  1. 1Properties and classification
  2. 2Flammability and combustion
  3. 3Decomposition and detonation
  4. 4Acetylene cylinders
  5. 5Cylinders exposed to fire
  6. 6Production and use
  7. 7Worked example
  8. 8Limitations and uncertainty
  9. 9See also
  10. 10Notes
  11. 11References

Acetylene (also called ethyne, C2H2) is a colourless flammable gas whose two carbon atoms are joined by a triple bond.[1][2] It is used mainly in chemical processing and as the fuel gas for oxygen–fuel gas welding and cutting.[1] The triple bond is easily broken, which makes acetylene one of the most reactive common gases. It burns in air between 2.5 % and 81 % by volume, can be ignited by sparks of less than 0.02 mJ and has a burning velocity about 3.6 times that of propane.[3][4][5]

Acetylene is also unstable on its own. As a liquid or solid, or as a gas at moderate or high pressure, it can decompose rapidly into carbon and hydrogen without any air.[1] For this reason it is not stored as a simple compressed gas. Cylinders contain a porous mass saturated with acetone or dimethylformamide (DMF), in which the acetylene is dissolved.[1] In the United States, the NFPA 704 marking of acetylene shows a flammability rating of 4, an instability rating of 3 and a health rating of 0.[1] Acetylene cylinders exposed to fire need special precautions, because they can rupture hours after the exposure.[6]

Properties and classification

Each carbon atom of acetylene is bonded to the other by a triple bond and to one hydrogen atom by a single bond.[1] The molar mass is 26.04 g/mol.[7] With a specific gravity of 0.91, the gas is only slightly lighter than air and does not readily dissipate after a release.[3][6] Pure acetylene is odourless. The gas in general use has a characteristic odour from impurities left by its production from calcium carbide or from other hydrocarbons.[1] Acetylene is not toxic, and many years ago it was mixed with oxygen for use as an anaesthetic.[1]

Acetylene is an endothermic compound: forming it from carbon and hydrogen absorbs energy. The SFPE Handbook gives its heat of formation as +226.9 kJ/mol at 25 °C, whereas methane, ethane and propane have negative values.[8] When the molecule decomposes, this energy is released again. Its heat of combustion, measured by bomb calorimetry, is 1255.5 kJ/mol at 25 °C.[2] NUREG-1805 lists 48,220 kJ/kg, which agrees with that value.[9]

In the United States, the handbook classifies acetylene as reactive, flammable, compressed and industrial.[1] Under the transport regulations of the Department of Transportation, it is a Division 2.1 flammable gas.[10] In the 2007 edition of NFPA 704, flammability rating 4 covers materials that turn rapidly or completely into vapour at atmospheric pressure and normal temperature and burn readily.[11] Instability rating 3 covers materials capable of detonation or explosive decomposition that need a strong initiating source or heating under confinement.[11] Acetylene is therefore also an unstable reactive material, although its health rating is 0.[1]

Flammability and combustion

The handbook gives flammability limits of 2.5 % and 81.0 % by volume in air, and an autoignition temperature of 305 °C (581 °F).[3] Lemoff warns that an upper limit of 100 % is sometimes quoted instead. That value signals that a hazardous heat-producing reaction can occur without air, but he calls it a technical misapplication of the concept of flammability limits.[1] The lower limit is also unusual. For most fuels the adiabatic flame temperature at the lower limit is about 1600 K, but for acetylene it is only 1280 K.[12] Beyler interprets a low flame temperature at the lower limit as a sign of high reactivity.[12]

Acetylene ignites very easily. Its minimum ignition energy in dry air at 1 atm and 25 °C is 0.017 mJ, almost the same as hydrogen at 0.016 mJ. Methane needs 0.21 mJ and propane 0.24 mJ.[4] Even a corona discharge, which usually cannot ignite ordinary gases, can ignite acetylene.[13] Reducing the oxygen content of air from 21 % to 10 % prevents fires and explosions of most fuels, but acetylene, hydrogen and carbon disulfide need greater dilution.[14]

