== Rated containers, vaults and file rooms == | == Rated containers, vaults and file rooms == | ||
Limited quantities of valuable records can be kept in factory-built records protection equipment, tested to UL 72, ''Tests for Fire Resistance of Record Protection Equipment'', of Underwriters Laboratories (UL).<ref name="Beals-9-108" /> This [[Fire resistance test|fire resistance test]] rates equipment by an interior temperature limit and a time. The limits are 177 °C (350 °F) for paper, 66 °C (150 °F) for photographic records and 52 °C (125 °F) for most magnetic media.<ref name="Beals-9-108" /> A rating such as "Class 350, 2 hours" means that the interior limit is not exceeded for 2 hours in the standard test fire.<ref name="Beals-9-108" /> | Limited quantities of valuable records can be kept in factory-built records protection equipment, tested to UL 72, ''Tests for Fire Resistance of Record Protection Equipment'', of Underwriters Laboratories (UL).<ref name="Beals-9-108" /> This [[Fire resistance test|fire resistance test]] rates equipment by an interior temperature limit and a time. The limits are 177 °C (350 °F) for paper, 66 °C (150 °F) for photographic records and 52 °C (125 °F) for most magnetic media.<ref name="Beals-9-108" /> A rating such as "Class 350, 2 hours" means that the interior limit is not exceeded for 2 hours in the standard test fire.<ref name="Beals-9-108" /> | ||
[[File:fse-records-protection-v1.svg|thumb|upright=1.5|alt=Horizontal bar chart of interior temperature limits: 52 °C magnetic media, 66 °C photographic records, 177 °C paper, with a 100 °C steam line|Interior temperature limits of the three UL 72 classes of records protection equipment, with the steam temperature expected inside an insulated safe | [[File:fse-records-protection-v1.svg|thumb|upright=1.5|alt=Horizontal bar chart of interior temperature limits: 52 °C magnetic media, 66 °C photographic records, 177 °C paper, with a 100 °C steam line|Interior temperature limits of the three UL 72 classes of records protection equipment, with the steam temperature expected inside an insulated safe.]] | ||
{| class="wikitable" | {| class="wikitable" | ||
| Line 58: | Line 58: | ||
In NFPA 232, as summarised in the handbook, a vault is a completely fire-resistive enclosure of up to 142 m³ (5,000 ft³), used only for records and with no work inside. Vaults are classified for 4 and 6 hours, are built in the field, and have tested doors that limit their inner face to 177 °C.<ref name="Beals-9-109" /> The contents of some vaults are a greater fire hazard than any outside exposure, and NFPA 232 requires sprinklers in vaults.<ref name="Beals-9-109" /> A standard file room is limited to 1,416 m³ (50,000 ft³) and 3.66 m (12 ft) in height, with walls rated for 2, 4 or 6 hours. Its doors are rated for only ½ or 1 hour, and open-shelf filing inside requires sprinklers.<ref name="Beals-9-109-110">Beals (2008), pp. 9-109–9-110.</ref> | In NFPA 232, as summarised in the handbook, a vault is a completely fire-resistive enclosure of up to 142 m³ (5,000 ft³), used only for records and with no work inside. Vaults are classified for 4 and 6 hours, are built in the field, and have tested doors that limit their inner face to 177 °C.<ref name="Beals-9-109" /> The contents of some vaults are a greater fire hazard than any outside exposure, and NFPA 232 requires sprinklers in vaults.<ref name="Beals-9-109" /> A standard file room is limited to 1,416 m³ (50,000 ft³) and 3.66 m (12 ft) in height, with walls rated for 2, 4 or 6 hours. Its doors are rated for only ½ or 1 hour, and open-shelf filing inside requires sprinklers.<ref name="Beals-9-109-110">Beals (2008), pp. 9-109–9-110.</ref> | ||
[[File:fse-records-protection-v2.svg|thumb|upright=1.5|alt=Nested rectangles: sealed steel can inside a rated container, inside a vault or file room, inside a sprinklered building, with a separate duplicate site|Layers of records protection as described for NFPA 232 (2007) in the Fire Protection Handbook: medium, rated container, vault or file room, building, and a duplicate kept at another site | [[File:fse-records-protection-v2.svg|thumb|upright=1.5|alt=Nested rectangles: sealed steel can inside a rated container, inside a vault or file room, inside a sprinklered building, with a separate duplicate site|Layers of records protection as described for NFPA 232 (2007) in the Fire Protection Handbook: medium, rated container, vault or file room, building, and a duplicate kept at another site.]] | ||
