Contents
A pyrophoric material is a substance that ignites spontaneously on contact with air, without any external ignition source.[1][2] In the international transport hazard classes given in the 2008 Fire Protection Handbook, a pyrophoric liquid or solid is one that, even in small quantities, can ignite within 5 minutes of contact with air.[2] Pyrophoric gases, such as silane and phosphine, are flammable gases that ignite spontaneously in air, and they are found mainly in semiconductor manufacturing.[3] Typical solid and liquid examples are white phosphorus, the aluminium alkyls such as triethylaluminium, and some finely divided metals such as zirconium dust and plutonium chips.[4][1][5][6] Because they need no spark or flame, keeping ignition sources away does not protect them. They must be isolated from air by a method suitable for the particular substance, such as water, an inert liquid or gas, or a closed system.[3][1][7] Some, such as the aluminium alkyls, also react violently with water, and some pyrophoric gases can be released without immediate ignition and then explode.[1][8]
Definition and classification
The word describes behaviour rather than a chemical family. Davenport (2008) explains it for the aluminium trialkyls, most of which are pyrophoric, "that is, they ignite spontaneously on exposure to air".[1] DeGiorgio and Peterkin (2008) use the same wording for gases that "ignite spontaneously on contact with air".[7] NUREG-1805 defines pyrophoricity as the spontaneous combustion of a material upon exposure to air, that is, to atmospheric oxygen.[9]
Transport rules add a time limit: in the hazard classes reproduced by C. J. Wright (2008a), Division 4.2, the spontaneously combustible materials, contains two groups.[2] A pyrophoric material is a liquid or solid that, even in small quantities and without an external ignition source, can ignite within 5 minutes after contact with air.[2] A self-heating material is one that, in contact with air and without an energy supply, is liable to self-heat.[2] Phosphorus, aluminium alkyls and charcoal are the examples given for the division, and the class is described as flammable, some members spontaneously, possibly water reactive, toxic or corrosive, and possibly extremely difficult to extinguish.[10] NUREG-1805 lists the same division in its table of United States Department of Transportation hazard classes.[11]
For gases, NFPA 55, as described by Lemoff (2008), treats pyrophoric gas as a separate physical hazard class, next to flammable, oxidising and unstable reactive gases.[3] Pyrophoric gases are flammable gases that spontaneously ignite in air; their storage is of special concern because they do not require a source of ignition to burn.[3] Hildebrand and Noll (2008) also list pyrophorics among the examples of a physical hazard under the United States workplace rules (OSHA, 29 CFR 1910) as they stood at the time.[12]
How pyrophoric ignition differs from ordinary ignition
Ignition normally needs heat. In the fire triangle described by Van Rossum (2027), a combustible substance mixed with oxygen cannot ignite unless enough heat is supplied, and the ignition temperature is the lowest temperature at which ignition takes place.[13] The autoignition temperature of a liquid is the temperature of the surroundings that starts combustion without an obvious ignition source.[14] It is measured by heating a closed or nearly closed container until the vapour ignites by itself, often after a time lag.[14] Rosales and Stoltzfus (2008) call the same minimum temperature the autoignition or spontaneous ignition temperature.[15] A pyrophoric material ignites in ordinary air at ordinary temperatures, without this heating.[4][3]
The mechanism is rapid oxidation. Christman (2008) notes that some metals oxidise so quickly in air or moisture that they generate enough heat to reach their ignition temperatures, while others oxidise so slowly that the heat is dissipated first.[16] Metals tend to be most reactive when finely divided, and finer particles or thinner sections present an increasing hazard; Christman reports reduced reactivity for sections thicker than 381 µm (0.015 in.).[17] The same metal can therefore be pyrophoric as a powder and very difficult to ignite as a casting.[16] Zirconium in massive form withstands extremely high temperatures, yet clouds and layers of dust with an average particle size of about 3 µm can ignite spontaneously at room temperature.[5] Zalosh (2002) reads the zero limiting oxygen concentration measured for zirconium dust as a sign of its pyrophoric behaviour as a powder.[18]
