Skip to content
From Fire Safety Academy Wiki
Contents
  1. 1Material and history
  2. 2Chemistry and degree of nitration
  3. 3Decomposition and burning behaviour
  4. 4Toxic combustion products
  5. 5Storage, handling and transport
  6. 6Fire protection and extinguishment
  7. 7Archives, libraries and museums
  8. 8See also
  9. 9Notes
  10. 10References

Cellulose nitrate film is photographic, motion picture and X-ray film with a base of cellulose nitrate, a cellulose plastic also known as nitrocellulose or pyroxylin.[1][2] It presents a hazard of flash burning. Once heated above about 150 °C (300 °F), it decomposes in a reaction that produces its own heat and needs no air from outside.[3][1] The hazard was controlled by phasing nitrate film out and replacing it with slow-burning acetate "safety film". The 2008 handbook states that all photographic film made in the United States and Canada since 1952 used a safety base.[3][2]

Old nitrate film remained a concern in the 2008 handbook. By 2008, appreciable quantities of nitrate motion picture film and aerial film still existed, and some hospitals still kept old X-rays on nitrate base.[2] People who handle such film may not know its hazards or the precautions it needs.[2] A fire in nitrate film needs large volumes of water, cannot be smothered with carbon dioxide and gives off poisonous oxides of nitrogen.[2][4] For the United States, the 2008 handbook points to NFPA 40, Standard for the Storage and Handling of Cellulose Nitrate Film.[2]

Material and history

Cellulose nitrate is made by the action of nitric and sulfuric acids on cellulose materials such as cotton.[1] It belongs to the cellulosics, plastics produced by chemical modification of cellulose, a natural polymer obtained mainly from cotton linters and wood pulp.[5] Wood cellulose is the raw material for products as different as motion picture film, textile fibres, lacquers, explosives and propellants.[6][7] In the NFPA classification of polymers, the cellulosics are grouped with the thermoplastics.[8]

Cellulose nitrate is one of the oldest plastics. Mixed with camphor it gives celluloid, which dates from about 1870, only a decade after vulcanised fibre.[9] Pyroxylin plastic is the lower nitrated product and contains 11 to 12 percent nitrogen.[1] The handbook also uses the term pyroxylin for cellulose nitrate as a whole. For its storage as a plastic in the United States, the 2008 handbook points to NFPA 42, Code for the Storage of Pyroxylin Plastic.[2]

Cellulose acetate later replaced the hazardous nitrate for photographic use under the name "safety film".[5] Cellulose triacetate, which carries three acetate groups on each glucose unit of the cellulose molecule instead of two, became the prevalent base for photographic safety film.[10] Safety-base film may also be polyester.[2] Most articles once made of cellulose nitrate now use less hazardous plastics. It was still used to some extent for shoe heels, some housewares and as a pigment in lacquers, and an engraving process in some printing plants used cellulose nitrate plates.[1][2]

Chemistry and degree of nitration

Cellulose nitrate is unstable because it carries its own oxidiser. Combustion is a set of exothermic reactions between a fuel and an oxidiser, usually oxygen from the air.[11] Gunpowder achieves a reactive mixture physically, by mixing a fuel with a nitrate. When reactive groups such as the nitrate group are built chemically into the fuel molecule, as in cellulose nitrate or trinitrotoluene, the result can be highly unstable and can decompose violently.[12]

The handbook table of heats of combustion gives three formulas for cellulose nitrate. They have one, two or three nitrate groups per repeating unit: C6H9NO7, C6H8N2O9 and C6H7N3O11.[13] Each further nitrate group replaces one hydrogen atom by NO2. With the atomic weights of the handbook (C 12.01, H 1.01, N 14.01, O 16.00), each nitrate group adds 45.00 g/mol to the molar mass of the unit.[14] The nitrogen content then depends on the number of nitrate groups k as follows:

Line chart of nitrogen content against nitrate groups per unit: 6.76, 11.11 and 14.14 percent, with a band at 11 to 12 percent for pyroxylin.
Nitrogen content of cellulose nitrate with one, two and three nitrate groups per unit; pyroxylin plastic, with 11 to 12 percent nitrogen, lies between the dinitrate and the trinitrate.

wN=100kANM0+kΔM

Symbols in the nitrogen content relation
Symbol Description Unit
wN nitrogen content of the cellulose nitrate, by mass percent
k number of nitrate groups per repeating unit (1 to 3) –
AN atomic weight of nitrogen, 14.01 g/mol
M0 molar mass of the unit without nitrate groups, 162.16 g/mol
ΔM increase of molar mass per nitrate group, 45.00 g/mol