== Fire severity and container selection == | == Fire severity and container selection == | ||
| Line 86: | Line 86: | ||
For the record repository, the equivalent fire load is <math>W'' = 4200 / 18.608 = 226</math> kg/m². This lies between the 4½- and 7-hour rows, so a conservative reading selects the 7-hour row. The table itself assumes a lower heat of combustion of 7,600 Btu/lb (17.7 MJ/kg) in that row, allowing for more paper. With that value the repository gives 238 kg/m², in the same row.<ref name="Davoodi-18-5" /> The office gives 43 kg/m², between ½ and 1 hour, so a conservative reading selects 1 hour.<ref name="Davoodi-18-5" /> | For the record repository, the equivalent fire load is <math>W'' = 4200 / 18.608 = 226</math> kg/m². This lies between the 4½- and 7-hour rows, so a conservative reading selects the 7-hour row. The table itself assumes a lower heat of combustion of 7,600 Btu/lb (17.7 MJ/kg) in that row, allowing for more paper. With that value the repository gives 238 kg/m², in the same row.<ref name="Davoodi-18-5" /> The office gives 43 kg/m², between ½ and 1 hour, so a conservative reading selects 1 hour.<ref name="Davoodi-18-5" /> | ||
[[File:fse-records-protection-v3.svg|thumb|upright=1.5|alt=Step chart of illustrative equivalent fire severity in hours against fire load in kg per square metre, with office, library and record repository markers|Illustrative equivalent fire severity against fire load (Table 18.1.1); the source table covers offices and light commercial occupancies, so the record repository value is not a design rating | [[File:fse-records-protection-v3.svg|thumb|upright=1.5|alt=Step chart of illustrative equivalent fire severity in hours against fire load in kg per square metre, with office, library and record repository markers|Illustrative equivalent fire severity against fire load (Table 18.1.1); the source table covers offices and light commercial occupancies, so the record repository value is not a design rating.]] | ||
This illustrative 7-hour value exceeds the 4-hour rating of modern safes and approaches the handbook's 7 to 15 hours for the burnout of a records storage module.<ref name="Beals-9-111" /><ref name="Beals-9-114">Beals (2008), p. 9-114.</ref> A second IFEG table, from a 1983 compilation by the International Council for Building Research Studies and Documentation (CIB), covers libraries.<ref name="IFEG-3.4-8">National Research Council of Canada et al. (2005), p. 3.4-8.</ref> Its mean of 1,500 MJ/m² and 90 percent fractile of 2,550 MJ/m² give about 2 and 3 hours, respectively.<ref name="Davoodi-18-5" /> The IFEG adds, after the CIB, that a design value should be at least the 95 percent fractile; for libraries the table gives no such value.<ref name="IFEG-3.4-8" /> | This illustrative 7-hour value exceeds the 4-hour rating of modern safes and approaches the handbook's 7 to 15 hours for the burnout of a records storage module.<ref name="Beals-9-111" /><ref name="Beals-9-114">Beals (2008), p. 9-114.</ref> A second IFEG table, from a 1983 compilation by the International Council for Building Research Studies and Documentation (CIB), covers libraries.<ref name="IFEG-3.4-8">National Research Council of Canada et al. (2005), p. 3.4-8.</ref> Its mean of 1,500 MJ/m² and 90 percent fractile of 2,550 MJ/m² give about 2 and 3 hours, respectively.<ref name="Davoodi-18-5" /> The IFEG adds, after the CIB, that a design value should be at least the 95 percent fractile; for libraries the table gives no such value.<ref name="IFEG-3.4-8" /> | ||
| Line 96: | Line 96: | ||
Full-scale tests in December 1974 showed how fast such storage burns. With untreated boxes on 4 m (13 ft) open steel shelves, flames reached the top of the rack in 4½ minutes. Eight seconds later the facing array across the 0.75 m aisle flashed into flame from top to bottom.<ref name="Beals-9-106" /> | Full-scale tests in December 1974 showed how fast such storage burns. With untreated boxes on 4 m (13 ft) open steel shelves, flames reached the top of the rack in 4½ minutes. Eight seconds later the facing array across the 0.75 m aisle flashed into flame from top to bottom.<ref name="Beals-9-106" /> | ||
