A dip tank is a tank, vat or container of flammable or combustible liquid in which workpieces are immersed to coat, impregnate, prime or clean them.[1] Dip tanks range from small containers for cleaning parts to very large tanks in automated coating lines. Related equipment such as flow coaters, curtain coaters, roll coaters, solvent cleaners and vapour degreasers has similar hazards.[1] The liquids involved release a great deal of heat when they burn: their heat of combustion is about two and a half times that of an equal weight of wood. A fire also produces heavy smoke, which makes fire fighting very difficult.[1]
The hazard grows with a lower flash point, a larger exposed liquid surface, a greater depth or quantity of liquid, faster vapour generation and more combustible residue around the process.[2] Safety therefore rests on location and cut-off, ventilation that keeps vapour below a quarter of the lower flammable limit, control of ignition sources, and design features such as overflow pipes and bottom drains. Automatic covers and fire extinguishing systems complete the protection.[3][4] In the United States the subject is covered by NFPA 34, Standard for Dipping and Coating Processes Using Flammable or Combustible Liquids, as summarised in the Fire Protection Handbook (2008) for practice around 2007.[2]
Katunar (2008) describes dipping as the application of a coating, or another treatment, by immersing the workpiece in a tank, vat or container of flammable or combustible liquid. Dip tanks are built in many sizes and shapes for the specific process, from a small exposed liquid surface to a very large one.[1] In the SFPE Handbook, Kanury (2002b) lists dip tanks of paints or solvents among the typical forms in which liquid fuels occur in industry, next to sprays, spills and open pits.[5]
The same handbook chapter covers several related processes. Flow coaters pour unatomised coating from nozzles or slots onto the workpiece, usually inside an enclosure or tunnel, and recirculate the excess from a sump. Curtain coaters let the coating fall as a continuous vertical sheet onto flat workpieces. Roll coaters transfer it from liquid-coated rollers.[6] In electrostatic detearing, excess wet coating is drawn off the bottom edge of a dipped object by an electrostatic field.[2] A Spray booth applies similar coatings by atomisation, and in the United States the electrical hazardous location rules cover both spraying and dipping of flammable finishes.[7]
A typical installation, as drawn in the handbook, has a 2850 L (750 gal) process tank with a drainboard, a weir and an overflow drain, and a vent with a flame arrester. A quick-opening dump valve, released by a fusible link or by hand, drains the tank to a 3780 L (1000 gal) salvage tank. The same drawing shows automatic sprinklers, carbon dioxide or foam nozzles and a heat detector.[8]
Why dip tanks are hazardous
A burning dip tank is a Pool fire. The liquid itself does not burn: it must first evaporate, and the vapour then burns above the surface.[9] How easily this happens is described by the Flash point. This is the liquid temperature at which the vapour-air mixture just above the surface supports a momentary flash of flame when a small pilot flame is passed over it. At the slightly higher fire point the flame becomes self-sustaining; the fire point typically exceeds the flash point by about 20 to 40 °C.[10]
US practice groups liquids by flash point, following NFPA 30; this is explained under Flammable and combustible liquid classification. As summarised by Slye (2008), Class I liquids have flash points below 37.8 °C (100 °F). Class IA and IB lie below 22.8 °C (73 °F) and are separated by boiling point, and Class IC lies from 22.8 to 37.8 °C. Class II covers 37.8 to 60 °C (140 °F), Class IIIA 60 to 93 °C (200 °F) and Class IIIB 93 °C and above.[11] Common finishing solvents are mostly Class I. Cholin (2008d) gives approximate flash points of −20 °C for acetone, 4 °C for toluene and 27 °C for xylene.[12]
Katunar (2008) names two main factors for the severity of the hazard: the ease of ignition, and the rate of vapour generation from the liquid surface and from freshly coated articles, drainboards, floors and equipment. The intensity of the resulting fire and the chance of spread by radiation or by burning liquid also count.[2] Burning liquid can escape if a container ruptures, boils over or overflows. Flammable vapours are usually denser than air, collect in low points and can travel far before they meet an ignition source and flash back to the process.[2]
Water is a particular problem. Many flammable coatings are lighter than water and do not mix with it. Water from hose streams or sprinklers can therefore make the tank overflow and float the burning liquid away to other areas.[2] Several design features discussed below exist only to prevent this.
