Outdoor storage of forest products is the storage in open yards of logs, pulpwood, wood chips, bark, sawdust, lumber and wood panels, together with the fire protection measures that such yards need.[1][2] Large quantities of logs are kept at sawmills, paper mills and pulp mills, because wood is moved out of the forests only at certain times of the year.[3] Once ignited, these stores offer a very large fuel load, and without proper precautions a fire can quickly become impossible to extinguish.[1] Automatic sprinklers are usually not an option outdoors, so pile size, clear spaces, access roads and water supply for manual fire fighting set the level of protection.[4] Chip and bark piles add a second hazard: internal fires caused by self-heating, which can burn deep inside a pile before they are detected.[3][5] Most of the guidance summarised here comes from the US Fire Protection Handbook (2008) and the NFPA documents it cites, and describes American practice around 2007–2008.

Materials and scope

The stored material can consist of logs, chips, "stuck" lumber stacked with spacers for drying, dense-packed lumber or panels such as wood-based panels.[1] Bark from pulp mills and sawmills, sawdust, shavings and other wood waste are also piled outdoors, often for use as boiler fuel.[2] Outdoor storage areas count as a type of storage occupancy in the handbook, alongside warehouses, freight terminals and grain elevators.[6] Cholin (2008d) treats raw-material storage as one of the fire protection challenges of a woodworking facility.[1]

According to Cholin (2008d), the US criteria for bulk wood storage are found in NFPA 1, Uniform Fire Code. As described in the 2008 handbook, that code covers indoor storage of lumber at retail and wholesale locations and outdoor storage of timbers, logs and chips. It names five principal factors that allow fires to escalate to large losses: large undivided piles, congested storage, delayed fire detection, inadequate fire protection and ineffective fire-fighting tactics.[1] NFPA 1 also gives specific recommendations on pile size, separation between piles and water supply for each type of storage.[7]

The hazard of wood rises as it is processed, for two reasons. Its moisture content falls as it dries, and its particle size falls from the standing tree through lumber and chips to dust.[2] Solid wood is not readily ignited but can release a large amount of heat if it burns unimpeded. The rate of fire spread depends on the pile configuration, the moisture of the wood and the air, the size of the pieces, the presence of bark and the species. Pile size and configuration determine how much radiant heat a fire releases.[2]

Ignition and fire spread in wood piles

Outdoor yards are exposed to many ignition sources from outside the storage itself. J. Moore (2008) names grass, brush and forest fires, and sparks from rolling railroad equipment, incinerator stacks and electrical transformers on poles. Cigarettes discarded from passing cars are another source.[4] Refuse burners, boiler stacks, vehicle exhausts and locomotives also need safeguards against sparks.[8] Within the yard, torch cutting, welding and smoking must be controlled.[8]

The way the wood is stacked strongly affects how it burns. Lumber stacked in solid, orderly piles about 6 m (20 ft) high is a smaller problem than lumber in "stickered" piles, where spacers leave air gaps between the layers. Fire develops more rapidly in stickered piles because of these air spaces.[4] Pulpwood is sometimes stored in piles 61 m (200 ft) in diameter and 30 m (100 ft) high. The rough shapes of the logs create air pockets that accelerate burning.[4]

Lumber, plywood, pulpwood and pallets are among the materials that J. Moore (2008) lists as burning quickly and producing a great deal of heat.[4][8] A pile that is stable in normal conditions may collapse in a fire or under hose streams, which can spread the fire and hamper fire fighting.[8]

Fire spreads from a burning pile by radiation and by burning embers.[9] The handbook gives 12.5 kW/m² as a value that has been used for the minimum radiant heat flux to ignite wood. Babrauskas suggests 20 kW/m² for short exposures and 4.3 kW/m² for long exposures.[10] The radiation that reaches a target depends on the view factor between the flames and the target. That factor in turn depends on the area of the radiating surface, its distance and its orientation, and the same method is used to assess fire spread between buildings.[11] Janssens (2008) notes that outside storage with a nearly square plan acts as a cylindrical or conical radiant source.[9]

Firebrands are lifted by the upward flow in the fire plume and then carried by the wind. The largest come from the highest parts of a burning storage array that are still within the plume.[12] Their range depends on their shape, burning mode and density, on the heat release rate of the fire and on the wind speed.[12] High winds make the exposure problem almost impossible to control: they can carry burning material and brands over considerable distances, even when the fire itself is confined to a small area.[4]

Self-heating in chip and bark piles

Chip storage has replaced log storage at many pulp and paper mills. Two quite different types of fire occur in chip piles: surface fires and internal fires.[3] Because chips are small, about 16 to 32 mm (⅝ to 1¼ inches), fires in chip piles tend to stay at the surface. They penetrate no more than about 50 mm into the pile.[2] Long periods of hot, dry weather without regular surface wetting create conditions for fast-spreading surface fires.[3]