[[File:fse-records-protection-v4.svg|thumb|upright=1.5|alt=Cross-section of two facing 4 m shelving racks across a 0.75 m aisle with a timeline of flame spread and sprinkler operation|Cross-section of the December 1974 open-shelf test with untreated boxes, with the timeline from a small ignition to the first sprinkler operation | [[File:fse-records-protection-v4.svg|thumb|upright=1.5|alt=Cross-section of two facing 4 m shelving racks across a 0.75 m aisle with a timeline of flame spread and sprinkler operation|Cross-section of the December 1974 open-shelf test with untreated boxes, with the timeline from a small ignition to the first sprinkler operation.]] | ||
The first sprinkler, rated at 141 °C (286 °F), operated after a little more than 5 minutes, when the ceiling above the fire had reached 1,038 °C. The direct cause of the intense fire was the rupture of the cartons, which released paper that exfoliated into the aisle. With unboxed files set perpendicular to the aisle, the fire spread slowly.<ref name="Beals-9-106" /> Because such fires also spread upwards, standard t-squared growth curves, which assume horizontal spread, do not suit high racks.<ref name="VR-8.6">Van Rossum (2027), §8.6.</ref> | The first sprinkler, rated at 141 °C (286 °F), operated after a little more than 5 minutes, when the ceiling above the fire had reached 1,038 °C. The direct cause of the intense fire was the rupture of the cartons, which released paper that exfoliated into the aisle. With unboxed files set perpendicular to the aisle, the fire spread slowly.<ref name="Beals-9-106" /> Because such fires also spread upwards, standard t-squared growth curves, which assume horizontal spread, do not suit high racks.<ref name="VR-8.6">Van Rossum (2027), §8.6.</ref> | ||
Revision as of 08:34, 13 November 2026
Records protection is the set of measures that safeguards valuable records, on paper, film, magnetic or optical media, against fire and its side effects of heat, smoke, steam and water.[1][2] It combines rated containers such as fire-resistant safes and insulated records containers, vaults and file rooms, automatic suppression, fire prevention and duplicates kept at another site.[3] In the United States the main document is NFPA 232, Standard for the Protection of Records, whose 2007 edition is summarised in the 20th edition of the Fire Protection Handbook (2008).[1] Dense open shelving of cardboard boxes can produce a fire that endangers the building itself, while slight overheating can make a high-density data medium unreadable for good.[1][4] Protection is therefore graded by value: irreplaceable vital and archival records justify vaults or rated safes, whereas most other records can be reconstructed and need less.[5] Because most record media are combustible, no method gives complete protection, and the handbook names duplicates stored elsewhere as one of the most effective measures.[6][7]
Value and classification of records
Maximum possible protection is not desirable for the bulk of a collection, because most records can be reconstructed or exist elsewhere. A few irreplaceable documents, in contrast, justify elaborate measures to preserve a single sheet.[5] A protection programme therefore starts with an inventory of the type, volume, rate of acquisition, duplication, rate of disposal and importance of the records. Vital and archival records are irreplaceable, have historic or legal value, are worth more as originals, or are needed to keep a business running. Important records can be reproduced, but only at considerable expense or loss of time. Other records should be kept well apart from both classes, because they could form a fire exposure in themselves.[5]
Four basic items must then be evaluated.[8] The first is the chance that a fire elsewhere in the building spreads to the records, and the second the chance of a fire starting among them. The third is the quantity of fuel the records represent, and the fourth their susceptibility to fire, smoke, water and hose streams.[8] The same reasoning appears in business continuity planning, where a business impact analysis identifies vital records, drawings and electronic data. Their backups should be stored securely off site, with the location, box numbers and retrieval instructions documented.[9][10] For computer systems the stored information is usually worth more than the hardware, so the handbook advises keeping backups in a safe or remote location and testing them regularly.[11]
Damage limits of record media
Ordinary paper survives most fire effects reasonably well, except direct flaming, and burned paper is almost always a total loss. A high recovery rate is practical for records exposed only to water, humidity, smoke and moderately high temperatures of about 177 °C (350 °F).[2] Loose, exfoliated pages burn almost instantly, but packed files burn slowly at the edges.[2] Compact masses of paper such as books resist burning because of charring and limited air inside the mass.[12] The handbook states that virtually any wet paper record can be recovered if prompt and proper action is taken.[2]