Size of a dip tank fire
For a given liquid, the size of a dip tank fire depends strongly on the exposed liquid surface. Katunar (2008) compares two tanks holding the same 1500 L (400 gal) of liquid. One is wide and shallow, with a vapour source of 7.5 m² (80 ft²); the other is narrow and deep, with 0.8 m² (9 ft²). In both cases the area of the coated objects comes on top. The handbook states that the wide tank generates more vapour and has a higher rate of heat release.[13]
The SFPE Handbook gives an empirical equation for large pool fires in which radiation from the flames dominates. The heat release rate is the product of the heat of combustion, a limiting burning rate per unit area and the pool area. A correction factor reduces the burning rate for smaller pools:[14]
| Symbol | Description | Unit |
|---|---|---|
| Heat release rate of the pool fire | kW | |
| Net heat of combustion of the liquid | kJ/kg | |
| Mass burning rate per unit area of a very large pool | kg/(m²·s) | |
| Empirical constant of the liquid | m⁻¹ | |
| Pool diameter | m | |
| Burning liquid surface area | m² |
The equation applies to pools larger than about 0.2 m across, which burn in the radiative regime. It describes open burning only, in a space large and well ventilated compared with the fire.[15] For xylenes the SFPE Handbook gives Δhc = 40.8 MJ/kg, = 0.090 kg/(m²·s) with an uncertainty of ±0.007, and kβ = 1.4 m⁻¹.[16]
Worked example. Assume both tanks in Katunar's comparison hold xylene and that the whole liquid surface burns. The wide tank has 7.43 m² (80 ft²); treated as a circle of equal area, its diameter is 3.08 m. The correction factor is 1 − e−1.4 × 3.08 = 0.987, so = 40,800 kJ/kg × 0.090 kg/(m²·s) × 0.987 × 7.43 m² ≈ 27 MW. The narrow tank has 0.84 m² (9 ft²) and an equivalent diameter of 1.03 m. Its correction factor is 0.764 and its heat release rate about 2.3 MW.[17]
The burning-rate uncertainty alone gives a range of about 25 to 29 MW for the wide tank.[17] The same liquid volume thus gives a fire more than ten times larger in the wide tank, which supports Katunar's point about exposed surface area. The result ignores burning on the drainboard, on freshly coated objects and on any spilled liquid, all of which add to the area. It also ignores the enhanced burning that occurs when hot gases in a room radiate back onto the pool.[13][16]
Location and construction
Segregation is the basic principle in choosing a location. Dip tanks should be separated from other operations by distance, fire walls or fire partitions, preferably in a detached or cut-off one-storey sprinklered building of fire-resistive construction.[18] On upper storeys floors should be liquid-tight and drained to a safe place; tanks should not stand below grade, over basements or near pits, where liquid and vapour are hard to remove.[18] Where a process cannot be cut off, non-combustible curtain boards from the roof, floor curbs and automatic roof vents limit the spread of heat, smoke and burning liquid. Where highly flammable or unstable liquids are used in confined areas, deflagration venting may be needed.[18] Small installations deserve the same care, because a small operation often causes a major loss.[18]
Tanks, drainboards and covers should be of non-combustible material such as heavy-gauge steel, reinforced concrete or masonry.[1] The handbook gives a set of size-based rules. The top of the tank should be at least 150 mm (6 in.) above the floor and the liquid surface at least 150 mm below the top. Tanks larger than 570 L (150 gal) or with more than 1 m² (10 ft²) of liquid surface need a trapped overflow pipe to a safe location. This pipe must carry the larger of the maximum process liquid delivery and the maximum sprinkler discharge, and must never be smaller than 75 mm (3 in.).[19]
Tanks of 1900 L (500 gal) or more need a bottom drain that empties them in 5 minutes, operable both manually and automatically. For a 1900 L tank that means at least 6.3 L/s, and for the 2850 L tank in the handbook drawing 9.5 L/s.[19][20] The drain should be trapped and lead to a closed, vented salvage tank larger than the dip tank, or to a safe location outside. Where no bottom drain is possible, the process should be cut off or fully diked and protected by both a special extinguishing system and sprinklers.[19] Supports of tanks above 1900 L or 1 m² should have a fire resistance rating of at least 1 hour, because spill or exposure fires can weaken supports and collapse the tank.[19][1]