Internal fires start from spontaneous heating. Dungan (2008b) attributes them mainly to fines that cause too much compaction, or to humus material in the pile, which oxidises faster than clean chips.[2] J. Moore (2008) adds that piles built in ways that concentrate fines, and piles stored for long periods without turnover, are subject to internal heating. If it goes undetected, such heating can cause intense internal fires.[3]

Foreign material in chip or bark piles also appears to accelerate the build-up of heat. It may act through chemical reaction or simply through greater porosity, which lets air move more freely through the pile.[13] In some softwoods, resins undergo an exothermic condensation reaction that has been suspected as the cause of spontaneous ignition in piled chips of southern pine.[14]

Clean, dry wood is a different case. Cholin (2008c) finds little evidence that clean and dry wood products self-heat and ignite when stored at normal temperatures; in the cases studied by Babrauskas the material was always above 50 °C (122 °F).[10] The SFPE Handbook explains why large piles are the problem. Gray (2002) describes a critical size above which heat generation outruns heat loss, and notes that solar irradiation must be considered in outdoor storage.[15] Rockett and Milke (2002) observe that coal, wood chips and similar materials are occasionally stored in piles large enough for self-heating to matter.[16]

Gray (2002) also warns that spontaneous ignition leaves a burnt-out core inside an intact exterior. Large woodchip piles can therefore be dangerous for fire fighters, and the deep-seated burning can reignite days after it seemed to be out.[17] Stacks of freshly made chipboard of a few cubic metres can ignite within hours, much faster than material that heats from ambient temperature.[18]

Bark piles at pulp mills have sometimes grown into "miniature mountains". Their height and bulk create a hazard from internal heating leading to spontaneous ignition, and from sparks from the heavy equipment used to build them.[5] Dungan (2008b) describes a method of controlling such fires by limiting the horizontal flow of air into the pile. In this method the pile is sloped at 30 to 40 degrees from the horizontal.[5]

At a depth A below the top, pressure and moisture let the chemical reaction generate heat and volatile material, which supply two sides of the fire triangle. Oxygen can reach that zone only from a nearly horizontal direction, because hot gases rise through the pile. The distance B that air must travel through the pile is therefore what limits combustion.[5] For a pile face at angle θ, the horizontal distance from the face to a point at depth A follows from simple geometry:

B=Atan⁡θ

Symbol Description Unit
B Horizontal distance that air must travel from the pile face to the heating zone m
A Depth below the top of the pile at which heating can develop m
θ Slope of the pile face from the horizontal degrees

For a heating zone at a depth of 3 m, a slope of 30 degrees gives B=3/tan⁡30∘≈5.2 m, while a slope of 60 degrees gives B=3/tan⁡60∘≈1.7 m. The ratio of the two is exactly 3.0, which matches the handbook statement that the air path is about three times longer with a slope of 30 degrees than with one of 60 degrees.[5] The depth of 3 m is an illustrative value; the handbook gives no value for A. Where flatter slopes are not practical, sealing the slope against air penetration is an alternative.[5] In northern climates, a blanket of ice and snow can trap the heat that normally escapes from the surface, so limiting the pile height and the air flow through the sides becomes doubly important.[13]

Cross-section of a bark pile with a critical temperature line at depth A and horizontal air paths B for 30 and 60 degree slopes
Air path to the heating zone of a bark pile for slopes of 30 and 60 degrees.

Yard layout and separation

Logs are stored in two main arrangements. Large circular piles with logs dumped on top are called "stacked piles", and logs laid parallel, like matches in a box, form "ranked piles".[3] Stacked piles often approach 30.5 m (100 ft) in height, while ranked piles are usually 3 to 5 m (10 to 15 ft) high. Separation and aisles are much easier to keep with ranked piles, so their fire protection is also much easier.[3] Dungan (2008b) adds that ranked piles have less volume and less radiant heat exposure than stacked piles. For log storage at fuel-using plants, he recommends a distance of at least 30 m (100 ft) from the nearest important building.[5]

Side views of a tall circular stacked log pile with logs dumped on top and a low ranked pile of parallel logs
Stacked and ranked log piles.

