Clearance to combustibles is the minimum distance, normally an open air space, that must be kept between a heat-producing appliance, its connector, a chimney or a hot duct and any combustible material nearby.[1][2][3] Its purpose is to keep exposed combustibles below dangerous temperatures even when the appliance runs at maximum heat for long periods.[1] Wood can ignite far below its usual ignition temperature of about 200 °C when it is heated moderately for a long time, so the permitted surface temperatures are low.[4] In the United States, testing laboratories set the clearances of listed appliances so that exposed combustible surfaces rise no more than 65 °C above room temperature.[1] Standard tables, many taken from NFPA 211, apply unless a listing specifies otherwise, and approved shields with a ventilated air space can reduce these distances by up to two thirds.[4][5] In New Zealand, Building Code clause C2.2 limits the surface temperature of combustible building materials near fixed appliances to 90 °C.[6]
Definition and purpose
Any source of heat is a potential fire hazard unless it is arranged so that dangerous temperatures cannot develop on adjacent combustible materials.[1] Heat-producing appliances are therefore installed with a clearance between the appliance and combustibles. Under conditions of maximum heat, meaning long and continued exposure, the temperature of the exposed combustibles then stays within safe limits.[1] The minimum clearances for the various types of appliance have been determined by testing laboratories and through field experience.[1]
For a listed appliance, the clearances found in tests are published in the listing and shown on the appliance or in the installation manual.[1] Examples of laboratories that test and list appliances are FM Global Research, Underwriters Laboratories (UL), Underwriters Laboratories of Canada, Intertek and CSA International.[1] The combustibles to be protected may be fixed, such as walls and structural members, or moveable, such as furniture, bedding and clothing.[7] For chimneys, the 2008 handbook stresses that every clearance must consist of an air space. Solid material, including building insulation, must not fill it, whether it is combustible or not.[3]
The handbook names adequate clearance as one of the basic principles for all miscellaneous heat-producing devices, together with venting of combustion products, adequate combustion air, burner controls and safe fuel handling.[8] In performance-based design, the International Fire Engineering Guidelines (2005) list heating appliances among the ignition sources and the location of combustible materials among the fuel factors to review. Separation of ignition sources and fuel is named as a preventive measure.[9]
Why wood ignites at low temperatures
The ignition temperature of a material is the lowest temperature at which it ignites.[10] For wood, Iqbal and Salley (2004) give a typical piloted ignition temperature of 350 °C and an auto-ignition temperature of 600 °C, and they note that the value varies with the rate of heating.[11] The ignition temperature of wood products is generally quoted as about 200 °C (392 °F). Wood that is heated constantly over a period of time, however, may change chemically, which lowers its ignition temperature and increases the potential for self-ignition.[4]
The handbook cites several studies of this effect. Mitchell reported ignition of wood fibreboard after prolonged exposure at temperatures as low as 109 °C (229 °F).[4] MacLean found charring of wood at 93 °C (200 °F) and concluded that wood should not be exposed for long periods to temperatures much above 66 °C (151 °F).[4] McGuire suggested 100 °C (212 °F) as the maximum safe surface temperature of a combustible next to a constant heat source. Documented fires in wood members near low-pressure steam pipes point to a similar upper limit for long-term, low-level heating.[4]
By comparison, the charring temperature of wood in a standard fire resistance test lies between 280 and 300 °C.[12] The length of exposure is thus an important parameter.[4] Wood is also a good insulator, with a thermal conductivity of about 0.17 W/(m·K) for oak, so a small amount of energy can raise its surface to ignition temperature.[13][14]