Photographic records hold the image in an emulsion that heat, humidity and especially steam can loosen. A traditional insulated safe limits its internal temperature with the water of crystallisation in its insulation and may vent into its interior. Under severe exposure a steam atmosphere of 100 °C (212 °F) or more is expected inside, and tests showed that this damages photographic media.[2] Sealing the film in a steel can with moisture-resistant tape gives a high degree of safety. Magnetic tape is also vulnerable, because even minor distortion of its emulsion is severe when a machine must read it. It is regarded as safeguarded only up to about 52 °C (125 °F) and 85 percent relative humidity.[2]
A records box of paper holds roughly a file drawer of information, whereas an equal volume of CD-ROMs may hold a vault of paper records.[4] Polystyrene reels and cases add a severe hazard of their own, with a high fuel value and heat release rate.[13] Old cellulose nitrate film is a special case. It starts to decompose above 150 °C (300 °F) without needing outside air. In the handbook's US context, NFPA 40 governs its storage in cabinets, vaults, rooms or separate buildings, depending on the quantity.[14]
Rated containers, vaults and file rooms
Limited quantities of valuable records can be kept in factory-built records protection equipment, tested to UL 72, Tests for Fire Resistance of Record Protection Equipment, of Underwriters Laboratories (UL).[2] This fire resistance test rates equipment by an interior temperature limit and a time. The limits are 177 °C (350 °F) for paper, 66 °C (150 °F) for photographic records and 52 °C (125 °F) for most magnetic media.[2] A rating such as "Class 350, 2 hours" means that the interior limit is not exceeded for 2 hours in the standard test fire.[2]
| Equipment | Classes (interior limit) | Rated times | Drop test from 9 m (30 ft) |
|---|---|---|---|
| Insulated records containers | 350 (177 °C), 150 (66 °C), 125 (52 °C) | 1, 2, 3 and 4 h | Yes |
| Fire-resistant safes | 350, 150, 125 | 1, 2, 3 and 4 h | Yes |
| Insulated filing devices | 350, 150, 125 | ½ and 1 h | No |
| Insulated file drawers | 350, 150, 125 | 1 h | Not stated |
Containers and safes must protect their contents after a fall of 9 m (30 ft), and no type may explode when suddenly exposed to high temperature.[16] The 177 °C limit leaves a margin, because most paper ignites somewhat higher. Containers for film and tape are rated for no more than 66 °C, and no more than 85 percent relative humidity above 49 °C, but they are not drop-tested with magnetic media inside.[6] The criterion differs from the fire resistance rating of a wall, which ends when the unexposed side rises 140 °C (250 °F) above its initial temperature.[17] Beals refers to the standard test fire of UL 72 without describing it.[2] The NFPA 251 standard curve for building elements reaches 927 °C (1,700 °F) after 1 hour.[18]
| Container | Approximate fire resistance |
|---|---|
| Insulated records vault doors | 2, 4 and 6 h |
| Insulated file room doors | ½ and 1 h |
| Steel-plate vault doors with inner doors | About 15 min |
| Steel-plate door without inner doors | Less than 10 min |
| Modern safes | 1, 2 and 4 h |
| "Old-line", "iron" or "cast-iron" safes, 51–152 mm (2–6 in.) walls | Uncertain |
| Insulated records containers (files, cabinets) | ½, 1 and 2 h |
| Containers with air space or insulation less than 25 mm (1 in.) | 10 to 20 min |
| Uninsulated steel files and cabinets, wood files, desks | About 5 min |
Uninsulated steel files char their contents quickly in an exposure fire. They remain useful where the main exposure is the records themselves. An ignition even in an open file drawer would likely develop very slowly, whereas a fire in open-shelf files could be beyond manual control within a few minutes. Files and cabinets of wood or fibreboard can release their contents in a fire, and the handbook advises against them for valuable records.[16]