Worked example: nitrogen content. For the dinitrate, C6H8N2O9, the molar mass is 6 × 12.01 + 8 × 1.01 + 2 × 14.01 + 9 × 16.00 = 252.16 g/mol. Its nitrogen content is therefore 2 × 14.01 / 252.16 = 11.11 percent. The same calculation gives 6.76 percent for the mononitrate and 14.14 percent for the trinitrate. Solving the relation for k shows that the 11 to 12 percent nitrogen of pyroxylin plastic corresponds to about 2.0 to 2.3 nitrate groups per unit.[1]

Properties of cellulose nitrate compared with related materials[13][15]
Material Gross heat of combustion (MJ/kg) Note
Cellulose nitrate 9.11–13.48 decomposes; glass transition 53 °C
Celluloid (cellulose nitrate and camphor) 17.5–20.6 net value 16.4–19.2 MJ/kg
Cellulose acetate fibre 17.8–18.4 basis of safety film
Red oak 20.2 net value 18.7 MJ/kg

The heat of combustion of cellulose nitrate, 9.11 to 13.48 MJ/kg, is only about half to two-thirds of that of wood.[13] Its hazard thus comes from its self-sustaining decomposition and flash burning rather than from a large energy content.[3][1] The International Fire Engineering Guidelines give a rounded calorific value of 19 MJ/kg for celluloid.[16]

Decomposition and burning behaviour

When cellulose nitrate products are heated above about 150 °C (300 °F), decomposition starts. The decomposition generates further heat and soon raises the material to its ignition temperature.[1] This decomposition does not depend on an external supply of air.[1] The handbook describes the resulting hazard as flash burning, the reason why nitrate film was replaced.[3]

Loop diagram: heating above 150 °C starts decomposition, which releases heat and gases and heats the film further, without air from outside.
Above about 150 °C (300 °F), cellulose nitrate decomposes in a reaction that generates its own heat and needs no external air, so the material soon reaches its ignition temperature.

The fire triangle explains why ordinary measures fail. A fire needs fuel, oxygen and a high enough temperature, and lowering the oxygen concentration normally stops it from spreading.[17] Cellulose nitrate supplies part of the oxygen side itself, so carbon dioxide cannot suppress it. Wysocki lists materials such as cellulose nitrate, which contain available oxygen, among the few exceptions to the effectiveness of carbon dioxide.[18][4]

Heat history matters for self-heating. Cellulose nitrate that has been heated, for example material salvaged from a fire, may be so altered in composition that it becomes subject to spontaneous ignition.[1] For scrap nitrate film in drums and lined boxes, the handbook table of materials subject to spontaneous heating gives only a very slight tendency. The film must be properly stabilised against decomposition. Nitrocellulose film ignites at a low temperature, so external ignition, for example by sparks, is more likely than spontaneous heating.[19]

Solutions behave differently. Cellulose nitrate dissolved in acetone or another solvent has no greater hazard than the solvent itself. If the solvent evaporates, the hazard reverts to that of cellulose nitrate.[1] The table of polymer properties lists a glass transition temperature of 53 °C for cellulose nitrate and no melting point, only decomposition.[15]

Toxic combustion products

Burning cellulose nitrate film produces toxic oxides of nitrogen, alongside carbon monoxide.[2] In general, oxides of nitrogen can form from nitrogen-containing materials when enough oxygen is present.[20] The mixture, usually written NOx, consists mainly of nitrogen dioxide (NO2) and nitric oxide (NO), and nitric oxide is only about one-fifth as potent as NO2.[21] These gases set the fire toxicity of nitrate film apart from that of most commercial plastics, where carbon monoxide from incomplete combustion dominates.[22]

Nitrogen dioxide acts mainly as a pulmonary irritant, a gas that damages the lungs. In rat studies under smoke toxicity test conditions, its lethal potency was comparable to that of hydrogen cyanide, and deaths usually occurred after exposure, within one day. The consensus incapacitating concentration in ISO 13571 is 250 µL/L.[21] The 30-minute LC50 for rats, the concentration that kills half of the animals, is 170 µL/L for NO2. This compares with 5,700 µL/L for carbon monoxide and 3,800 µL/L for hydrogen chloride.[23] By this measure NO2 is about 34 times as lethal as carbon monoxide.

Log-scale bars of 30-minute LC50 for rats: HCN 165, NO2 170, HCl 3,800 and CO 5,700 µL/L; shorter bars mean more toxic.
30-minute LC50 values for rats; a lower value means a more toxic gas. Nitrogen dioxide from burning nitrate film is about as lethal as hydrogen cyanide.