Part of the mechanism is self-heating. Self-heating occurs when a material reacts and releases heat that is largely retained inside it because the material or its container conducts heat poorly.[15] Clean, dry wood does not self-heat at room temperature.[14] An external heat source must first raise it to the point where pyrolysis begins, after which the pyrolysed wood can heat itself further if the heat cannot escape.[14] In the cases studied by Babrauskas, as cited by Cholin (2008c), the material was always above 50 °C.[14] Thermal insulation around a heated material reduces its heat losses further, which explains why insulation packed against a hot surface is dangerous.[16][17]
Temperature limits
Clearances are set by limiting the temperature that a combustible surface may reach. The UL test standards on which United States listings are based allow a maximum temperature rise of 65 °C (117 °F) above room temperature on exposed surfaces. They allow 50 °C (90 °F) on unexposed surfaces, such as the floor beneath an appliance or behind a floor or wall protector.[1] Gore Willse (2008a) adds that under any operating condition the temperature of exposed combustible materials should not exceed 82 °C (180 °F).[4] For boiler furnaces, the handbook gives 71 °C (160 °F) as the limit for combustible floors and roofs near the boiler and its metal chimney.[18]
New Zealand uses an absolute limit instead of a rise. Clause C2.2 of the New Zealand Building Code, as reproduced in the 2013 commentary, sets the limit at 90 °C. It applies to combustible building materials close to fixed appliances using controlled combustion, operating at their design level.[6] The commentary explains that a fixed value avoids disputes about the ambient temperature to assume.[19]
The commentary also notes that published limits for long exposure range from 66 to 110 °C. Babrauskas regards any heating device of 77 °C or more applied to wood for a protracted period as a documented ignition hazard.[19] The value of 90 °C is consistent with the maximum rise of 65 °C used in Appendix B of the Australian and New Zealand standard AS/NZS 2918 for domestic solid-fuel appliances.[19]
| Temperature | Meaning | Source |
|---|---|---|
| 50 °C | Lowest material temperature in documented self-heating of wood products | Cholin (2008c), p. 6-69 |
| 66 °C | Long-term exposure limit suggested by MacLean | Gore Willse (2008a), p. 10-31 |
| 65 °C rise | UL listing limit on exposed combustible surfaces (about 85 °C in a 20 °C room) | Gore Willse (2008a), p. 10-28 |
| 77 °C | Heating device temperature that Babrauskas treats as a documented ignition hazard | Ministry of Business, Innovation and Employment (2013), p. 15 |
| 82 °C | Maximum for exposed combustibles under any operating condition (United States) | Gore Willse (2008a), p. 10-31 |
| 90 °C | New Zealand Building Code clause C2.2 limit | Ministry of Business, Innovation and Employment (2013), p. 14 |
| 109 °C | Ignition of fibreboard after prolonged exposure (Mitchell) | Gore Willse (2008a), p. 10-31 |
| 200 °C | Commonly quoted ignition temperature of wood products | Gore Willse (2008a), p. 10-31 |
Heat transfer across the clearance
A clearance limits the heat that reaches a combustible surface in two ways: distance reduces the thermal radiation received, and the air space lets circulating air carry heat away.[4] Radiation becomes the dominant mode of heat transfer at high temperatures, from about 400 °C, while convection dominates at lower temperatures.[20] A surface at about 550 °C emits enough visible radiation to glow red.[20] The handbook treats an appliance or connector that glows even a very dull red as a severe and immediate hazard.[21]
The net radiant heat flux from a hot surface to a cooler one depends on the absolute temperatures of both surfaces and on the emissivity of the hot surface.[20] The part of that radiation that reaches a target is set by the view factor, which depends on the size of the hot surface, the distance and the orientation. Close to a large hot surface the view factor approaches one.[20]