In NFPA 232, as summarised in the handbook, a vault is a completely fire-resistive enclosure of up to 142 m³ (5,000 ft³), used only for records and with no work inside. Vaults are classified for 4 and 6 hours, are built in the field, and have tested doors that limit their inner face to 177 °C.[16] The contents of some vaults are a greater fire hazard than any outside exposure, and NFPA 232 requires sprinklers in vaults.[16] A standard file room is limited to 1,416 m³ (50,000 ft³) and 3.66 m (12 ft) in height, with walls rated for 2, 4 or 6 hours. Its doors are rated for only ½ or 1 hour, and open-shelf filing inside requires sprinklers.[19]
Fire severity and container selection
Vaults are usually chosen where the volume of valuable records is large. They are often the only practical method in non-fire-resistive buildings where the probable fire severity exceeds the endurance of 4-hour safes.[6] The fire load is the energy released if all combustible material burns completely, and it is often used to estimate fire duration.[20] A classic method relates the fire load per unit floor area to an equivalent duration of the standard fire. It goes back to tests at the US National Bureau of Standards with contents representative of office, record room and household occupancies.[21][22]
The method expresses the fire load as an equivalent weight of ordinary combustibles such as wood and paper. Davoodi defines this as the weight of ordinary combustibles with a heat of combustion of 18.608 MJ/kg (8,000 Btu/lb) that releases the same total heat, divided by the floor area.[23]
| Symbol | Description | Unit |
|---|---|---|
| Fire load density (fire load per unit floor area) | MJ/m² | |
| Mass of combustible item | kg | |
| Heat of combustion of item | MJ/kg | |
| Floor area of the fire area | m² | |
| Equivalent fire load in ordinary combustibles | kg/m² | |
| Heat of combustion of ordinary combustibles, 18.608 | MJ/kg |
Table 18.1.1 gives equivalent fire severity: 24 kg/m² corresponds to ½ hour and 49 kg/m² to 1 hour. The 98, 147, 196 and 245 kg/m² rows correspond to 2, 3, 4½ and 7 hours, respectively.[23] For an illustration, the International Fire Engineering Guidelines (IFEG) list variable fire loads from Swiss surveys of 1967–1969.[24] They give 4,200 MJ/m² for a record repository of documents and 800 MJ/m² for a business office.[25]
For the record repository, the equivalent fire load is kg/m². This lies between the 4½- and 7-hour rows, so a conservative reading selects the 7-hour row. The table itself assumes a lower heat of combustion of 7,600 Btu/lb (17.7 MJ/kg) in that row, allowing for more paper. With that value the repository gives 238 kg/m², in the same row.[23] The office gives 43 kg/m², between ½ and 1 hour, so a conservative reading selects 1 hour.[23]
This illustrative 7-hour value exceeds the 4-hour rating of modern safes and approaches the handbook's 7 to 15 hours for the burnout of a records storage module.[6][26] A second IFEG table, from a 1983 compilation by the International Council for Building Research Studies and Documentation (CIB), covers libraries.[27] Its mean of 1,500 MJ/m² and 90 percent fractile of 2,550 MJ/m² give about 2 and 3 hours, respectively.[23] The IFEG adds, after the CIB, that a design value should be at least the 95 percent fractile; for libraries the table gives no such value.[27]
Davoodi calls these fire load concepts technically obsolete, though conservative. His table covers offices and light commercial occupancies in fire-resistive buildings with combustible furniture and shelving.[23] Applying it to a record repository is an illustration, not a design duration or container rating. Lane notes that the approach neglects ventilation, fuel type and fuel geometry.[22] The IFEG values cover contents only, so the comparison omits combustible construction.[24][27]
Bulk storage and records centres
Bulk storage covers any sizable collection not held in vaults, safes or insulated cabinets, from small file rooms to the largest records centres.[28] In open-shelf storage the racks face each other across aisles of about 600 to 750 mm (25 to 30 in.). The aisle presents a wall of box sides and loose paper that a cigarette, portable heater or faulty fluorescent ballast can ignite.[29]
Full-scale tests in December 1974 showed how fast such storage burns. With untreated boxes on 4 m (13 ft) open steel shelves, flames reached the top of the rack in 4½ minutes. Eight seconds later the facing array across the 0.75 m aisle flashed into flame from top to bottom.[29]
