Scarbrough, D. R. (2008b). Spray finishing and powder coating. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-27–9-37). National Fire Protection Association.
- Schwab, R. F. (2008c). Dusts. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-141–6-152). National Fire Protection Association.
- Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.
- Zalosh, R. (2002). Explosion protection. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-402–3-421). National Fire Protection Association; Society of Fire Protection Engineers.