Filling and storage are also controlled. A fill pipe from the top should end within 150 mm (6 in.) of the tank bottom, a filling pump needs a relief valve, and a limit device should prevent overfilling.[2] As summarised in the 2008 handbook, NFPA 34 limits storage cabinets to one of 454 L (120 gal) in a process area and 1350 L (360 gal) in total per fire area. In industrial occupancies, several groups of up to 1350 L each may share a fire area if they are 30 m (100 ft) apart. A single group of up to 2700 L (720 gal) is allowed if the building is sprinklered.[2]
Ventilation and vapour areas
In this context ventilation means air movement that prevents vapour-air mixtures above 25 percent of the lower flammable limit (LFL).[13] The vapour source is the exposed liquid, the drainboard and any coated object that still produces more than 25 percent of the LFL at 305 mm (1 ft). The surrounding vapour area should be as small as practical and should not extend more than 1.5 m (5 ft) from the source. Its actual extent can be measured with a combustible gas analyser.[13] Because vapours are denser than air, low-level peripheral exhaust works better than an overhead canopy hood, which lets vapour migrate.[13]
Typical exhaust rates are 15 to 60 m³/min per square metre (50 to 200 ft³/min per ft²) of wetted surface.[21] For Katunar's two tanks this gives 1.9 to 7.6 m³/s for the wide tank and 0.21 to 0.85 m³/s for the narrow one, before the coated objects are counted.[22] The hood, duct and fan form an Industrial exhaust system. The ventilation should run during dipping and afterwards until no vapour source remains, and automatic processes should stop if it fails.[21] Exhaust should discharge outdoors and not be recirculated into occupied spaces. Discharge points should be at least 1.8 m (6 ft) from walls and roofs and 7.6 m (25 ft) from combustible construction.[21]
Freshly coated objects should dry only in ventilated spaces or enclosures.[13] Many dipped parts are then baked. For batch ovens baking dip-coated metal parts, Ostrowski (2008a) reports a reasonably safe air change. It is about 10.7 m³/min (380 cfm) for each 3.79 L (1 gal) of flammable volatiles released.[23] Ovens directly above or beside dipping operations have been the ignition source of many fires. Their exhaust should be interlocked so that heating cannot run without ventilation, and indirect heating is preferred.[24]
Electrical classification and ignition sources
In the United States, electrical equipment must meet the hazardous location rules of NFPA 70, the National Electrical Code. This applies where Class I liquids are used, or Class II and III liquids at or above their flash point. For dipping, the classified areas are measured from the vapour source: the liquid surface or wetted surfaces.[21] The code defines these areas in its Article 516, and NFPA 34 gives further safeguards.[7]
For open processes, as summarised in the 2008 handbook, Class I, Division 1 (Zone 1) equipment is required within 1.5 m (5 ft) of the vapour source, and in pits within 7.6 m (25 ft). Division 2 (Zone 2) extends a further 0.9 m (3 ft) beyond Division 1, down to 0.9 m above the floor. Between the floor and 0.9 m it extends 6.1 m (20 ft) beyond Division 1, following the vapour downwards.[21] Tanks of at most 19 L (5 gal) with at most 0.5 m² (5 ft²) of surface are exempt, provided ordinary equipment is more than 2.4 m (8 ft) away. For enclosed processes, Division 1 applies inside the enclosure and Division 2 within 0.9 m of its openings.[21]
Open flames, spark-producing processes and surfaces hotter than the autoignition temperature of the liquid should be kept out of the process area and its surroundings.[24] Heating systems need limit controls where a liquid could be heated above its boiling point or to within about 56 K (100 °F) of its autoignition temperature. Heated workpieces should stay at least that margin below the autoignition temperature of the coating.[19] Conveyors, rollers and flowing liquid generate static electricity, so process equipment needs bonding and grounding, or humidification or ionisation of the air. Hot work needs strict supervision, and non-ferrous tools and a smoking ban are expected.[24]