| Symbol | Description | Unit |
|---|---|---|
| Net radiant heat flux received by the combustible surface | W/m² | |
| View factor from the combustible surface to the hot surface | – | |
| Emissivity of the hot surface | – | |
| Stefan–Boltzmann constant, 5.67 × 10−8 | W/(m²·K4) | |
| , | Absolute temperature of the hot and of the cooler surface | K |
The handbook states that a 51 mm (2 in.) clearance is of little protective value when the outer brick surface of a chimney reaches 260 °C (500 °F), particularly with little ventilation airflow.[17] The equation shows why. With Th = 533 K, Tc = 293 K, an emissivity of 0.9 for stone and a view factor of about 1 across the narrow gap, the net flux is about 3.8 kW/m².[20] This is close to the 4.3 kW/m² that Babrauskas, as cited by Cholin (2008c), suggests as the minimum flux for ignition of wood under long-term exposure.[14] For short exposures he suggests 20 kW/m², and Tewarson (1995), as cited in Iqbal and Salley (2004), lists a critical heat flux for ignition of 10 kW/m² for red oak and Douglas fir.[14][22] The critical heat flux is the value at or below which the ignition time is effectively infinite.[13]
The estimate ignores convection and the warming of the wood itself, so it shows only the order of magnitude. Emissivity also explains why shiny metal is reassuring. Polished aluminium has an emissivity of about 0.04, which gives only about 0.17 kW/m² at the same temperature.[20] In line with this, the handbook notes that shiny chimney surfaces are unlikely to radiate damaging amounts of heat if the chimney is installed at the correct clearance.[23]
Room size matters as well. In large rooms, a suitable clearance is all that is needed to prevent ignition, but in small or poorly ventilated rooms dangerous temperatures can build up whatever the clearance unless air circulation cools the space.[4][5] The standard tables define a large room as one with at least 12 times the volume of a furnace or 16 times that of a boiler. The ceiling height is counted at no more than 2.4 m (8 ft).[24]
Standard clearances
The 2008 handbook reproduces standard clearance tables for gas, oil and electric appliances and, from NFPA 211, for solid-fuel heating appliances.[1][4] A residential central warm-air furnace fired by oil, gas or electricity needs 152 mm (6 in.) above, at the back and at the sides. At the front it needs 457 to 610 mm (18 to 24 in.).[25] A listed furnace whose limit control cannot be set above 120 °C (250 °F) may have 51 mm (2 in.) instead of 152 mm. With a limit of 93 °C (200 °F), 25 mm (1 in.) is allowed.[24] Circulating oil or gas room heaters need 914 mm (36 in.) above, 610 mm (24 in.) in front and 305 mm (12 in.) at the back and sides.[25]
Solid-fuel appliances need more space. Room heaters, fireplace stoves and combinations need 914 mm (36 in.) in every direction, and solid-fuel furnaces 457 mm (18 in.) above, behind and at the sides and 1219 mm (48 in.) in front.[4] Fuel storage must be at least 914 mm (36 in.) from any side of the appliance.[4] Because the clearances of large heaters can exceed 914 mm, laboratory tests for listing may be performed with additional shielding of the walls.[21] Larger combination fireplace stoves may need more than the standard clearance, which reflects a geometric relationship between heater size and required clearance.[26]
Connectors and chimneys have their own clearances. A single-wall metal connector from a residential oil or solid-fuel appliance needs 457 mm (18 in.). The value falls to 229 mm (9 in.) for boilers and furnaces with listed gas burners and draft hoods. Listed gas appliances with draft hoods that are suitable for Type B vents need 152 mm (6 in.).[27] These values, covered further under gas appliance venting, apply unless the listing of the appliance specifies a different clearance.[27]
Residential and low-heat chimneys need an air space of 51 mm (2 in.) inside a building and 25 mm (1 in.) entirely outside it.[3] Factory-built residential chimneys are tested fully enclosed with a flue gas generator at 540 °C (1000 °F) to establish a clearance of no more than 51 mm.[28] Masonry fireplaces need 51 mm (2 in.) at the sides and 102 mm (4 in.) at the back. If the opening is smaller than 0.56 m² (6 ft²), the noncombustible hearth extension reaches at least 406 mm (16 in.) in front.[29]
