Oil quenching is a heat treatment process in which hot metal parts are hardened and tempered by plunging them into a bath of oil, which cools them in a controlled way.[1] In the Fire Protection Handbook (2008), Ostrowski describes it as a controlled cooling of heated materials by immersion in a liquid quenching medium. This changes the metallurgy at the surface of the metal.[1] Because quench oils are combustible, the process carries a serious fire hazard.[1] The oil is often heated, up to about 204 °C in heated quenching, and may lie under a flammable furnace atmosphere.[2]

The handbook names partial immersion of the work as the most common cause of quench oil fires.[3] Water that leaks into the oil is an even greater danger: a hot workload can then cause a boilover or a steam explosion.[4] Safe practice in the United States, as summarised in the 2008 handbook, rests on several measures. These include tank freeboard and drains, rapid and complete immersion, oil temperature control, interlocks, and fixed extinguishing systems over the tank.[2][5]

Process and quench media

Quenching may be automatic and continuous, semiautomatic or a batch operation. In each case elevators, conveyors, hoists or cranes immerse the work in the oil, move it through the bath and lift it out. Of these three steps, the entry of the work into the quench is the one critical to safety.[1] The quench tank is often built as an integral part of a special atmosphere furnace, an industrial oven or furnace in which a protective gas surrounds the work during heating.[4]

Mineral oils are used in most cases. Specific metallurgical requirements sometimes call for mixtures with animal or vegetable oils, and wetting agents may be blended in.[1][2] A quench oil should have a low viscosity and should stay stable and fluid over long use.[2] Polymer quenchants are a more recent alternative in integral quench furnaces. A furnace designed for oil cannot simply be changed over to polymer, and the handbook advises consulting the furnace manufacturer first.[2] Steel parts can also be quenched isothermally in molten salt baths, which form a separate group of processes with their own hazards.[6]

The operating temperature of the oil sets the margin to ignition. For unheated quenching, temperatures of 38 to 93 °C (100 to 200 °F) are considered normal, and standard quench oils for this range usually have flash points somewhat above 149 °C (300 °F).[2] For heated quenching, operating temperatures of 93 to 204 °C (200 to 400 °F) are common. Oils for this service generally have flash points above 260 °C (500 °F).[2]

Fire hazards

Why a quench tank burns

The flash point of a liquid is the temperature at which the vapour-air mixture just above its surface can support a brief flash of flame when a small pilot flame is swept near it. At the slightly higher fire point, the flame becomes self-sustaining and the liquid keeps burning.[7] For spilled liquids, the temperature of the liquid relative to its flash point is the single most important factor in how fast flame spreads over the surface.[8] A quench bath is an open pool of combustible oil, often heated, into which much hotter work is plunged. Failures that overheat the oil locally, such as a loss of agitation, can cause a fire at the surface.[4]

The handbook lists seven factors that contribute to the hazard. These are a special atmosphere of flammable gas over the oil, the temperature required of the oil, its physical properties and its limited volume. The size and shape of the work, the location of furnaces and tanks, and mutual exposure with other processes or storage complete the list.[1] In the US water supply guidance described by Martin (2008), open oil quenching is listed with flammable liquid spraying and paint dipping among the extra hazard (Group 2) occupancies.[9]

Partial immersion

Rapid and complete immersion is essential both for the metallurgy and for safety. The method must give minimal splashing and no overflow, and partial immersion must be eliminated or minimised.[3] Trays, baskets and elevators cause partial immersion more often than any other handling method.[4]

The handbook names three critical concerns. The elevator must be supported so it cannot fall unevenly, and it needs guides so it cannot wedge. Stops must prevent the load from shifting and jamming the elevator.[4] Chutes must let the work fall freely under all normal feed conditions, with proper size, pitch and smooth surfaces.[3]

Hoists and cranes for large workloads need stops, limit switches and sometimes mechanical guides to position the work over the tank.[4] When the work is lifted out, it is usually still warm and some oil may vaporise. Any ignition source can then start a fire, and oil vapour that condenses on cool surfaces above the drain area adds to the potential loss.[4]

Water in the oil

The handbook regards water entering the oil as more hazardous than a simple loss of cooling. When a hot workload is immersed in oil that contains too much water, the water flashes to steam and can produce a boilover.[4] The critical water volume varies with the oil. If the water content reaches 0.50 % by volume, the oil is no longer considered safe to use.[4] Water expands 1,600 to 1,700 times when it turns to steam, and 3.8 L (1 US gal) of water gives more than 6.3 m³ of steam.[10]