Self-heating is the slower relative. Self-heating and eventual spontaneous ignition can occur if the heat produced by auto-oxidation is not removed, especially in porous solids such as coal, where the material insulates its own interior.[19] The transport definitions draw the line by time: a pyrophoric material can ignite within 5 minutes of contact with air, whereas a self-heating material is liable to heat up and may eventually ignite.[2][19]
Pyrophoric solids and liquids
White, or yellow, phosphorus is the classic example. It is more dangerous than red phosphorus because it oxidises readily and ignites spontaneously in air, and it is therefore shipped and stored under water, usually in hermetically sealed metal containers.[4] It is very toxic, should not touch the skin, and on ignition gives off dense white clouds of toxic fumes that attack the lungs.[4] Red phosphorus does not oxidise and burn spontaneously at ordinary temperatures and can be stored without water.[4] Once it has turned to vapour, however, it takes on all the fire hazards of white phosphorus, to which it reverts on condensation.[4] Care is needed when containers of red phosphorus are opened, because spontaneous ignition can take place on exposure to air.[4]
Organometallic compounds form the second group. Most aluminium trialkyls are pyrophoric and also react violently with water and certain other chemicals.[1] Triethylaluminium, the most common member, ignites spontaneously both in air and on contact with water, and mixtures with strong oxidising agents or halogenated hydrocarbons can react violently or detonate.[1] Some hydrides behave in a related way. Sodium hydride may ignite when it absorbs moisture from the air, and a spilled solution of lithium aluminium hydride in ether may ignite combustibles spontaneously or by light friction.[4]
Many metals are pyrophoric in finely divided form, which links this hazard to that of the combustible metal. Finely divided calcium ignites spontaneously in air, and barium and strontium behave similarly.[20] Hafnium in sponge form may ignite spontaneously unless it has been inactivated.[5] Plutonium dust and chips are subject to spontaneous ignition in air, and plutonium is normally handled by remote control in an inert gas.[6] Uranium scrap from machining is subject to spontaneous ignition, and uranium surfaces treated with concentrated nitric acid can explode or ignite spontaneously in air.[6] Titanium surfaces treated with nitric acid, particularly red fuming nitric acid, become pyrophoric and may be explosive, and dry titanium fines can ignite spontaneously when dropped through the air in cyclone separators.[21]
Some pyrophoric materials form during processing. In metalworking, Dobbs (2008) lists impact ignition of pyrophoric surface compounds among the ignition sources.[22] Magnesium nitride, which sometimes appears on the surface of castings, can explode under the impulse of a very minor impact.[23] Alkali metals provide further cases. Christman's (2008) solid-metal table lists potassium ignition at 69 °C (156 °F) in oxygen and separately notes spontaneous ignition in moist air; NaK leaks under pressure have also ignited spontaneously.[24][25] Sodium, by contrast, has not been reported to ignite spontaneously at room temperature except in finely divided form.[21]
Pyrophoric gases
Pyrophoric gases are not widely used, and they are most likely to be found in semiconductor manufacturing facilities.[3] There, acids, alkalis, flammable liquids and gases, pyrophoric gases and toxic gases are all common, and pyrophoric gases are among the hazards not widely encountered in other industries.[26][27] The gases may be used pure or mixed with a carrier gas such as hydrogen or nitrogen.[7] Examples named in the handbook are silane, dichlorosilane, diborane and phosphine.[7] Arsine, phosphine and diborane are also highly toxic.[28] At the standard conditions used in Cholin's (2008a) table, silane and phosphine have specific densities of 1.114 and 1.184 relative to air, respectively; gas temperature and jet behaviour also matter when assessing a leak.[29]