Other building services follow the same idea. Hot-water pipes at up to 120 °C and steam pipes at up to 103 kPa need 25 mm (1 in.), while higher-pressure steam pipes need 152 mm (6 in.).[1] Commercial kitchen grease ducts need 457 mm (18 in.) to combustible materials and 76 mm (3 in.) to limited-combustible materials unless protected as NFPA 96 permits.[30] Engine exhaust systems need at least 229 mm (9 in.) from combustible materials.[31]
Reducing clearances with protection
Where an appliance cannot practically be moved, the clearance can be reduced by installing protection between the appliance and the combustible material.[5] A clearance reduction system is a barrier of metal, metal with insulating material, or masonry. Except for specific systems, an air space is left between the barrier and the hot surface and between the barrier and the combustible. The air currents set up in these spaces keep the combustible below a dangerous temperature even at the smaller clearance.[32] The ventilated systems need at least 25 mm (1 in.) between the barrier and the combustible wall, noncombustible spacers, and no spacers or ties directly behind the appliance or connector.[5]
NFPA 211, as summarised in the handbook, assigns each protection system a maximum allowable reduction. A 90 mm (3½ in.) masonry wall without a ventilated air space allows 33 %. Noncombustible insulation board over mineral wool batts without an air space allows 50 % on walls. Systems with a ventilated air space, such as 0.61 mm (24-gauge) sheet metal, allow 66 % on walls and 50 % on ceilings.[5] The reduced clearance is calculated from the unprotected clearance and the allowed reduction.[5]
| Symbol | Description | Unit |
|---|---|---|
| Minimum allowable clearance with protection | mm | |
| Required clearance with no protection | mm | |
| Maximum allowable reduction for the protection system | % |
For a solid-fuel room heater with an unprotected clearance of 914 mm (36 in.) and a wall shield of sheet metal on a ventilated air space, R = 66 %. The minimum clearance is then 914 × (1 − 0.66) ≈ 311 mm.[5] The handbook table lists this case as 305 mm (12 in.), and as 457 mm (18 in.) for the same shield used on a ceiling.[5] For a single-wall connector that needs 457 mm (18 in.), the same shield gives 457 × 0.34 ≈ 155 mm, listed as 152 mm (6 in.).[33] The tabulated values are rounded down to whole inches, so the formula result is the safer value. No reduction may bring the clearance below the value that the table allows, and clearances in front of loading or ash doors are not reduced.[5]
The conditions on the materials matter. Mineral wool batts must have a density of at least 128.7 kg/m³ and a melting point of at least 816 °C. Insulation used in a reduction system must also have a low thermal conductivity, specified as no more than 1.0 Btu·in./(ft²·h·°F).[5] The protector itself must stand at least 25 mm (1 in.) away from the appliance.[5] Insulation alone is not sufficient, because long continued heat eventually penetrates any thickness. It protects only if some method conducts the heat away before it reaches the combustible material.[32][34]
Clearances in practice
Inadequate clearance is a common thread in the handbook's fire experience. In United States home structure fires in 1999–2002, a heat source too close to combustibles was a contributing factor in 12 % of the fires coded in Version 5.0 of the national reporting system.[35] Fires in solid-fuel room heaters are due primarily to inadequate clearances and other installation deficiencies, and to poor maintenance.[36] The connector problems named are violations of the 457 mm (18 in.) clearance and single-wall connectors passing unprotected through combustible walls.[21] Central warm-air furnaces cause fires through inadequate clearances, and under some operating conditions their plenums become hot enough to ignite adjacent unprotected woodwork.[37]