The handbook shows a good layout for ranked log piles. Each pile is separated from the next by a fire lane at least 1½ times the pile height H, and not less than 6.1 m (20 ft). Groups of piles are surrounded by a clear space and fire lane of 30.5 m (100 ft), with hydrants spaced 76.2 m (250 ft) apart.[3] For a ranked pile of height H in metres, the lane width w in metres can be written as:

Plan view of ranked log piles separated by fire lanes of one and a half times pile height, with a 30.5 m clear space and hydrants every 76.2 m
Plan layout for ranked log piles in a storage yard.

w=max⁡(1.5H, 6.1 m)

For a pile 4.6 m (15 ft) high, the rule gives 1.5 × 4.6 ≈ 6.9 m. For a pile 3 m (10 ft) high, 1.5 × 3 = 4.5 m, so the minimum of 6.1 m governs. The two terms are equal at a pile height of about 4.1 m. Along a yard edge 300 m long, hydrants at 76.2 m spacing mean at least five hydrants, counting one at each end. These numbers illustrate the layout in the handbook; the governing values for a real yard are those of the applicable code.[3]

Line chart of fire lane width against ranked pile height: flat at 6.1 m up to 4.1 m height, then rising as 1.5 times the height
Fire lane width between ranked log piles as a function of pile height.

General rules for outdoor storage yards follow the same logic. Congestion is a major factor in fire spread, so the yard must be large enough for the stock plus the spacing between piles.[4] For fast-burning materials such as lumber and pulpwood, aisles as wide as the pile height are desirable. J. Moore (2008) recommends driveways at least 4.5 m (15 ft) wide, so that fire apparatus can reach all parts of the yard. Aisles of 3 m (10 ft) or more reduce spread from pile to pile.[8] In very large yards, main aisles or firebreaks subdivide the storage much as firewalls do indoors.[8] Mattern (2008b) stresses that these passageways must never be blocked, even temporarily, by contractors' huts, crates or pallets.[19]

Clearances also protect neighbouring property. Adequate clearances to adjacent properties should be kept to limit mutual exposure, and the future use of adjacent land should be considered where no zoning rule sets a distance.[4] Piles should be detached from buildings and placed far enough apart to let fire fighters control an exposing fire. They also need enough clearance from forest, brush or grass to stop an outside fire from reaching the storage.[13] Janssens (2008) treats a safe separation distance as passive exposure protection: it keeps the radiant heat flux and the firebrands reaching a target low enough during the exposing fire. In a prescriptive US regime, NFPA 80A can provide that distance; in a performance-based design it must be demonstrated.[9]

Water supply and fire fighting

Because truly engineered fire protection is difficult outdoors, the available manual fire fighting dictates the arrangement of the storage. Public water supply and its reliability, the available fire flow, the location and travel time of the fire department and the means of raising the alarm all need to be assessed.[4] Private water mains and hydrants may be needed throughout a yard. They should be installed during site preparation and be able to deliver the required fire flow.[8]

Log yard fires can require large quantities of water. Many portable turrets and monitor nozzles may have to operate at once, each discharging about 3,785 L/min (1,000 gpm).[3] As an illustration, four such monitors together would use about 15,100 L/min, or roughly 250 L/s. The handbook gives a looped underground fire main with hydrants spaced throughout the yard as good practice. Monitor nozzles on towers are useful in log yards, especially those with high stacked piles.[3]

Aerial or elevated view of a pulp mill log yard with ranked log piles and wide access roads
Log storage yard at a pulp or saw mill.

Burrowing fires in large stacked piles are difficult to extinguish even after the surface burning is under control.[3] Chip and bark piles also need large amounts of water, which is one reason to keep them small.[20] Where wood chips are used as fuel on a large scale, the plant is often in an isolated area far from municipal fire protection and water supplies. Dungan (2008b) states that such plants should keep outdoor chip piles smaller and lower than the sizes recommended in NFPA 1. If possible, they should be sited near a pond or stream.[5]

Ranked log piles at such plants should be protected by a yard hydrant system as defined in NFPA 1. Where the water supply or the fire brigade is inadequate, smaller and more segregated piles with greater clear space are needed.[20] J. Moore (2008) recommends marked portable extinguishers, preferably of the non-freezing water type, so that none is more than 23 m (75 ft) away. Equipped hose houses with trained staff are recommended for active, occupied sites.[8] A private fire brigade can provide the first response. The larger and more valuable the yard, the greater the need for one; NFPA 600 sets minimum requirements for its organisation and training.[8]

Prevention and yard management

Cholin (2008d) reports that NFPA 1 calls for a positive fire prevention programme under the direct supervision of top management. As summarised in the handbook, it includes sound design of the storage yards and handling equipment and systems for early detection, alarm and extinguishment. It also calls for fire lanes between large piles, separation of yard storage from mill operations and other exposures, and regular yard inspections by trained personnel.[7]