The term boilover is used here in a broad sense. In the terminology of Slye (2008), a true boilover occurs in a burning open-top tank of crude oil after a long period of burning, when a hot, dense residue layer sinks towards free water at the tank bottom.[11] The overflow of a container that is not on fire, when water boils under the surface of a viscous hot oil, is called a frothover. A slopover is the milder case in which water is applied to the surface of a burning oil above 100 °C.[12] In a quench tank the common factor is water turning to steam beneath hot oil, which throws hot or burning oil out of the tank.

The usual sources of water are the cooling systems. Quench oil can be cooled by coils in the tank, by external heat exchangers or by water jackets.[4] According to the handbook, water jackets and internal water coils must not be used with combustible quench oils. A failure of a coil or of the tank shell lets water into the oil, often without being noticed. The first sign may then be a boilover or steam explosion when a hot load goes in.[4]

In an external heat exchanger, the oil must be circulated at a higher pressure than the cooling water, so that a leak sends oil into the water and not water into the oil.[4] Water-cooled vestibules above integral quench tanks have also failed many times and released cooling water into the tank below.[4]

Overheating and furnace atmospheres

If the oil level is too low when a large workload is immersed, the oil can overheat. Low-level detectors should therefore sound an alarm and shut down quenching before this happens.[4] Agitation keeps the bath temperature safe and uniform. If it fails, local overheating can cause a fire at the surface. Excess vaporisation can also raise the pressure inside an enclosed special atmosphere furnace and force gas and oil vapour out around doors and vents, where they often ignite.[4]

Where the oil is heated by immersion heaters, the interface between heater and oil becomes excessively hot. The heating system should then be locked out if the level is low, the agitation is off or the oil is too hot.[4] Hydraulic systems near the furnace add fuel. The handbook recommends a fire-resistant hydraulic fluid, such as a water-in-oil emulsion, a water-glycol fluid or a synthetic phosphate ester.[5][13]

Tank design and layout

A quench tank should allow proper quenching under normal conditions and tolerate small control variations and operator errors. A fire confined to the oil surface in the tank is much easier to control than a fire in oil that has overflowed.[2] The freeboard is the distance from the oil surface to the top of the tank with the tank loaded to capacity. It must allow for the splashing expected when the largest load enters at maximum speed. The oil level with the work submerged should be at least 152 mm (6 in.) below the furnace door or any other opening.[2]

Fully trapped overflow drains should lead overflowing oil to a safe location outside the building or to special tanks. Tanks with a capacity of 570 L (150 gal) or more, or a liquid surface of 0.93 m² (10 ft²) or more, should have them.[2] Bottom drains or pumps allow the tank to be emptied in a serious fire, and they should be sized to remove the oil within 5 minutes.[3] The handbook gives minimum pipe sizes for both.[2][3]

Overflow drain: liquid surface area Minimum pipe diameter (I.D.)
0.93–6.7 m² (10–75 ft²) 76 mm (3 in.)
6.7–14 m² (75–150 ft²) 101 mm (4 in.)
14–21 m² (150–225 ft²) 127 mm (5 in.)
21–30.2 m² (225–325 ft²) 152 mm (6 in.)
over 30.2 m² (325 ft²) 203 mm (8 in.)
Emergency gravity drain: tank capacity Minimum pipe diameter (I.D.)
1.9–2.8 m³ (500–750 gal) 76 mm (3 in.)
2.8–3.8 m³ (750–1,000 gal) 101 mm (4 in.)
3.8–9.5 m³ (1,000–2,500 gal) 127 mm (5 in.)
9.5–15 m³ (2,500–4,000 gal) 152 mm (6 in.)
over 15 m³ (4,000 gal) 203 mm (8 in.)

Emergency drains should only be used under the control of trained and experienced personnel. Where a flammable atmosphere lies over the oil, draining can create a negative pressure. This may cause an explosion, a more severe fire, or both.[3]

Quench operations should be housed in fire-resistive buildings, well separated from exits, combustible materials, valuable stock and important equipment. The safest location for a tank is at grade. A boilover from a tank above grade spreads fire to the floors below, and a fire below grade is hard to fight manually.[3]

Tanks need noncombustible hoods and vents to remove vapours. These ducts are treated as flues, kept clear of combustible roofs and protected by an approved automatic extinguishing system.[3] A similar combination of open tank, hood and drainage is found at a dip tank, although there the liquid is usually a flammable coating or solvent rather than a hot oil.