Acetylene also burns fast. Its fundamental burning velocity in air is 166 cm/s in the NFPA handbook, against 46 cm/s for propane and 40 cm/s for methane.[5] The SFPE Handbook gives maximum values of 175 cm/s in air and 1120 cm/s in oxygen.[15] In a closed 5-litre test sphere, acetylene reached a maximum explosion pressure of 10.6 bar and a deflagration index of 1415 bar·m/s.[16] Most other gases in the SFPE table lie between 6.8 and 8.1 bar gauge, and propane has an index of 100 bar·m/s.[17]

Lemoff concludes that acetylene is easier to ignite and burns more rapidly than most flammable gases. This makes combustion explosions more severe and explosion venting more difficult.[6]

When acetylene burns in a fire, it produces a very sooty, strongly radiating flame. In Tewarson's data for well-ventilated fires, acetylene has a soot yield of 0.096 g/g, while no soot yield is listed for methane.[18] Of its net heat of complete combustion of 47.8 kJ/g, 36.7 kJ/g is released in the flame and 18.0 kJ/g of that is radiated.[18] That is about half of the heat released, compared with about one-seventh for methane. Acetylene is also considered one of the most likely precursors of soot in flames.[19]

The special hazards of acetylene appear in electrical codes as well. In the United States, electrical equipment for flammable gas atmospheres is grouped by the gap through which a burning gas can pass. Most flammable gases fall in Groups C and D, hydrogen in Group B, and acetylene alone in Group A.[20][21] NUREG-1805 lists the same groups.[22] Group A equipment is limited in variety, so electrical equipment is avoided in areas where acetylene is likely to be released.[6]

Decomposition and detonation

Acetylene can react violently without air. In the liquid or solid state, and as a gas at moderate or high pressure, it can decompose rapidly into carbon and hydrogen, releasing heat.[1] Heat can start this decomposition, and in liquid or solid acetylene mechanical impact can also start it.[1] In a confined space, the hot decomposition gases can raise the pressure until a container, pipe or piece of equipment fails.[1] Schwab names acetylene, with ethylene and nitrous oxide, among the pure gases that decompose violently under pressure.[23]

Because the ease and violence of decomposition rise with pressure, gaseous acetylene in most piping systems is kept stable by limiting the pressure.[1] In general, according to the handbook, this pressure must not exceed 103 kPa (15 psi). Higher pressures, as in cylinder charging plants, need special piping design.[1][6] The use of liquid or solid acetylene is extremely hazardous and is prohibited by the standards and codes for conventional applications.[6]

A second chemical hazard is the formation of metal acetylides. Acetylene reacts with certain metals to form these extremely shock-sensitive explosive compounds. Even a small detonating quantity can initiate decomposition of the acetylene itself.[1] Copper and some copper alloys are the main concern and must be avoided in most acetylene piping and equipment. Brass with less than 65 % copper can be used for piping, and some parts such as torch tips are acceptable under controlled conditions.[1]

In a detonation the flame travels through the unburned mixture at supersonic speed, and the pressure rises almost instantly as a shock wave passes.[24] The SFPE Handbook lists a detonation cell width of 0.98 cm for a stoichiometric acetylene–air mixture, against 1.5 cm for hydrogen and 28 cm for methane.[25] The energy needed to initiate a detonation directly is about 5 kJ for acetylene and hydrogen in air, compared with an estimated 93,000 kJ for methane.[25] The cell width is the length scale of detonability: a detonation can only be sustained where the dimensions of the mixture exceed some multiple of it.[25] The small cell width of acetylene therefore allows detonations in much smaller pipes and spaces than that of methane.

Acetylene cylinders

An acetylene cylinder is a special type of compressed gas cylinder. Lemoff notes that its contents are not all in the gaseous phase, which makes it unique among compressed gases.[1] The cylinder is filled with a porous mass of carbon or carbon-based material with very small pores. Any volume of free gas inside is therefore small, which limits the decomposition energy available and the communication between spaces.[1] The mass is saturated with acetone or DMF, a flammable liquid in which acetylene dissolves readily. When the valve is opened and the pressure falls, the gas comes out of solution and leaves the cylinder as a gas.[1]