For wood stored as fuel, the first line of defence is to limit pile size to the minimum needed for economical operation. Logs should be ranked rather than stacked, and two or more smaller piles are better than one large pile.[13] Keeping chip and bark piles free of contamination is an effective preventive measure.[13] The site should be clean and on solid ground with good access for fire fighting.[5] J. Moore (2008) adds that the ground should be levelled if possible, because sloping terrain makes piles unstable.[4]

J. Moore (2008) extends good housekeeping to the whole yard. Vegetation should be cleared, sprayed with a herbicide or ground sterilant, or removed when dead, so that it cannot dry out and carry fire.[4][8] Scrap lumber, broken pallets and other debris dumped in the clear spaces should be checked for daily and removed, and windblown debris should not be allowed to collect around the piles.[3] Smoking should be prohibited or limited to remote areas, and hot work should be done only with suitable precautions under NFPA 51B.[8] Fuel for lift trucks should be stored to NFPA 30, with tanks placed so that spills cannot flow under the storage. Tarpaulins used to cover stock should be of fire-retardant-treated material.[8]

Limits of the guidance

The values in this article are those of the 2008 US handbook and of the NFPA documents it summarises, such as NFPA 1, NFPA 30, NFPA 51B, NFPA 80A and NFPA 600. The handbook does not state which editions of these documents it describes.[1][9] The layout of ranked log piles is presented as an example of good practice, not as a universal rule, and later editions of the codes or other national rules may differ.[3] Ideal aisle width depends on the material, how it is stored, its height, the expected wind, and the fire-fighting capability and equipment available.[8]

The handbook gives no quantitative method for the heat release rate or radiation of a burning log or chip pile. The radiant ignition thresholds for wood vary with species, moisture, grain orientation and exposure time.[10] Self-heating theory explains why size and storage time matter, but it needs measured data for the particular material. The geometric bark-pile relation describes only the air path; it does not predict whether a given pile will heat.[5]

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 1.4 1.5 Cholin (2008d), p. 9-5.
  2. ↑ 2.0 2.1 2.2 2.3 2.4 2.5 Dungan (2008b), p. 7-8.
  3. ↑ 3.00 3.01 3.02 3.03 3.04 3.05 3.06 3.07 3.08 3.09 3.10 3.11 3.12 3.13 J. Moore (2008), p. 20-177.
  4. ↑ 4.00 4.01 4.02 4.03 4.04 4.05 4.06 4.07 4.08 4.09 4.10 J. Moore (2008), p. 20-175.
  5. ↑ 5.00 5.01 5.02 5.03 5.04 5.05 5.06 5.07 5.08 5.09 Dungan (2008b), p. 7-9.
  6. ↑ J. Moore (2008), p. 20-158.
  7. ↑ 7.0 7.1 Cholin (2008d), p. 9-6.
  8. ↑ 8.00 8.01 8.02 8.03 8.04 8.05 8.06 8.07 8.08 8.09 8.10 8.11 8.12 J. Moore (2008), p. 20-176.
  9. ↑ 9.0 9.1 9.2 9.3 Janssens (2008), p. 2-71.
  10. ↑ 10.0 10.1 10.2 Cholin (2008c), p. 6-69.
  11. ↑ Van Rossum (2027), §5.4.
  12. ↑ 12.0 12.1 Janssens (2008), p. 2-72.
  13. ↑ 13.0 13.1 13.2 13.3 13.4 Dungan (2008b), p. 7-10.
  14. ↑ Cholin (2008c), p. 6-63.
  15. ↑ Gray (2002), p. 2-211.
  16. ↑ Rockett and Milke (2002), p. 1-36.
  17. ↑ Gray (2002), p. 2-212.
  18. ↑ Gray (2002), p. 2-224.
  19. ↑ Mattern (2008b), p. 11-36.
  20. ↑ 20.0 20.1 Dungan (2008b), p. 7-11.

References

  • Cholin, J. M. (2008c). Wood and wood-based products. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-61–6-74). National Fire Protection Association.
  • Cholin, J. M. (2008d). Woodworking facilities and processes. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-3–9-25). National Fire Protection Association.
  • Dungan, K. W. (2008b). Storage and handling of solid fuels. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-3–7-13). National Fire Protection Association.
  • Gray, B. (2002). Spontaneous combustion and self-heating. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-211–2-228). National Fire Protection Association; Society of Fire Protection Engineers.
  • Janssens, M. L. (2008). Basics of fire containment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-59–2-74). National Fire Protection Association.
  • Mattern, L. J. (2008b). Housekeeping practices. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-27–11-38). National Fire Protection Association.
  • Moore, J. (2008). Storage occupancies. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-157–20-178). National Fire Protection Association.
  • Rockett, J. A., & Milke, J. A. (2002). Conduction of heat in solids. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 1-27–1-43). National Fire Protection Association; Society of Fire Protection Engineers.
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.