Temperature limits and a worked example

Three simple rules from the handbook can be written as equations. The first limits the oil temperature in a central oil system relative to the flash point of the oil. The handbook states that the temperature must never rise to less than 50 °F below the flash point, whatever oil is used.[5] It gives the SI equivalent as 10 °C, but a temperature difference of 50 °F corresponds to 27.8 °C, so the larger margin is the safe reading.

Tmax=Tfp−ΔTm

The second is the average flow that the emergency drains or pumps must achieve to empty the tank within 5 minutes.[3] The third estimates the steam volume released when water in the oil boils, using the expansion ratio of water to steam given by Frank (2008).[10]

V˙d=VoiltdVs≈EVw

Symbol Description Unit
Tmax Highest permitted oil temperature °C
Tfp Flash point of the quench oil °C
ΔTm Margin below the flash point: 50 °F, that is 27.8 K K
V˙d Average emergency drain flow m³/s
Voil Volume of oil in the tank m³
td Maximum emptying time, 300 s (5 minutes) s
Vs Volume of steam formed m³
Vw Volume of liquid water in the oil m³
E Expansion ratio of water to steam, 1,600 to 1,700 –

As an example, consider a quench tank of 3.0 m by 2.0 m holding oil to a depth of 1.9 m. These dimensions are assumed for illustration. The tank holds 11.4 m³ (about 3,000 US gal) and has a liquid surface of 6.0 m² (65 ft²).

  • Overflow drain: a surface of 6.0 m² falls in the range 0.93–6.7 m², so the minimum overflow pipe is 76 mm (3 in.).[2]
  • Emergency drain: 11.4 m³ falls in the range 9.5–15 m³, so the minimum gravity drain is 152 mm (6 in.).[3] To empty the tank in 300 s, the drain must pass on average 11.4/300 = 0.038 m³/s, or 38 L/s.
  • Water limit: 0.50 % of 11.4 m³ is 57 L of water.[4] With an expansion ratio of 1,600 to 1,700, this water would form about 91 to 97 m³ of steam, roughly eight times the volume of oil in the tank.
  • Temperature: a heated quench oil with a flash point of 260 °C, kept 27.8 °C below it, may not exceed about 232 °C. At the top of its common operating range of 93 to 204 °C, the oil is 56 °C below its flash point and 28 °C below this limit.[2]

The steam estimate shows why a fraction of a percent of water matters, even though the steam forms in pockets and not all at once. The example applies the handbook rules to an assumed tank. It is not a design: drain pipes must also be designed for each tank, and US practice may have changed since the 2008 edition.[2]

Controls and fire protection

Every automatic shutdown of a quench operation should leave the workload either completely immersed or completely removed. Partial immersion must always be considered hazardous.[5] If a malfunction stops the load, qualified operators must be allowed to override the interlocks and finish the immersion or remove the load by hand. If exit doors have to be opened, a fire should be expected, and extinguishing means to protect the operator should be at hand.[5]

All safety controls and interlocks should be tested on a regular schedule, at intervals of no more than six months.[5] In a central oil system serving several tanks, the oil flow must be supervised. Replenishment oil should not be added while the quench is at 100 °C (212 °F) or above, because it could foam or boil over.[5]

The handbook calls automatic water spray one of the most effective forms of area protection. Ceiling sprinklers have limited building and equipment damage both from fires confined to the tank and from oil spread by a boilover.[5] For the open oil surface and the drainage areas, most oil fires can be extinguished by a fixed carbon dioxide extinguishing system or by dry chemical. Foam may also work, depending on the oil and its temperature. These systems are meant to act automatically, well before any sprinkler discharge.[5]

Wysocki (2008) gives a minimum design carbon dioxide concentration of 34 % for quench and lubricating oils, against a theoretical minimum of 28 %.[14] In local application, carbon dioxide is discharged directly onto the burning surface through low-velocity nozzles that avoid splashing, and automatic detection is a necessity.[15][16] At concentrations above 9 %, most people lose consciousness within a short time, so personnel safety measures are part of every such system.[14]