The DOT and Transport Canada regulations recognise a maximum charging pressure of 1724 kPa (250 psig) at 21 °C (70 °F).[1] For each atmosphere of pressure, acetone or DMF dissolves about 25 times its own volume of acetylene, so at the charging pressure it holds about 425 volumes.[1] The pressure rises or falls by 2.5 psi for every 1 °F of temperature change, which is about 31 kPa per °C.[1] Cylinders are shipped under DOT and Transport Canada rules, and acetylene is also stored in low-pressure gas holders.[1]

In the United States and Canada, acetylene cylinders are protected against overpressure by fusible metal plugs of low-melting eutectic alloys. These are similar to the alloys of automatic sprinklers and melt at about 100 °C (212 °F).[1][6] When a plug melts, the cylinder empties completely, because the gas and the solvent escape together.[1] An acetylene cylinder is therefore not subject to a boiling liquid expanding vapour explosion (BLEVE), which requires a liquid above its normal boiling point.[1] Internal decomposition during fire exposure or charging has nevertheless caused similar effects, such as rupture and propulsion of cylinders with small fireballs.[1] Most acetylene cylinders in Europe and other parts of the world have no pressure-relief devices and are more susceptible to overpressure and rupture.[6]

Cylinders exposed to fire

If part of an acetylene cylinder is heated above about 299 °C (570 °F), the acetylene begins to decompose into carbon and hydrogen.[6] The decomposition releases large quantities of energy and can be so rapid that the fusible plugs cannot always prevent rupture.[6] Rupture can occur within a few minutes or several hours after the exposure, and cylinders exposed to fire can explode even 24 hours later.[6] The handbook therefore advises spraying such cylinders with water from a protected location and keeping people away from them.[6]

A small leak can escalate in the same way. If it ignites, the small flame can heat the fusible plug, which then releases a torch-like flame up to about 3.66 m (12 ft) long.[6] Manz and Blank describe fires at loosely tightened connections between fuel gas cylinders and regulators. The burning gas can release the fusible plugs of acetylene cylinders, so that more gas escapes and the fire grows.[26] Because quantities in transport and storage are limited, emergencies are rare. Fire control follows the practice for any flammable, nontoxic gas: cool the containers with water and stop the gas flow if possible.[6]

Production and use

Acetylene is made by reacting calcium carbide, a solid, with water, sometimes in generators at the place of use.[1] The same reaction makes carbides a hazard in storage. Calcium, lithium, potassium and barium carbides decompose in water to form acetylene. When water of about one-third the carbide's weight is added, the temperature can rise enough to ignite the gas.[27] Water is therefore not compatible with these materials as an extinguishing agent.[28] In the chemical industry, acetylene is also made by cracking natural gas with partial oxidation and sudden quenching.[29]

The most visible use of acetylene is in oxy-fuel gas cutting and welding. With oxygen, acetylene gives a neutral flame temperature of 3087 °C (5589 °F), against 2927 °C for methylacetylene-propadiene (MPS) and 2526 °C for propane.[30] Acetylene remains the preeminent welding fuel because it has the highest flame temperature of all fuel gases. Other hydrocarbons such as propane and natural gas are not suitable for welding ferrous metals.[30] Air–acetylene torches are also used for brazing and soldering.[31]

The heat flux from an oxyacetylene torch can be about 140 kW/m², much higher than that of the small incidental ignition sources tabulated in the handbook.[32] Systems that carry both oxygen and fuel gas are fitted with backflow prevention devices to stop flammable mixtures forming in containers.[33]

MPS is an alternative fuel gas that has found acceptance for welding and cutting.[30] Its components contain double and triple bonds and are unstable, with hazards and copper reactivity similar to those of acetylene.[34] In the United States, NFPA 51 covers oxygen–fuel gas systems for welding and cutting, and NFPA 51A covers acetylene cylinder charging plants. NFPA 51B covers fire prevention during welding, cutting and other hot work.[35]

Worked example

This example shows how wide the flammable range of acetylene is, compared with that of propane. Complete combustion follows C2H2 + 2.5 O2 → 2 CO2 + H2O.[2] Air contains about 21 % oxygen by volume.[36] Following the molar method of Introduction to Fire Safety Engineering, one mole of acetylene needs 2.5/0.21 = 11.9 moles of air.[37] The stoichiometric volume fraction is therefore 1/(1 + 11.9) = 0.0775, or 7.75 %. The equivalence ratio compares the fuel–air ratio of a mixture with that of the stoichiometric mixture:[38]