The first sprinkler, rated at 141 °C (286 °F), operated after a little more than 5 minutes, when the ceiling above the fire had reached 1,038 °C. The direct cause of the intense fire was the rupture of the cartons, which released paper that exfoliated into the aisle. With unboxed files set perpendicular to the aisle, the fire spread slowly.[29] Because such fires also spread upwards, standard t-squared growth curves, which assume horizontal spread, do not suit high racks.[30]
Archivists were once nervous about water pipes above their records and were offered low-sensitivity 141 °C sprinklers, unlikely to operate accidentally on hot days. Beals reported in 2008 that most accepted sprinklers and showed interest in 68 °C (155 °F) quick-acting sprinklers that might limit damage to 50 boxes or less.[29] In a December 1999 test in 9 m (30 ft) shelving, a single such sprinkler in the shelving controlled a fire whose flames had reached 3.7 m.[29] Mobile shelving, pushed together on tracks, forms tunnels where a burrowing fire is sheltered from sprinkler water. Without internal metal dividers it may spread through the whole array, but overhead sprinklers keep it from jumping to other arrays.[13] In a test for the US National Archives and Records Administration (NARA), ranges parked 127 mm (5 in.) apart under quick-response sprinklers limited the loss to 0.28 m³ of paper.[31]
Larger rooms are records centres. Tests of 4.3 m (14 ft) open shelving indicated ceiling temperatures above 649 °C (1,200 °F) for up to 8 minutes with standard sprinklers, a threat to lightweight bar joist roofs.[5] NFPA 232, as summarised in the handbook, defines a compartmented records centre as one with storage compartments under 3,715 m² (40,000 ft²), separated by at least 2 hours.[5] Caverns have no outside venting and basements are very difficult to ventilate, so a fire beyond sprinkler control may involve all contents.[32] NFPA 75, as summarised in the handbook, requires automated tape libraries in computer rooms to be sprinklered internally.[13] In data centre fire protection, the handbook recommends separating records and paper supplies from the computer room by partitions rated at least 2 hours in ordinary hazard occupancies.[33]
Detection and suppression
All the automatic extinguishing systems that the handbook describes for records are loss-initiated: they act only once a fire is established and some loss has occurred.[34] Automatic sprinklers are the most common type. They limit both fire and water damage, discharge only near the fire and rarely open by accident.[35] A preaction system admits water only after a detector operates, which reduces accidental water damage but adds failure modes.[35] For sprinkler systems protecting important records, another handbook chapter advises considering single- or double-interlock preaction systems.[36]
A smoke detection system with manual response was once favoured by archivists as a full substitute for sprinklers. Beals (2008) regarded it only as a useful supplement, perhaps unsuitable for rapidly developing open-shelf fires.[34] Dungan (2008) described laser-based spot smoke detectors for archives with up to 100 times the sensitivity of LED-based units.[37] In library and museum fire protection, quick-response sprinklers react earlier than standard ones, and the Library of Congress and the US National Archives were installing them in storage areas.[38]
The handbook lists valuable paper records and electronic media storage vaults among the special hazards protected by gaseous agents.[39] A total flooding carbon dioxide system must hold a high concentration until a deep-seated fire has cooled below its ignition temperature.[35] NUREG-1805, written for the fire inspection programme of the US Nuclear Regulatory Commission, summarises the minimum design concentrations of the carbon dioxide standard NFPA 12. Record storage such as bulk paper requires 65 percent by volume, against 34 percent for surface fires in liquids.[40]
These concentrations are lethal, and the report records a bank employee who suffocated in a New York City vault in 2000 after triggering such a system.[41] Halon 1301 inhibits only flaming, so it will not extinguish deep-seated smouldering fires.[35] Such fires are unlikely to be extinguished below 10 percent, and some need more than 18 to 30 percent to put out the glow.[42]
High-expansion foam must fill the whole compartment and keep refilling it, so every item in the area is affected, though only slightly.[35] Where it justifies records centres in caverns or multistorey buildings, the handbook asks for full-scale proof in a 7,100 m³ (250,000 ft³) module. In one successful earlier test, all the box labels slid off onto the floor.[35] The SFPE Handbook lists archives and record centre storage among the hazards for which NFPA standards identify this agent as suitable.[43]