Fire protection
The simplest extinguishing device is a self-closing cover that cuts off the air supply. A cable with a fusible link holds it open; heat melts the link and the cover drops onto the tank.[25] Covers should be non-combustible, overlap the tank by at least 25 mm (1 in.), stay closed when the process is idle and not be obstructed by drainboards. For open tanks under 570 L (150 gal) or under 1 m² (10 ft²), an automatic and manually operable cover or an extinguishing system is needed.[4] Ceiling sprinklers can protect small processes and combustible coatings with limited surface. They are essential for the building at larger installations and often back up special systems.[25]
Automatic fire extinguishing systems are needed for enclosed processes, for open processes with peripheral vapour containment, and for tanks over 570 L (150 gal) or 1 m² (10 ft²). They should discharge simultaneously onto the tank, the drainboard, the freshly coated work, the pumps and the exhaust ducts. Suitable agents are foam, carbon dioxide and dry chemical, and water spray for liquids with flash points above 60 °C (140 °F).[25] Sprinkler water must not overflow the tank. This is achieved by drainboards that keep water out of the tank, by automatic covers or by an overflow pipe.[4]
A Carbon dioxide extinguishing system for an open tank can work by local application: the gas is discharged directly onto the burning surface instead of filling a room.[26] The liquid part of the discharge should last at least 30 seconds, or 3 minutes for liquids whose autoignition temperature is below their boiling point.[27] Local application can still create dangerous concentrations in the room and in adjacent low-lying spaces, so each system must be assessed for personnel safety.[28] The SFPE Handbook also lists dip and quench tanks among typical local application hazards.[29]
Ventilation should be interlocked with the fire alarm and keep running during an alarm. Where a special extinguishing system protects the process, however, fans may have to stop and duct dampers close.[4] Portable extinguishers suitable for flammable liquid fires belong in the process area. Under NFPA 10, as summarised in NUREG-1805, painting, dipping and coating are examples of extra hazard occupancies for extinguisher selection.[4][30]
Maintenance, regulation and limits of the sources
Combustible residue near dip tanks can ignite spontaneously through oxidation or reaction between coating components. Where excess residue builds up in work areas, ducts or discharge points, operations should stop until it is cleaned.[19] Cleaning solvents should have flash points above 38 °C (100 °F), or not below those of the process liquids. Waste containers should be emptied at least daily or after each shift.[19] Inspections, usually at least monthly, should cover covers, overflow pipes, drains, wiring, grounding, ventilation and extinguishing equipment.[31]
All requirements in this article are US practice as described in the 2008 handbook, not current or universal rules. At federal level, the Occupational Safety and Health Administration regulates dip tanks with flammable or combustible liquids in 29 CFR 1910.108. Many of these rules derive from older editions of NFPA standards.[32] The handbook does not state which editions of NFPA 34 and NFPA 30 it summarises.[33]
The handbook text contains two inconsistencies. After saying that the wide tank in its comparison generates more vapour and heat, it ends with a sentence calling the tank with the smaller surface the greater hazard.[13] It also gives slot velocities as 1000 to 2000 ft³/min (28 to 56 m³/min), a volume-flow unit, so that value is not used here.[21] The pool fire example is a free-burning estimate and gives no information on room effects.[16]
See also
- Local application system
- Oil quenching
- Hazardous area classification
- Industrial oven and furnace
- Explosion venting
Notes
- ↑ 1.0 1.1 1.2 1.3 1.4 1.5 Katunar (2008), p. 9-39.