Moveable combustibles cause a recurring problem. Maintaining clearance from furniture, bedding and clothing is a common problem for all types of portable and area heating equipment, including the portable space heater.[7] Winter preparedness guidance advises keeping kerosene heaters at least 0.9 m (3 ft) from flammable objects.[38] When the 1996 edition of the National Fuel Gas Code allowed listed unvented wall-mounted heaters in bedrooms and bathrooms, the committee's concern was the lack of clearance in these small rooms. Heaters there might be used to dry towels and clothing, and wall-mounted heaters were seen as addressing this concern.[39]
The handbook's occupancy and process chapters repeat the requirement. Housekeeping checklists call for ample horizontal and overhead clearances for portable heaters and ample clearance around boilers and furnaces.[40] In storage occupancies, sufficient clearance must be kept between stored goods and heating appliances or lighting fixtures.[41] Engine exhausts piped outside a building under construction need at least 152 mm (6 in.) to combustibles.[42] On pleasure and commercial motor craft, fabrics may not be used within 1 m (39 in.) of a galley stove.[43] Railway cabooses heated by oil or coal have had fires because stoves and stovepipes lacked adequate clearance.[44]
Limitations and misconceptions
Masonry or concrete attached directly to a combustible surface may look like protection to a layperson, but it may provide none. Heat transfer through a covering usually becomes more efficient as its density increases. Without an air space, the heat transfer to the combustible can therefore increase, and the masonry only delays ignition by its mass.[34][2] Filling the air space around a chimney with insulation is equally hazardous, even with noncombustible insulation, because it stops the heat from dissipating.[17]
The standard tables assume continuous operation at maximum temperature in a room that is large compared with the appliance. A very large appliance may need more clearance, and the handbook therefore recommends installing every appliance according to the terms of its listing.[4] A clearance that is correct at installation can also be lost later. Before and during the heating season, frequent checks are needed to make sure the area stays free of combustibles.[4] Space around an appliance also matters for servicing, because equipment that is hard to reach tends to be neglected.[2]
The values in this article come from the 2008 United States handbook, based on NFPA 211 and UL standards of that period. The New Zealand values are those reproduced in the 2013 commentary. Later editions, other countries and the listing of a specific appliance may give different values. Two handbook tables also contain inconsistencies. The metric value printed for the 6 in. steam pipe clearance does not match the inch value.[1] The connector reduction table names a 914 mm base clearance, while its values correspond to 457 mm.[33]
See also
Notes
- ↑ 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 1.10 1.11 Gore Willse (2008a), p. 10-28.
- ↑ 2.0 2.1 2.2 Gore Willse (2008a), p. 10-35.
- ↑ 3.0 3.1 3.2 Gore Willse (2008a), p. 10-47.
- ↑ 4.00 4.01 4.02 4.03 4.04 4.05 4.06 4.07 4.08 4.09 4.10 4.11 4.12 4.13 4.14 Gore Willse (2008a), p. 10-31.
- ↑ 5.00 5.01 5.02 5.03 5.04 5.05 5.06 5.07 5.08 5.09 5.10 Gore Willse (2008a), p. 10-32.
- ↑ 6.0 6.1 Ministry of Business, Innovation and Employment (2013), p. 14.
- ↑ 7.0 7.1 Lathrop (2008b), p. 20-58.
- ↑ Gore Willse (2008a), p. 10-25.
- ↑ National Research Council of Canada et al. (2005), pp. 1.2-9–1.2-10.
- ↑ Van Rossum (2027), §4.2.
- ↑ Iqbal and Salley (2004), p. 6-2.
- ↑ Kodur and Harmathy (2002), p. 1-164.
- ↑ 13.0 13.1 Madrzykowski and Stroup (2008), p. 2-34.
- ↑ 14.0 14.1 14.2 14.3 14.4 14.5 Cholin (2008c), p. 6-69.
- ↑ Gray (2002), p. 2-211.
- ↑ Gray (2002), p. 2-224.
- ↑ 17.0 17.1 17.2 Gore Willse (2008a), p. 10-51.
- ↑ Mattern et al. (2008), p. 10-104.
- ↑ 19.0 19.1 19.2 Ministry of Business, Innovation and Employment (2013), p. 15.
- ↑ 20.0 20.1 20.2 20.3 20.4 20.5 Van Rossum (2027), §5.4.
- ↑ 21.0 21.1 21.2 Gore Willse (2008a), p. 10-24.