ϕ=x(1−xst)xst(1−x)

Symbol Description Unit
ϕ equivalence ratio –
x fuel volume fraction in the mixture –
xst stoichiometric fuel volume fraction –

At the lower limit, x = 0.025 gives φ = 0.31. At the upper limit, x = 0.81 gives φ = 51. For most simple hydrocarbons, the limits lie at about φ = 0.5 and 3.[39] For propane, with limits of 2.15 % and 9.6 % and xst = 0.040, the values are 0.53 and 2.6.[3][38] Acetylene can thus burn in mixtures about fifty times richer than stoichiometric, while propane stops at less than three times.

The energy released by decomposition can be compared with that of combustion. Dividing the heat of formation by the molar mass gives 226.9/26.04 = 8.7 kJ/g. This energy is available without any air.[8][7] The heat of combustion is 1255.5/26.04 = 48.2 kJ/g, so decomposition releases about 18 % of the energy of complete combustion.[2]

The temperature sensitivity of a cylinder can be estimated in the same way. A cylinder charged to 1724 kPa (250 psig) at 21 °C and warmed to 40 °C rises by 19 °C, or 34.2 °F. At 2.5 psi per °F, its pressure rises by about 85 psi, or 590 kPa, to about 2310 kPa gauge.[1] Since susceptibility to decomposition rises with pressure, a warm cylinder is less stable than a cool one.[1]

Limitations and uncertainty

The data in the sources do not always agree. The handbook gives an autoignition temperature of 305 °C, while NUREG-1805 lists an ignition temperature of 755 °C for acetylene.[3][9] The upper flammability limit is given as 81 %, but values of 100 % also appear in the literature.[1] Burning velocities of 166 and 175 cm/s are reported for acetylene–air.[5][15] The handbook gives the temperature effect on cylinder pressure as 2.5 psig per °F and, in metric units, 9 kPa per °C. Conversion of the first value gives about 31 kPa per °C, so the printed metric value appears to be in error.[1]

The deflagration index of 1415 bar·m/s was measured in a 5-litre sphere with a 10 J igniter. The handbook notes that the method for obtaining such values has not been standardised.[16] The requirements described in this article are those of the United States and Canada, as presented in the 2008 Fire Protection Handbook. The handbook notes that practice elsewhere differs, for example in the absence of pressure-relief devices on most European cylinders.[6] Later editions of the American codes, and the rules of other countries, may set different limits.