The SFPE Handbook gives a 30-minute LC50 range of 60 to 250 ppm for mammals and a level of severe sensory irritation in humans of about 80 ppm.[24] Purser places nitrogen dioxide, with hydrogen cyanide, among the fire gases that are highly toxic at concentrations of 0.1 to 1 g/m³. Carbon monoxide and common acid gases lie in the 1 to 10 g/m³ range.[25] For irritants up to and including NO2 in his table, death is likely to result from lung irritation rather than asphyxiation.[24]

Two practical consequences follow in the handbook. Water from sprinklers tends to absorb the poisonous oxides of nitrogen, but it has no effect on carbon monoxide.[2] Firefighters should stay upwind or wear self-contained breathing apparatus.[2]

Storage, handling and transport

In the United States, the 2008 edition of the Fire Protection Handbook describes four elements of fire safety in plants processing cellulose nitrate plastic. These are segregation of hazards, elimination of ignition sources, good housekeeping and strong fire control facilities.[1] Where finished cellulose nitrate parts are only assembled with other articles, the hazard and the necessary protection depend on the quantity used. Large quantities call for the same safeguards as a plant making the product entirely from cellulose nitrate.[2]

For US practice as described in the 2008 handbook, cellulose nitrate storage needed special facilities. Depending on the quantity, these could be cabinets, vaults, storage rooms or isolated storage buildings, as described in NFPA 40 and NFPA 42.[2] Small amounts of portrait, industrial and amateur nitrate film kept in paper envelopes pose no serious hazard. The concern is the larger collections of old motion picture and aerial film.[2]

Four storage types in a row with an arrow for increasing quantity: cabinet, vault, storage room and isolated storage building.
The 2008 handbook lists US storage facilities for cellulose nitrate film and plastics from cabinets to isolated buildings, depending on the quantity stored (NFPA 40 and NFPA 42).

Projection of nitrate film is a separate risk. Although it is unlikely to be projected in a cinema showing present-day films, it may be shown in small art or film society theatres. Projectionists may not know that a print is nitrate, so the handbook recommends keeping theatre projection standards for nitrate film in effect.[2]

In the United States, NEC Article 540, as described by Milatovich (2008), governs projection rooms. If cellulose nitrate film is used, motor-generator sets, transformers and similar equipment must be in a separate room, and the film must be guarded so that arcs or sparks cannot reach it.[26] Rooms approved for safety film only carry a sign reading "Safety Film Only Permitted in This Room". Miller and Roether (2008) state that projection rooms designed for safety film cannot safely project nitrate film.[26][27]

Transport is regulated. As described in the 2008 handbook, the United States Department of Transportation (DOT) regulated interstate transport of cellulose nitrate plastic. It permitted dry shipment of specially packaged scrap, but required packaging under water if there was any sign or possibility of decomposition.[2] The handbook also describes prescribed packaging for motion picture and X-ray films, with inside containers of light metal, cardboard or fibreboard for individual reels. It states that NFPA 40 restricted their transport in public vehicles.[2]

Under International Air Transport Association rules described in the 2008 handbook, air transport of cellulose nitrate scrap was not permitted.[2] The 2008 handbook gives nitrocellulose as an example of a Division 4.1 flammable solid in its international hazard-class table.[28] The same handbook states that shipments of other plastics were not subject to special DOT requirements.[29]

By 2008, scrap disposal had become harder: amounts of scrap nitrate film had fallen and most agencies that once handled it no longer existed, so scrap could accumulate in dangerous quantities. The former best practice was to burn it in the open at a remote location, with all personnel upwind. Because of later concern about air pollution from open burning, the handbook advises checking with environmental authorities whether such burning is permitted locally.[2]

Fire protection and extinguishment

Cellulose nitrate is the one plastic that the handbook does not class as an ordinary combustible. All other plastics are fought like wood and other ordinary combustibles in Class A fires.[22] Large volumes of water are required to extinguish cellulose nitrate fires.[2] Automatic sprinkler systems are the best general protection for areas where it is stored or handled. Water supplies should be particularly strong, and sprinklers must be spaced more closely than in ordinary occupancies to supply enough water to absorb the heat.[2] If hose streams are needed, the aim is to get large quantities of water onto the fire as soon as possible.[2]

The International Fire Engineering Guidelines reflect the special status of nitrocellulose in their fire load table, based on Swiss surveys from 1967 to 1969.[30] For nitrocellulose manufacture, the fabrication fire load is marked as "special", and storage carries 1,100 MJ/m² per metre of storage height. Celluloid manufacture has 800 MJ/m² for fabrication and 3,400 MJ/m² per metre for storage.[31][32]

Archives, libraries and museums

The surviving nitrate film consists mainly of old motion picture and aerial film, with some X-ray film in hospitals.[2] Stored nitrate film is therefore also a topic of records protection and of library and museum fire protection, which deal with photographic media in general. Photographic records on any base hold their image in an emulsion. Tests showed that these emulsions do not withstand high temperature and humidity and are particularly susceptible to steam.[33] Insulated safes and files limit their internal temperature through water in the insulation, so a steam atmosphere of 100 °C (212 °F) or more can form inside them in a severe fire.[33]