Water mist lowers the water application rate. One manufacturer reportedly tested nozzle pressures below 7 bar for an archive, but sprinklers operate comfortably at 1 bar, so such a system may still need a stronger water supply.[44] For staff use, water extinguishers are preferred, because carbon dioxide, halon and dry chemical units have little effect on deep-seated fires.[34]
Fire experience
In United States office properties in 1999–2002, excluding the events of 11 September 2001, records storage rooms and vaults were the area of origin of about 50 structure fires a year. These were 1 percent of the total and caused 1 civilian injury and US$1 million in direct damage a year.[45] In July 1973 a fire in the unsprinklered, six-storey Military Personnel Records Center in Overland, Missouri, destroyed the top floor and approximately 16–18 million Official Military Personnel Files documenting the service history of former military personnel discharged from 1912 to 1964.[6][46] The 222 m long concrete building had no expansion joints, and about 700 mm of horizontal expansion caused partial collapse.[47]
On 29 October 1996 a sprinklered records archive in Chicago burned for nearly 10 hours before it was under control. Its boxes stood on 8.5 m (28 ft) racks with solid shelves under ceiling sprinklers only. Firefighters held the fire to its 3,250 m² compartment, and early estimates of the loss exceeded US$50 million.[48]
In March 1997 three arson fires struck two adjacent records buildings in South Brunswick, New Jersey. Sprinklers and firefighters controlled the first two, but the third broke through the roof of a building with an estimated 850,000 boxes, and one building was destroyed.[49] In May 1997 a 13 m tall records centre in West Pittston, Pennsylvania, with 12.8 m racks and ceiling-only sprinklers, was a total loss. In 2000, by contrast, sprinklers, firefighters and prepared staff at a NARA records centre limited an arson fire to about 50 lost boxes.[49]
Duplication, planning and misconceptions
Duplicates, often on microfilm, stored away from the originals are one of the most effective safeguards. A duplicate considerably reduces the value of the original, unless the original has legal, intrinsic or historic value.[6] Fire prevention remains the first line of defence, with good housekeeping, maintenance and a ban on smoking. The handbook adds that an emergency plan should be kept current and practised, that records belonging in vaults should never be left out overnight and that copies rather than originals should be loaned.[26] Emergency exits are needed even in secure records facilities, at some cost to security.[1]
The thickness of insulation is no reliable guide to fire resistance, which only tests can establish.[6] A paper-rated safe can fill with steam that ruins film.[2] Burglary ratings measure resistance to attack, for example 2 hours for Class 3 vault doors, and are separate from the fire classes.[50]
Some curators and archivists consider water a greater hazard than fire. Yet the fire in the Los Angeles Central Library in 1986, without automatic suppression, took more than 7 hours to control and destroyed over 400,000 objects.[51] Passive containers do not replace detection and suppression.[52] Nor are sprinklers a guarantee: after Chicago, two other sprinklered records facilities were destroyed with their contents.[49]
See also
Notes
- ↑ 1.0 1.1 1.2 1.3 Beals (2008), p. 9-105.
- ↑ 2.00 2.01 2.02 2.03 2.04 2.05 2.06 2.07 2.08 2.09 2.10 Beals (2008), p. 9-108.
- ↑ Beals (2008), pp. 9-108–9-114.
- ↑ 4.0 4.1 Beals (2008), pp. 9-107–9-108.
- ↑ 5.0 5.1 5.2 5.3 5.4 Beals (2008), p. 9-110.
- ↑ 6.0 6.1 6.2 6.3 6.4 6.5 6.6 6.7 Beals (2008), p. 9-111.
- ↑ Beals (2008), p. 9-117.
- ↑ 8.0 8.1 Beals (2008), pp. 9-110–9-111.
- ↑ Schmidt (2008), p. 1-142.
- ↑ Schmidt (2008), p. 1-148.
- ↑ Rawson (2008), p. 8-60.
- ↑ Cholin (2008c), p. 6-67.
- ↑ 13.0 13.1 13.2 Beals (2008), p. 9-107.
- ↑ Benedetti and Colonna (2008), pp. 6-223–6-224.
- ↑ Beals (2008), pp. 9-108–9-109.
- ↑ 16.0 16.1 16.2 16.3 Beals (2008), p. 9-109.
- ↑ Hirschler (2008a), p. 6-37.
- ↑ Davoodi (2008), p. 18-4.
- ↑ Beals (2008), pp. 9-109–9-110.
- ↑ Van Rossum (2027), §4.4.
- ↑ Davoodi (2008), pp. 18-4–18-5.
- ↑ 22.0 22.1 Lane (2008), pp. 19-80–19-81.
- ↑ 23.0 23.1 23.2 23.3 23.4 23.5 Davoodi (2008), p. 18-5.