- ↑ Tewarson (1995), as cited in Iqbal and Salley (2004), p. 6-6.
- ↑ Gore Willse (2008a), p. 10-52.
- ↑ 24.0 24.1 Gore Willse (2008a), p. 10-30.
- ↑ 25.0 25.1 Gore Willse (2008a), p. 10-29.
- ↑ Gore Willse (2008a), pp. 10-54–10-55.
- ↑ 27.0 27.1 Gore Willse (2008a), p. 10-38.
- ↑ Gore Willse (2008a), p. 10-46.
- ↑ Gore Willse (2008a), p. 10-53.
- ↑ Demers (2008b), p. 10-79.
- ↑ Biggins (2008), p. 8-107.
- ↑ 32.0 32.1 Gore Willse (2008a), p. 10-33.
- ↑ 33.0 33.1 Gore Willse (2008a), p. 10-39.
- ↑ 34.0 34.1 Gore Willse (2008a), p. 10-34.
- ↑ Ahrens et al. (2008), p. 3-72.
- ↑ Gore Willse (2008a), p. 10-23.
- ↑ Gore Willse (2008a), p. 10-21.
- ↑ Penney (2008), p. 5-40.
- ↑ Gore Willse (2008a), pp. 10-41–10-42.
- ↑ Mattern (2008b), p. 11-37.
- ↑ J. Moore (2008), p. 20-161.
- ↑ Davis (2008a), p. 11-54.
- ↑ Eberly (2008), p. 21-156.
- ↑ C. J. Wright (2008b), p. 21-121.
References
- Ahrens, M., Frazier, P., & Kelch, G. (2008). Use of fire incident data and statistics. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-61–3-92). National Fire Protection Association.
- Biggins, J. B. (2008). Stationary combustion engines and fuel cells. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-105–8-111). National Fire Protection Association.
- Cholin, J. M. (2008c). Wood and wood-based products. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-61–6-74). National Fire Protection Association.
- Davis, R. J. (2008a). Fire hazards of construction, alteration, and demolition of buildings. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-47–11-58). National Fire Protection Association.
- Demers, D. P. (2008b). Ventilation of commercial cooking operations. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 10-77–10-89). National Fire Protection Association.
- Eberly, R. (2008). Marine vessels. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-151–21-185). National Fire Protection Association.
- Gore Willse, P. J. (2008a). Heating systems and appliances. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 10-9–10-56). National Fire Protection Association.
- Gray, B. (2002). Spontaneous combustion and self-heating. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-211–2-228). National Fire Protection Association; Society of Fire Protection Engineers.
- Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
- Kodur, V. K. R., & Harmathy, T. Z. (2002). Properties of building materials. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 1-155–1-181). National Fire Protection Association; Society of Fire Protection Engineers.
- Lathrop, J. K. (2008b). One- and two-family dwellings. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-55–20-61). National Fire Protection Association.
- Madrzykowski, D., & Stroup, D. W. (2008). Flammability hazard of materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-31–2-48). National Fire Protection Association.
- Mattern, L. J. (2008b). Housekeeping practices. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-27–11-38). National Fire Protection Association.
- Mattern, L. J., Catania, E., & Ehrlich, S. (2008). Boiler furnaces. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 10-91–10-104). National Fire Protection Association.
- Ministry of Business, Innovation and Employment. (2013). Commentary for Building Code clauses C1–C6 and Verification Method C/VM2.
- Moore, J. (2008). Storage occupancies. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-157–20-178). National Fire Protection Association.
- National Research Council of Canada, International Code Council, Department of Building and Housing, & Australian Building Codes Board. (2005). International fire engineering guidelines (2005 ed.). Australian Building Codes Board.
- Penney, G. (2008). Disaster preparedness education. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 5-29–5-43). National Fire Protection Association.
- Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.
- Wright, C. J. (2008b). Rail transportation systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-109–21-134). National Fire Protection Association.