Beals reports that photographic media sealed in a steel can with moisture-resistant tape, inside a records container, reach a high degree of safety. In salvage after a fire, photographic records should be given priority over paper.[33] For collections in general, McDaniel notes that relatively low levels of heat can destroy film and other heat-sensitive materials. Passive protection is therefore no substitute for timely detection and suppression.[34]

See also

Notes

  1. ↑ 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 1.10 1.11 Benedetti and Colonna (2008), p. 6-223.
  2. ↑ 2.00 2.01 2.02 2.03 2.04 2.05 2.06 2.07 2.08 2.09 2.10 2.11 2.12 2.13 2.14 2.15 2.16 2.17 2.18 2.19 2.20 2.21 2.22 2.23 Benedetti and Colonna (2008), p. 6-224.
  3. ↑ 3.0 3.1 3.2 3.3 Benedetti and Colonna (2008), p. 6-209.
  4. ↑ 4.0 4.1 Wysocki (2008), p. 17-6.
  5. ↑ 5.0 5.1 Benedetti and Colonna (2008), p. 6-213.
  6. ↑ Cholin (2008c), p. 6-61.
  7. ↑ Cholin (2008c), p. 6-65.
  8. ↑ Benedetti and Colonna (2008), p. 6-210.
  9. ↑ Benedetti and Colonna (2008), p. 6-212.
  10. ↑ Benedetti and Colonna (2008), pp. 6-214–6-215.
  11. ↑ Van Rossum (2027), §4.1.
  12. ↑ Drysdale (2008), p. 2-17.
  13. ↑ 13.0 13.1 13.2 Babrauskas (2008a), p. 6-280.
  14. ↑ Drysdale (2008), pp. 2-15–2-16.
  15. ↑ 15.0 15.1 Babrauskas (2008a), p. 6-273.
  16. ↑ National Research Council of Canada et al. (2005), p. 3.3-6.
  17. ↑ Van Rossum (2027), §4.2.
  18. ↑ Wysocki (2008), p. 17-3.
  19. ↑ Babrauskas (2008a), p. 6-291.
  20. ↑ Gann and Bryner (2008), p. 6-13.
  21. ↑ 21.0 21.1 Gann and Bryner (2008), p. 6-16.
  22. ↑ 22.0 22.1 Benedetti and Colonna (2008), p. 6-230.
  23. ↑ Gann and Bryner (2008), p. 6-18.
  24. ↑ 24.0 24.1 Purser (2002), p. 2-92.
  25. ↑ Purser (2002), p. 2-93.
  26. ↑ 26.0 26.1 Milatovich (2008), p. 8-160.
  27. ↑ Miller and Roether (2008), p. 20-92.
  28. ↑ C. J. Wright (2008a), p. 13-119.
  29. ↑ Benedetti and Colonna (2008), p. 6-229.
  30. ↑ National Research Council of Canada et al. (2005), p. 3.4-2.
  31. ↑ National Research Council of Canada et al. (2005), p. 3.4-3.
  32. ↑ National Research Council of Canada et al. (2005), p. 3.4-6.
  33. ↑ 33.0 33.1 33.2 Beals (2008), p. 9-108.
  34. ↑ McDaniel (2008), p. 20-192.

References

  • Babrauskas, V. (2008a). Tables and charts. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-269–6-294). National Fire Protection Association.
  • Beals, J. A. (2008). Protection of records. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-105–9-117). National Fire Protection Association.
  • Benedetti, R. P., & Colonna, G. R. (2008). Polymeric materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-209–6-231). National Fire Protection Association.
  • Cholin, J. M. (2008c). Wood and wood-based products. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-61–6-74). National Fire Protection Association.
  • Drysdale, D. (2008). Physics and chemistry of fire. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-3–2-20). National Fire Protection Association.
  • Gann, R. G., & Bryner, N. P. (2008). Combustion products and their effects on life safety. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-11–6-34). National Fire Protection Association.
  • McDaniel, D. L. (2008). Library and museum collections. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-179–20-202). National Fire Protection Association.
  • Milatovich, R. M. (2008). Electrical systems and appliances. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-127–8-173). National Fire Protection Association.
  • Miller, G., & Roether, E. (2008). Assembly occupancies. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-85–20-95). National Fire Protection Association.
  • National Research Council of Canada, International Code Council, Department of Building and Housing, & Australian Building Codes Board. (2005). International fire engineering guidelines (2005 ed.). Australian Building Codes Board.
  • Purser, D. A. (2002). Toxicity assessment of combustion products. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-83–2-171). National Fire Protection Association; Society of Fire Protection Engineers.
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.
  • Wright, C. J. (2008a). Managing the response to hazardous material incidents. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 13-117–13-144). National Fire Protection Association.
  • Wysocki, T. J. (2008). Carbon dioxide and application systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-3–17-15). National Fire Protection Association.