See also

Notes

  1. ↑ 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 1.10 1.11 1.12 1.13 1.14 1.15 1.16 1.17 1.18 1.19 1.20 1.21 1.22 1.23 1.24 1.25 1.26 1.27 1.28 1.29 1.30 1.31 1.32 1.33 Lemoff (2008), p. 6-177.
  2. ↑ 2.0 2.1 2.2 2.3 Drysdale (2002), p. 1-94.
  3. ↑ 3.0 3.1 3.2 3.3 3.4 Lemoff (2008), p. 6-174, Table 6.10.3.
  4. ↑ 4.0 4.1 Britton (1999), as cited in Ural and Garzia (2008), p. 17-147.
  5. ↑ 5.0 5.1 5.2 Schwab (2008b), p. 18-82, Table 18.6.3.
  6. ↑ 6.00 6.01 6.02 6.03 6.04 6.05 6.06 6.07 6.08 6.09 6.10 6.11 6.12 6.13 6.14 Lemoff (2008), p. 6-178.
  7. ↑ 7.0 7.1 Babrauskas (2008a), p. 6-270.
  8. ↑ 8.0 8.1 Drysdale (2002), p. 1-95.
  9. ↑ 9.0 9.1 Iqbal and Salley (2004), p. 15-10.
  10. ↑ C. J. Wright (2008a), p. 13-119.
  11. ↑ 11.0 11.1 C. J. Wright (2008a), p. 13-123.
  12. ↑ 12.0 12.1 Beyler (2002b), p. 2-177.
  13. ↑ Scarbrough (2008a), pp. 11-65–11-66.
  14. ↑ Yu and Newman (2008), p. 2-88.
  15. ↑ 15.0 15.1 Simmons (2002), p. 1-146.
  16. ↑ 16.0 16.1 Schwab (2008b), p. 18-80, Table 18.6.1.
  17. ↑ Zalosh (2002), p. 3-407.
  18. ↑ 18.0 18.1 Tewarson (2002), p. 3-111, Table 3-4.14.
  19. ↑ Tewarson (2002), p. 3-131.
  20. ↑ Lemoff and Rivkin (2008), p. 7-41.
  21. ↑ Ural and Garzia (2008), p. 17-151.
  22. ↑ Iqbal and Salley (2004), p. B-24.
  23. ↑ Schwab (2008a), p. 8-25.
  24. ↑ Zalosh (2008), p. 2-99.
  25. ↑ 25.0 25.1 25.2 Zalosh (2002), p. 3-412.
  26. ↑ Manz and Blank (2008), p. 9-79.
  27. ↑ Davenport (2008), p. 7-51.
  28. ↑ Yu and Newman (2008), p. 2-91.
  29. ↑ Schwab (2008a), p. 8-24.
  30. ↑ 30.0 30.1 30.2 Manz and Blank (2008), p. 9-76, Table 9.6.1.
  31. ↑ Manz and Blank (2008), p. 9-77.
  32. ↑ Babrauskas (2008b), p. 6-118.
  33. ↑ Lemoff (2008), p. 6-173.
  34. ↑ Lemoff (2008), p. 6-184.
  35. ↑ Lemoff (2008), p. 6-186.
  36. ↑ Van Rossum (2027), §4.2.
  37. ↑ Van Rossum (2027), §3.3.
  38. ↑ 38.0 38.1 Zalosh (2008), p. 2-98.
  39. ↑ Beyler (2002b), p. 2-172.

References

  • Babrauskas, V. (2008a). Tables and charts. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-269–6-294). National Fire Protection Association.
  • Babrauskas, V. (2008b). Upholstered furniture and mattresses. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-103–6-128). National Fire Protection Association.
  • Beyler, C. L. (2002b). Flammability limits of premixed and diffusion flames. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-172–2-187). National Fire Protection Association; Society of Fire Protection Engineers.
  • Davenport, J. A. (2008). Storage and handling of chemicals. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-43–7-55). National Fire Protection Association.
  • Drysdale, D. D. (2002). Thermochemistry. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 1-90–1-98). National Fire Protection Association; Society of Fire Protection Engineers.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Lemoff, T. C. (2008). Gases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-165–6-186). National Fire Protection Association.
  • Lemoff, T. C., & Rivkin, C. H. (2008). Storage of gases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-35–7-42). National Fire Protection Association.
  • Manz, A. F., & Blank, M. E. (2008). Welding, cutting, and other hot work. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-73–9-83). National Fire Protection Association.
  • Scarbrough, D. R. (2008a). Control of electrostatic ignition sources. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-59–11-68). National Fire Protection Association.
  • Schwab, R. F. (2008a). Chemical processing equipment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-17–8-29). National Fire Protection Association.
  • Schwab, R. F. (2008b). Deflagration (explosion) venting. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 18-79–18-88). National Fire Protection Association.
  • Simmons, R. F. (2002). Premixed burning. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 1-144–1-154). National Fire Protection Association; Society of Fire Protection Engineers.
  • Tewarson, A. (2002). Generation of heat and chemical compounds in fires. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-82–3-161). National Fire Protection Association; Society of Fire Protection Engineers.
  • Ural, E. A., & Garzia, H. W. (2008). Explosion prevention and protection. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-141–17-165). National Fire Protection Association.
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.
  • Wright, C. J. (2008a). Managing the response to hazardous material incidents. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 13-117–13-144). National Fire Protection Association.
  • Yu, H.-Z., & Newman, J. S. (2008). Theory of fire extinguishment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-79–2-92). National Fire Protection Association.
  • Zalosh, R. (2002). Explosion protection. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-402–3-421). National Fire Protection Association; Society of Fire Protection Engineers.
  • Zalosh, R. (2008). Explosions. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-93–2-106). National Fire Protection Association.