A battery energy storage system (BESS) is a stationary installation that stores energy in rechargeable cells and supplies electricity when it is needed. The installation comprises the batteries and the equipment that charges them, connects them to the load and controls their operation. One application is standby power for a building. A battery can keep communications or computer equipment running during the interval between the loss and restoration of the normal electricity supply.[1]

Battery chemistry changes the fire safety question. Charging a bank of vented lead-acid cells can release hydrogen into the battery room. A damaged lithium-ion cell can heat itself, release gases and transfer enough heat to its neighbours for them to fail in turn. A fire assessment therefore considers what happens inside a cell, how the batteries are arranged, and where heat and gas can travel in the enclosing space.[2][3][4]

From battery to electrical load

A static uninterruptible power supply (UPS) illustrates how stored energy reaches a load. In one arrangement, a rectifier converts the incoming alternating current (AC) to direct current (DC). A battery connects to the DC circuit, and an inverter converts DC back to AC for the equipment being supplied. If the incoming supply fails, the battery continues to feed the inverter. When supply returns, the rectifier supplies the load and recharges the battery.[1]

A rectifier feeds a DC bus and an inverter supplies the AC load. A battery on the bus can charge or discharge.
The battery feeds the direct-current bus when the normal supply fails. The inverter continues to supply the load. Based on Chisholm (2008), p. 10-5.

Power describes how quickly energy is delivered. Drawing 1 kW for 1 h delivers 1 kWh of electrical energy. The heat release rate of a fire describes how quickly combustion releases energy as heat. It depends on the chemistry, the materials taking part and how the fire develops.[5]

What a battery capacity rating means

A capacity in ampere-hours describes electric charge. At a constant discharge current, charge delivered equals current multiplied by elapsed time. The rating applies under stated discharge conditions, including the voltage at which discharge ends. For a lead-acid battery, increasing the discharge current can reduce the charge available before that voltage is reached.[6]

C=It

Symbol Quantity Unit
C Charge delivered over the interval Ah
I Constant discharge current A
t Discharge time h

The Fire Protection Handbook gives the example of a small standby battery supplying 0.5 A for 20 h. It delivers 10 Ah over that interval. A load drawing more current can bring the battery to its limiting voltage earlier. Voltage also matters when converting a charge rating into an energy rating.[6]

Lithium-ion failure and gas accumulation

During thermal runaway, reactions inside a cell generate heat faster than the cell can lose it. Heat can pass to a neighbouring cell and start a second runaway. A battery management system monitors the cells and can interrupt charging when it detects abnormal conditions. Disconnecting the external circuit leaves chemical energy inside the cells, so heat and gas production can continue after electrical isolation.[3]

A failing cell branches towards a neighbouring cell heated by it and an enclosure into which released gases can collect.
Heat can propagate between cells while released gas accumulates in an enclosure. Based on Van der Graaf et al. (2023), pp. 22–23 and 26–27.

A lithium-ion battery fire can involve both the cell and gases released from it. A study by the Netherlands Institute for Public Safety describes how gases from vehicle battery packs can accumulate in an enclosed space before they ignite. In a stationary enclosure, the corresponding question is whether a flammable mixture can form and where its combustion products can expand. Ignition can produce a deflagration, a flame that travels through the mixture, with a pressure rise in a confined space. Carbon monoxide and hydrogen fluoride can also contribute to the toxicity of the atmosphere.[7][4]

Gas detection, cooling and pressure relief address different stages of that sequence. Cooling can limit heat transfer to adjacent cells. Explosion venting provides an engineered route for expanding gases if a deflagration occurs. The enclosure, vent discharge path and consequences for nearby people are installation-level questions. Measurements from a vehicle pack describe that pack. An assessment of a stationary installation also needs evidence for its enclosure and arrangement.[3][7][4]

Hydrogen in a lead-acid battery room

Vented lead-acid cells have another route to a flammable atmosphere. As a cell approaches full charge, some charging current breaks down water in the electrolyte into hydrogen and oxygen. This can occur during charging without a fire. Ventilation of the battery room dilutes the hydrogen, while provision for liquid electrolyte addresses a separate hazard from a leaking cell.[1][2]

Vented lead-acid cells release hydrogen above a battery bank. Arrows show an illustrative inlet and extraction path.
Hydrogen produced during charging can enter room air. Ventilation performance depends partly on how well the air mixes. Based on Iqbal and Salley (2004), pp. 16-1–16-2 and 16-8–16-10.

In their study of backup batteries at US nuclear power plants, Iqbal and Salley considered the charging conditions, how much gas the cells release and how effectively the room air mixes. Two rooms with the same nominal airflow can have different local concentrations if air enters and leaves by different routes. The calculation concerns hydrogen from the lead-acid banks described in that study. A lithium-ion failure can release a mixture of gases by a different mechanism.[2][7]

Assessing safeguards together

The fire safety assessment for an indoor installation can trace what happens after a battery alarm. For example, if one detector both alerts staff and starts a protective function, loss of that detector can affect both actions. Australia's Fire Safety Verification Method handbook uses a building example to show how shared detection can affect several safeguards at once. It also considers the alarm information and access available to the fire service when part of the system fails.[8]

Where a site also has photovoltaic generation, its pre-incident plan can identify each electricity source and the equipment each source feeds. The handbook account of emergency power describes identification of multiple electrical sources. Distinguishing the battery circuit from the normal supply helps explain why a load can remain live during a mains failure.[1][8]

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 Chisholm (2008), chap. 10.1, pp. 10-4–10-5.
  2. ↑ 2.0 2.1 2.2 Iqbal and Salley (2004), chap. 16, pp. 16-1–16-2 and 16-8–16-10.
  3. ↑ 3.0 3.1 3.2 Van der Graaf et al. (2023), §§1.2.1 and 1.3.1, pp. 21–23.
  4. ↑ 4.0 4.1 4.2 Zalosh (2002), chap. 3.16, pp. 3-402 and 3-414.
  5. ↑ Van Rossum (2027), §§4.4–4.5. Van der Graaf et al. (2023), §§1.3.1–1.3.3, pp. 22–25.
  6. ↑ 6.0 6.1 Cholin (2008), chap. 14.5, pp. 14-64–14-65.
  7. ↑ 7.0 7.1 7.2 Van der Graaf et al. (2023), §1.3.5, pp. 26–27.
  8. ↑ 8.0 8.1 Australian Building Codes Board (2020), pp. 29 and 99–101.

References

  • Australian Building Codes Board. (2020). Fire safety verification method: Handbook (Version 1.1).
  • Chisholm, D., Sr. (2008). Emergency and standby power supplies. In A. E. Cote (Ed.), Fire protection handbook (20th ed., chap. 10.1). National Fire Protection Association.
  • Cholin, J. M. (2008). Inspection, testing, and maintenance of fire alarm systems. In A. E. Cote (Ed.), Fire protection handbook (20th ed., chap. 14.5). National Fire Protection Association.
  • Iqbal, N., & Salley, M. H. (2004). Fire dynamics tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission fire protection inspection program (NUREG-1805). U.S. Nuclear Regulatory Commission.
  • Van der Graaf, J., Hessels, T., & Rosmuller, N. (2023). Fire safety of indoor car parks accommodating electrically powered vehicles (English translation of the 2021 report). Netherlands Institute for Public Safety.
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.
  • Zalosh, R. (2002). Explosion protection. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed., chap. 3.16). National Fire Protection Association and Society of Fire Protection Engineers.