The burning behaviour of these gases is not fully understood, mainly because engineering controls have been so successful in preventing uncontrolled releases.[7][8] Experience shows that a leak in an unconfined area, for example outdoors, usually ignites on release and then burns like other flammable gases.[8] Silane, whose use as a source of silicon has grown greatly, is more variable. It can self-ignite with a visible flame on release, but it can also be released with no ignition or with delayed ignition, possibly resulting in a detonation.[8] Released into a confined space such as a gas cabinet, silane has been known to detonate.[8]
DeGiorgio and Peterkin (2008) report that Compressed Gas Association studies of large silane releases led to publication P32-2000, which had by then been revised as G-13, "Storage and Handling of Silane and Silane Mixtures".[8] Its minimum separation distances recognise both the probability of immediate ignition and the probability of latent ignition with explosive effects.[8] The 2006 edition of NFPA 318 added performance-based guidance on gas cabinet ventilation rates for silane, based on FM Global research testing.[30][8]

Storage and handling
The basic rule is to keep pyrophoric materials away from air. Air-reactive chemicals such as aluminium hydride, aluminium alkyls and yellow phosphorus must be stored so that they cannot contact air.[1] Yellow phosphorus is kept under water, and the aluminium alkyls, which react with both water and air, under inert liquids or inert gas.[1] Storage areas for them should contain no incompatible materials.[1] White phosphorus containers should be checked periodically for leaks.[4] Metal powders may need shipment and storage under inert gas or liquid, or a coating, and Christman (2008) recommends bagging in polyethylene under argon inside a metal container where product contamination is not a concern.[17]
Water storage has its own trap. Some metal powders and fines can be stored under water, but at a critical moisture level, particularly with fine powders that begin to dry out, spontaneous combustion may occur.[17] Uranium, thorium and plutonium fines collected under water in containers larger than 3.8 L (1 gal) can ignite, because the water cannot cool the fines at the centre.[6] Limiting the collected quantity to less than 3.8 L has prevented such ignitions.[6] Some pyrophoric materials are also water reactive, so the choice of cover medium depends on the material; a water-reactive material such as an aluminium alkyl needs an inert liquid or gas.[1]
For gases, NFPA 55 (2005 edition), as described by Lemoff and Rivkin (2008), required pyrophoric gas cylinders to be kept 6.10 m (20 ft) from toxic or highly toxic, oxidising and flammable gases.[31] The distance could be reduced without limit by a noncombustible barrier at least 1.52 m (5 ft) high with a fire resistance rating of at least half an hour.[31] The maximum allowable quantity of pyrophoric gas per control area in that edition was zero in unsprinklered areas.[32] In sprinklered areas it was 1.81 kg (4 lb) of liquefied or 1.42 m³ (50 ft³) of nonliquefied gas, and twice these amounts in a gas cabinet, gas room or exhausted enclosure.[32]
Anderson (2008a) describes requirements in laboratories for lecture-bottle-size cylinders of pyrophoric gases to be kept in continuously mechanically ventilated enclosures, and larger cylinders in ventilated gas cabinets with sprinkler protection inside the cabinet.[33] Each compressed gas cylinder should be handled and stored according to procedures of the Compressed Gas Association.[33] DeGiorgio and Peterkin (2008) recommend locating pyrophoric and toxic gases outside semiconductor plants and piping them to cleanrooms in welded stainless steel tubing.[7] They also recommend exhaust gas conditioning for process equipment using high concentrations of pyrophoric gases such as silane, and continuous exhaust-system monitoring to warn of abnormal conditions.[7]