- ↑ 24.0 24.1 National Research Council of Canada et al. (2005), p. 3.4-2.
- ↑ National Research Council of Canada et al. (2005), p. 3.4-6.
- ↑ 26.0 26.1 Beals (2008), p. 9-114.
- ↑ 27.0 27.1 27.2 National Research Council of Canada et al. (2005), p. 3.4-8.
- ↑ Beals (2008), pp. 9-105–9-106.
- ↑ 29.0 29.1 29.2 29.3 29.4 Beals (2008), p. 9-106.
- ↑ Van Rossum (2027), §8.6.
- ↑ McDaniel (2008), p. 20-199.
- ↑ Beals (2008), pp. 9-114–9-115.
- ↑ Rawson (2008), p. 8-59.
- ↑ 34.0 34.1 34.2 Beals (2008), p. 9-112.
- ↑ 35.0 35.1 35.2 35.3 35.4 35.5 Beals (2008), p. 9-113.
- ↑ Hague (2008a), p. 16-217.
- ↑ Dungan (2008a), p. 14-22.
- ↑ McDaniel (2008), p. 20-189.
- ↑ Harrington (2008), p. 17-124.
- ↑ Iqbal and Salley (2004), p. B-47.
- ↑ Iqbal and Salley (2004), p. B-50.
- ↑ Grant (1995), as cited in Iqbal and Salley (2004), p. B-46.
- ↑ Scheffey and Hickey (2002), p. 4-124.
- ↑ Mawhinney and Back (2002), p. 4-331.
- ↑ Marburger (2008), p. 20-108.
- ↑ Beals (2008), p. 9-115.
- ↑ Davis (2008b), p. 19-53.
- ↑ Beals (2008), pp. 9-115–9-116.
- ↑ 49.0 49.1 49.2 Beals (2008), p. 9-116.
- ↑ Clary (2008), pp. 14-123–14-124.
- ↑ McDaniel (2008), p. 20-186.
- ↑ McDaniel (2008), p. 20-192.
References
- Beals, J. A. (2008). Protection of records. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-105–9-117). National Fire Protection Association.
- Benedetti, R. P., & Colonna, G. R. (2008). Polymeric materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-209–6-231). National Fire Protection Association.
- Cholin, J. M. (2008c). Wood and wood-based products. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-61–6-74). National Fire Protection Association.
- Clary, S. M. (2008). Security and intrusion detection systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 14-119–14-133). National Fire Protection Association.
- Davis, R. J. (2008b). Structural integrity during fire. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 19-29–19-57). National Fire Protection Association.
- Davoodi, H. (2008). Confinement of fire in buildings. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 18-3–18-21). National Fire Protection Association.
- Dungan, K. W. (2008a). Automatic fire detectors. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 14-15–14-28). National Fire Protection Association.
- Hague, D. R. (2008a). Care and maintenance of water-based extinguishing systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 16-205–16-222). National Fire Protection Association.
- Harrington, J. L. (2008). Application of gaseous agents to special hazards fire protection. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-123–17-139). National Fire Protection Association.
- Hirschler, M. M. (2008a). Concepts and protocols of fire testing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-35–6-60). National Fire Protection Association.
- Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
- Lane, B. (2008). Approaches to calculating structural fire resistance. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 19-77–19-126). National Fire Protection Association.
- Marburger, B. L. (2008). Business occupancies. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-105–20-113). National Fire Protection Association.
- Mawhinney, J. R., & Back, G. G., III. (2002). Water mist fire suppression systems. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 4-311–4-337). National Fire Protection Association; Society of Fire Protection Engineers.
- McDaniel, D. L. (2008). Library and museum collections. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-179–20-202). National Fire Protection Association.
- National Research Council of Canada, International Code Council, Department of Building and Housing, & Australian Building Codes Board. (2005). International fire engineering guidelines (2005 ed.). Australian Building Codes Board.
- Rawson, B. P. (2008). Protection of electronic equipment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-57–8-64). National Fire Protection Association.
- Scheffey, J. L., & Hickey, H. E. (2002). Foam system calculations. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 4-123–4-148). National Fire Protection Association; Society of Fire Protection Engineers.
- Schmidt, D. L. (2008). Emergency management and business continuity. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 1-137–1-156). National Fire Protection Association.
- Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.