- ↑ 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 Katunar (2008), p. 9-42.
- ↑ Katunar (2008), pp. 9-42–9-43.
- ↑ 4.0 4.1 4.2 4.3 4.4 Katunar (2008), p. 9-50.
- ↑ Kanury (2002b), p. 2-188.
- ↑ Katunar (2008), pp. 9-40–9-42.
- ↑ 7.0 7.1 Milatovich (2008), p. 8-172.
- ↑ Katunar (2008), p. 9-40.
- ↑ Van Rossum (2027), §4.1.
- ↑ Kanury (2002b), p. 2-190.
- ↑ Slye (2008), p. 6-198.
- ↑ Cholin (2008d), p. 9-11.
- ↑ 13.0 13.1 13.2 13.3 13.4 13.5 13.6 Katunar (2008), p. 9-44.
- ↑ Babrauskas (2002b), p. 3-25.
- ↑ Babrauskas (2002b), pp. 3-25–3-26.
- ↑ 16.0 16.1 16.2 Babrauskas (2002b), p. 3-26.
- ↑ 17.0 17.1 Calculation with values from Katunar (2008), p. 9-44, and Babrauskas (2002b), pp. 3-25–3-26; the equal-area circle is an assumption of this example.
- ↑ 18.0 18.1 18.2 18.3 Katunar (2008), p. 9-43.
- ↑ 19.0 19.1 19.2 19.3 19.4 19.5 19.6 Katunar (2008), p. 9-48.
- ↑ Calculation based on Katunar (2008), pp. 9-40 and 9-48.
- ↑ 21.0 21.1 21.2 21.3 21.4 21.5 21.6 Katunar (2008), p. 9-45.
- ↑ Calculation with values from Katunar (2008), pp. 9-44–9-45.
- ↑ Ostrowski (2008a), p. 8-80.
- ↑ 24.0 24.1 24.2 Katunar (2008), p. 9-47.
- ↑ 25.0 25.1 25.2 Katunar (2008), p. 9-49.
- ↑ Wysocki (2008), p. 17-6.
- ↑ Wysocki (2008), p. 17-13.
- ↑ Wysocki (2008), p. 17-8.
- ↑ Grant (2002), p. 4-158.
- ↑ Iqbal and Salley (2004), p. B-14.
- ↑ Katunar (2008), p. 9-49.
- ↑ Snyder (2008), p. 12-183.
- ↑ Katunar (2008), p. 9-51.
References
- Babrauskas, V. (2002b). Heat release rates. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-1–3-37). National Fire Protection Association; Society of Fire Protection Engineers.
- Cholin, J. M. (2008d). Woodworking facilities and processes. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-3–9-25). National Fire Protection Association.
- Grant, C. C. (2002). Halon design calculations. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 4-149–4-172). National Fire Protection Association; Society of Fire Protection Engineers.
- Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
- Kanury, A. M. (2002b). Ignition of liquid fuels. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-188–2-199). National Fire Protection Association; Society of Fire Protection Engineers.
- Katunar, J., III (2008). Dipping and coating processes. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-39–9-51). National Fire Protection Association.
- Milatovich, R. M. (2008). Electrical systems and appliances. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-127–8-173). National Fire Protection Association.
- Ostrowski, R. (2008a). Industrial and commercial heat utilization equipment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-71–8-92). National Fire Protection Association.
- Slye, O. M., Jr. (2008). Flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-197–6-208). National Fire Protection Association.
- Snyder, M. (2008). Industrial fire loss prevention. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 12-177–12-198). National Fire Protection Association.
- Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.
- Wysocki, T. J. (2008). Carbon dioxide and application systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-3–17-15). National Fire Protection Association.