Restricted flow orifices limit how much gas a failure can release. In the NFPA 318 data reproduced by DeGiorgio and Peterkin (2008), orifices of 0.36 mm and 0.25 mm pass 49% and 25% of the silane flow through a 0.51 mm orifice.[8] These factors are close to the ratios of the orifice areas, (0.36/0.51)² = 0.50 and (0.25/0.51)² = 0.24. The same data show the effect of supply pressure: through the 0.25 mm orifice, the flow at 13.8 bar (200 psi) is only about 9% of that at 103.4 bar (1500 psi).[8] Under the table's specified conditions, a smaller orifice and a lower supply pressure therefore lower the silane flow that a ventilated gas cabinet must dilute.[8]
Fire control
Extinguishment does not remove the hazard, because the material can reignite once it is exposed to air again. For white phosphorus, water solidifies the phosphorus melted by the heat of the fire, after which it can be covered with dry sand or dirt.[34] All of the chemical must then be disposed of before it can dry out and reignite.[34] Several air-reactive chemicals, such as the aluminium alkyls, also react particularly violently with water; their fires can be contained by dry chemical while the material burns out under control.[34]
Pyrophoric metals are fought as metal fires. Burning metal must be completely covered with a compatible agent, and portable Class D extinguishers or agents developed for the specific metal can control small fires.[24] Christman (2008) notes that plutonium fines can ignite spontaneously and describes allowing a plutonium fire to burn under conditions that limit both fire and the spread of radiological contamination.[6] NUREG-1805 advises against processing or storing radioactive materials together with other pyrophoric materials where possible, because a fire could spread radioactive contamination widely.[35]
For pyrophoric gases, the handbook places the emphasis on preventing and detecting releases, through engineering controls, continuous monitoring and separation distances.[7][8] A gas that ignites on release burns like other flammable gases, but silane that does not ignite at once can build up and detonate, especially in a confined space.[8] In quantitative risk assessment for process plants, Barry (2002) lists pyrophoric materials among the process ignition exposures, next to chemical reactions and unstable materials.[36]
Limits and common misconceptions
A pyrophoric material does not always ignite at once. Silane may be released with no ignition or delayed ignition.[8] Fine metal particulates show an insidious inconsistency: at times they seemingly cannot be ignited, and at other times the static from a plastic bag or the scuff of a foot ignites them.[24] Christman (2008) warns that a long period of "being lucky" can lead to a false sense of security.[24]
Prompt ignition is not the same as pyrophoricity either. Gaseous hydrogen released at high pressure can be ignited by nominally small heat sources such as friction and static, and Lemoff (2008) notes that it "may be frequently thought of as self-igniting" under these circumstances.[37] Released at low pressure, however, hydrogen is unlikely to self-ignite.[37] Hydrogen appears in the handbook among the common flammable gases, not among the pyrophoric ones.[38][3]
The definitions also differ in scope. The transport definition sets a 5 minute limit for liquids and solids, the NFPA 55 definition applies to gases, and the NUREG-1805 glossary gives only a general description.[2][3][9] Whether a metal behaves pyrophorically depends on particle size, surface treatment and moisture rather than on the element alone.[17][6] The quantities and distances given here are United States rules as presented in the 2008 edition of the Fire Protection Handbook, from NFPA 55 (2005 edition) and NFPA 318 (2006 edition).[32][30]
See also
Notes
- ↑ 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 1.10 Davenport (2008), p. 7-50.
- ↑ 2.0 2.1 2.2 2.3 2.4 2.5 2.6 C. J. Wright (2008a), p. 13-120.
- ↑ 3.0 3.1 3.2 3.3 3.4 3.5 3.6 3.7 Lemoff (2008), p. 6-166.
- ↑ 4.0 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 Davenport (2008), p. 7-51.
- ↑ 5.0 5.1 5.2 Christman (2008), p. 6-160.
- ↑ 6.0 6.1 6.2 6.3 6.4 6.5 6.6 Christman (2008), p. 6-162.
- ↑ 7.0 7.1 7.2 7.3 7.4 7.5 7.6 7.7 DeGiorgio and Peterkin (2008), p. 9-126.
- ↑ 8.00 8.01 8.02 8.03 8.04 8.05 8.06 8.07 8.08 8.09 8.10 8.11 8.12 8.13 DeGiorgio and Peterkin (2008), p. 9-127.
- ↑ 9.0 9.1 Iqbal and Salley (2004), p. F-47.