Fixed foam systems for open dip and quench tanks use a small aspirating foam-maker. It discharges into a mixing box that spreads the foam gently over the surface.[17] Where operators must free jammed loads and close furnace doors, carbon dioxide or fixed water spray is the most effective protection for the operator.[5] Manual fire equipment and trained personnel are, in the words of the handbook, the most important protection in every heat treatment shop. This includes portable and wheeled extinguishers and hose connections with fog or spray nozzles.[5]

Conroy (2008) groups quench tank fires with other fires in liquids deeper than 6.4 mm (¼ in.). Portable extinguishers should not be relied on for an indoor open tank of more than about 1 m² (10 ft²), because heat and smoke make it dangerous to stay near it.[18]

Limits of the guidance

The guidance in this article reflects US practice as summarised in the 2008 handbook. The handbook refers to NFPA 86, Standard for Ovens and Furnaces, for hydraulic equipment, but names no standard or edition for its quench tank rules.[5] The temperature ranges, drain sizes, the 0.50 % water limit and the six-month test interval are typical values from that source. They are not universal requirements and may differ in later editions and in other countries. The handbook itself stresses that fire protection for oil quenching requires a detailed evaluation of the specific hazard, and that the suitability of foam depends on the oil and temperatures involved.[5] The critical water content also varies with the specific oil or oil mixture.[4] Settling and centrifuges in central oil systems are not dependable enough to replace periodic testing of the oil in each tank.[5]

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 1.4 1.5 Ostrowski (2008b), p. 8-93.
  2. ↑ 2.00 2.01 2.02 2.03 2.04 2.05 2.06 2.07 2.08 2.09 2.10 2.11 2.12 2.13 Ostrowski (2008b), p. 8-94.
  3. ↑ 3.00 3.01 3.02 3.03 3.04 3.05 3.06 3.07 3.08 3.09 Ostrowski (2008b), p. 8-95.
  4. ↑ 4.00 4.01 4.02 4.03 4.04 4.05 4.06 4.07 4.08 4.09 4.10 4.11 4.12 4.13 4.14 4.15 4.16 4.17 Ostrowski (2008b), p. 8-96.
  5. ↑ 5.00 5.01 5.02 5.03 5.04 5.05 5.06 5.07 5.08 5.09 5.10 5.11 5.12 5.13 Ostrowski (2008b), p. 8-97.
  6. ↑ Ostrowski (2008b), p. 8-99.
  7. ↑ Kanury (2002b), p. 2-190.
  8. ↑ Gottuk and White (2002), p. 2-300.
  9. ↑ Martin (2008), p. 15-68.
  10. ↑ 10.0 10.1 Frank (2008), p. 17-32.
  11. ↑ Slye (2008), p. 6-205.
  12. ↑ Slye (2008), p. 6-206.
  13. ↑ Schacht (2008), p. 8-115.
  14. ↑ 14.0 14.1 Wysocki (2008), p. 17-5.
  15. ↑ Wysocki (2008), p. 17-6.
  16. ↑ Wysocki (2008), p. 17-7.
  17. ↑ Scheffey (2008), p. 17-60.
  18. ↑ Conroy (2008), p. 17-72.

References

  • Conroy, M. T. (2008). Fire extinguisher use and maintenance. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-71–17-92). National Fire Protection Association.
  • Frank, J. A. (2008). Characteristics and hazards of water and water additives for fire suppression. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-31–17-43). National Fire Protection Association.
  • Gottuk, D. T., & White, D. A. (2002). Liquid fuel fires. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-297–2-316). National Fire Protection Association; Society of Fire Protection Engineers.
  • Kanury, A. M. (2002b). Ignition of liquid fuels. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-188–2-199). National Fire Protection Association; Society of Fire Protection Engineers.
  • Martin, W. M. (2008). Water supplies for sprinkler systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 15-63–15-73). National Fire Protection Association.
  • Ostrowski, R. (2008b). Oil quenching and molten salt baths. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-93–8-103). National Fire Protection Association.
  • Schacht, P. K. (2008). Fluid power systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-113–8-116). National Fire Protection Association.
  • Scheffey, J. L. (2008). Foam extinguishing agents and systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-45–17-70). National Fire Protection Association.
  • Slye, O. M., Jr. (2008). Flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-197–6-208). National Fire Protection Association.
  • Wysocki, T. J. (2008). Carbon dioxide and application systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-3–17-15). National Fire Protection Association.