- ↑ C. J. Wright (2008a), p. 13-119.
- ↑ Iqbal and Salley (2004), p. B-22.
- ↑ Hildebrand and Noll (2008), p. 13-82.
- ↑ Van Rossum (2027), §4.2.
- ↑ 14.0 14.1 Slye (2008), p. 6-201.
- ↑ Rosales and Stoltzfus (2008), p. 9-228.
- ↑ 16.0 16.1 Christman (2008), p. 6-153.
- ↑ 17.0 17.1 17.2 17.3 Christman (2008), p. 6-154.
- ↑ Zalosh (2002), p. 3-404.
- ↑ 19.0 19.1 Benedetti (2008), p. 6-5.
- ↑ Christman (2008), p. 6-161.
- ↑ 21.0 21.1 Christman (2008), p. 6-158.
- ↑ Dobbs (2008), p. 9-67.
- ↑ Dobbs (2008), p. 9-72.
- ↑ 24.0 24.1 24.2 24.3 Christman (2008), p. 6-155.
- ↑ Christman (2008), p. 6-159.
- ↑ DeGiorgio and Peterkin (2008), p. 9-119.
- ↑ DeGiorgio and Peterkin (2008), p. 9-125.
- ↑ DeGiorgio and Peterkin (2008), p. 9-128.
- ↑ Cholin (2008a), p. 14-107.
- ↑ 30.0 30.1 DeGiorgio and Peterkin (2008), p. 9-124.
- ↑ 31.0 31.1 Lemoff and Rivkin (2008), p. 7-38.
- ↑ 32.0 32.1 32.2 Lemoff and Rivkin (2008), p. 7-39.
- ↑ 33.0 33.1 Anderson (2008a), p. 9-165.
- ↑ 34.0 34.1 34.2 Davenport (2008), p. 7-52.
- ↑ Iqbal and Salley (2004), p. B-29.
- ↑ Barry (2002), p. 5-192.
- ↑ 37.0 37.1 Lemoff (2008), p. 6-181.
- ↑ Lemoff (2008), p. 6-174.
References
- Anderson, R. R. (2008a). Fire protection of laboratories using chemicals. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-157–9-166). National Fire Protection Association.
- Barry, T. F. (2002). Quantitative risk assessment in chemical process industries. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 5-176–5-213). National Fire Protection Association; Society of Fire Protection Engineers.
- Benedetti, R. P. (2008). Fire hazards of materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-3–6-9). National Fire Protection Association.
- Cholin, J. M. (2008a). Gas and vapor detection systems and monitors. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 14-99–14-112). National Fire Protection Association.
- Christman, T. (2008). Metals. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-153–6-164). National Fire Protection Association.
- Davenport, J. A. (2008). Storage and handling of chemicals. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-43–7-55). National Fire Protection Association.
- DeGiorgio, V., & Peterkin, H. (2008). Semiconductor manufacturing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-119–9-129). National Fire Protection Association.
- Dobbs, P. G. (2008). Metalworking processes. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-67–9-72). National Fire Protection Association.
- Hildebrand, M. S., & Noll, G. G. (2008). Public fire protection and hazmat management. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 13-81–13-98). National Fire Protection Association.
- Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
- Lemoff, T. C. (2008). Gases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-165–6-186). National Fire Protection Association.
- Lemoff, T. C., & Rivkin, C. H. (2008). Storage of gases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-35–7-42). National Fire Protection Association.
- Rosales, K., & Stoltzfus, J. M. (2008). Oxygen-Enriched atmospheres. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-225–9-243). National Fire Protection Association.
- Slye, O. M., Jr. (2008). Flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-197–6-208). National Fire Protection Association.
- Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.
- Wright, C. J. (2008a). Managing the response to hazardous material incidents. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 13-117–13-144). National Fire Protection Association.
- Zalosh, R. (2002). Explosion protection. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-402–3-421). National Fire Protection Association; Society of Fire Protection Engineers.