Skip to content
From Fire Safety Academy Wiki
Peter (talk | contribs)
Add SVG figures fse-portable-space-heater-v1.svg, fse-portable-space-heater-v2.svg, fse-portable-space-heater-v3.svg, fse-portable-space-heater-v4.svg (list-3 visual plan)
Mark (talk | contribs)
m Remove source references from image captions
 
Line 3: Line 3:
== Types and operating principles ==
== Types and operating principles ==
A room heater is a self-contained appliance that heats the space around it directly, without pipes or ducts, and it is either circulating or radiant.<ref name="GoreWillse-10-23" /> A fuel-burning circulating heater has an outer jacket around the combustion chamber, and room air flows through the gap between the two shells. From a safety point of view, all other room heaters are classed as radiant.<ref name="GoreWillse-10-23" /> The handbook warns that heaters which can be moved easily must be placed so that their radiating surfaces do not face walls, curtains or furniture nearby.<ref name="GoreWillse-10-23" /> In the United States fire reporting system, portability is a separate data field, so a portable space heater is coded as a heater (code 141) with the box "portable" ticked.<ref name="AhrensStewart-3-53">Ahrens and Stewart (2008), p. 3-53.</ref>
A room heater is a self-contained appliance that heats the space around it directly, without pipes or ducts, and it is either circulating or radiant.<ref name="GoreWillse-10-23" /> A fuel-burning circulating heater has an outer jacket around the combustion chamber, and room air flows through the gap between the two shells. From a safety point of view, all other room heaters are classed as radiant.<ref name="GoreWillse-10-23" /> The handbook warns that heaters which can be moved easily must be placed so that their radiating surfaces do not face walls, curtains or furniture nearby.<ref name="GoreWillse-10-23" /> In the United States fire reporting system, portability is a separate data field, so a portable space heater is coded as a heater (code 141) with the box "portable" ticked.<ref name="AhrensStewart-3-53">Ahrens and Stewart (2008), p. 3-53.</ref>
[[File:fse-portable-space-heater-v1.svg|thumb|upright=1.5|alt=Side sections of a circulating heater with air flowing up between two shells and a radiant heater sending heat rays forward|Circulating and radiant room heaters: the circulating type warms air passing between an inner combustion chamber and an outer jacket, the radiant type sends heat directly to surfaces in front of it. Based on Gore Willse (2008a), p. 10-23.]]
[[File:fse-portable-space-heater-v1.svg|thumb|upright=1.5|alt=Side sections of a circulating heater with air flowing up between two shells and a radiant heater sending heat rays forward|Circulating and radiant room heaters: the circulating type warms air passing between an inner combustion chamber and an outer jacket, the radiant type sends heat directly to surfaces in front of it.]]


Electric portable heaters use resistance heating elements: metal alloy wires, nonmetallic carbon rods or printed circuits.<ref name="GoreWillse-10-17">Gore Willse (2008a), p. 10-17.</ref> Kerosene heaters usually have a wick-type burner built into the fuel reservoir.<ref name="GoreWillse-10-25" /> Kerosene is classed with No. 1 and No. 2 fuel oils as a distillate petroleum fuel; safe fuel storage and handling matter for these heaters.<ref name="GoreWillse-10-11">Gore Willse (2008a), p. 10-11.</ref> Self-contained kerosene stoves, also called cabinet heaters or space heaters, have integral tanks of at most 7.6 L (2 gal); they are not considered portable but can be moved rather easily.<ref name="GoreWillse-10-25" /> LP-gas cabinet heaters are portable space heaters supplied from a fuel cylinder.<ref name="LemoffRivkin-7-36" />
Electric portable heaters use resistance heating elements: metal alloy wires, nonmetallic carbon rods or printed circuits.<ref name="GoreWillse-10-17">Gore Willse (2008a), p. 10-17.</ref> Kerosene heaters usually have a wick-type burner built into the fuel reservoir.<ref name="GoreWillse-10-25" /> Kerosene is classed with No. 1 and No. 2 fuel oils as a distillate petroleum fuel; safe fuel storage and handling matter for these heaters.<ref name="GoreWillse-10-11">Gore Willse (2008a), p. 10-11.</ref> Self-contained kerosene stoves, also called cabinet heaters or space heaters, have integral tanks of at most 7.6 L (2 gal); they are not considered portable but can be moved rather easily.<ref name="GoreWillse-10-25" /> LP-gas cabinet heaters are portable space heaters supplied from a fuel cylinder.<ref name="LemoffRivkin-7-36" />
Line 51: Line 51:


The equation applies to thermally thick materials during the transient period before steady state. Its critical heat flux is an extrapolated model parameter, distinct from a measured minimum heat flux for ignition.<ref name="IqbalSalley-6-5" /> Worked example: Douglas fir has a critical heat flux of 10 kW/m² and a thermal response parameter of 138 kW·s<sup>1/2</sup>/m².<ref name="IqbalSalley-6-6">Iqbal and Salley (2004), p. 6-6.</ref> At 20 kW/m², <math>t_\mathrm{ig}</math> = (π/4) × (138 / 10)² ≈ 149 s, or about 2.5 minutes. At 15 kW/m² the calculated time grows to about 600 s, or 10 minutes. Light corrugated paper, with a critical heat flux of 10 kW/m² and a thermal response parameter of 152 kW·s<sup>1/2</sup>/m², ignites after about 3 minutes at 20 kW/m².<ref name="IqbalSalley-6-6" /> Polyurethane foam, by far the dominant padding of upholstered furniture, is listed with an ignition time of 300 s at only 10 kW/m².<ref name="Babrauskas-6-109" /><ref name="IqbalSalley-6-4" />
The equation applies to thermally thick materials during the transient period before steady state. Its critical heat flux is an extrapolated model parameter, distinct from a measured minimum heat flux for ignition.<ref name="IqbalSalley-6-5" /> Worked example: Douglas fir has a critical heat flux of 10 kW/m² and a thermal response parameter of 138 kW·s<sup>1/2</sup>/m².<ref name="IqbalSalley-6-6">Iqbal and Salley (2004), p. 6-6.</ref> At 20 kW/m², <math>t_\mathrm{ig}</math> = (π/4) × (138 / 10)² ≈ 149 s, or about 2.5 minutes. At 15 kW/m² the calculated time grows to about 600 s, or 10 minutes. Light corrugated paper, with a critical heat flux of 10 kW/m² and a thermal response parameter of 152 kW·s<sup>1/2</sup>/m², ignites after about 3 minutes at 20 kW/m².<ref name="IqbalSalley-6-6" /> Polyurethane foam, by far the dominant padding of upholstered furniture, is listed with an ignition time of 300 s at only 10 kW/m².<ref name="Babrauskas-6-109" /><ref name="IqbalSalley-6-4" />
[[File:fse-portable-space-heater-v2.svg|thumb|upright=1.5|alt=Line chart of calculated time to ignition against heat flux for Douglas fir, red oak and light corrugated paper, rising steeply near 10 kW per m²|Calculated time to ignition of three thermally thick materials against incident heat flux (Tewarson method). Based on Iqbal and Salley (2004), pp. 6-5–6-6.]]
[[File:fse-portable-space-heater-v2.svg|thumb|upright=1.5|alt=Line chart of calculated time to ignition against heat flux for Douglas fir, red oak and light corrugated paper, rising steeply near 10 kW per m²|Calculated time to ignition of three thermally thick materials against incident heat flux (Tewarson method).]]


The example shows why the incident flux matters. The 26 kW/m² value is emission from an ideal black surface at 550 °C, not a measured flux from a portable heater. The flux reaching an object depends on the heater's emissivity, size, distance and orientation. Within the transient model, lower incident flux gives a longer calculated ignition time.<ref name="VR-5.4" /><ref name="IqbalSalley-6-5" /> The model ignores long-term chemical change of wood: under prolonged low-level heating wood can ignite at temperatures well below its usual ignition temperature.<ref name="GoreWillse-10-28">Gore Willse (2008a), p. 10-28.</ref>
The example shows why the incident flux matters. The 26 kW/m² value is emission from an ideal black surface at 550 °C, not a measured flux from a portable heater. The flux reaching an object depends on the heater's emissivity, size, distance and orientation. Within the transient model, lower incident flux gives a longer calculated ignition time.<ref name="VR-5.4" /><ref name="IqbalSalley-6-5" /> The model ignores long-term chemical change of wood: under prolonged low-level heating wood can ignite at temperatures well below its usual ignition temperature.<ref name="GoreWillse-10-28">Gore Willse (2008a), p. 10-28.</ref>
Line 75: Line 75:


Worked example: a bedroom heater at the maximum input of 2.93 kW needs <math>V_\mathrm{min}</math> = 4.8 × 2.93 ≈ 14.1 m³, or 14.2 m³ (500 ft³) when calculated in the original units. Assuming a room height of 2.4 m (8 ft) for this illustration, the minimum volume corresponds to a floor area of at least 5.9 m². A bathroom heater at 1.76 kW needs at least 8.5 m³, or about 3.6 m² of floor. The inverse of 4.8 m³/kW is about 0.2 kW/m³ (20 Btu/h per ft³). Separately, the handbook says appliances that normally do not need venting may require it above this aggregate input density.<ref name="GoreWillse-10-41" /> The rule resulted from problems in the southern United States, where old unvented gas heaters, many installed before 1940, could neither be repaired nor replaced under the earlier prohibition.<ref name="GoreWillse-10-41" /> The listing standard requires an oxygen depletion sensor, and wall mounting addresses the concern that heaters in small rooms would be used to dry towels and clothing.<ref name="GoreWillse-10-41" /><ref name="GoreWillse-10-42">Gore Willse (2008a), p. 10-42.</ref>
Worked example: a bedroom heater at the maximum input of 2.93 kW needs <math>V_\mathrm{min}</math> = 4.8 × 2.93 ≈ 14.1 m³, or 14.2 m³ (500 ft³) when calculated in the original units. Assuming a room height of 2.4 m (8 ft) for this illustration, the minimum volume corresponds to a floor area of at least 5.9 m². A bathroom heater at 1.76 kW needs at least 8.5 m³, or about 3.6 m² of floor. The inverse of 4.8 m³/kW is about 0.2 kW/m³ (20 Btu/h per ft³). Separately, the handbook says appliances that normally do not need venting may require it above this aggregate input density.<ref name="GoreWillse-10-41" /> The rule resulted from problems in the southern United States, where old unvented gas heaters, many installed before 1940, could neither be repaired nor replaced under the earlier prohibition.<ref name="GoreWillse-10-41" /> The listing standard requires an oxygen depletion sensor, and wall mounting addresses the concern that heaters in small rooms would be used to dry towels and clothing.<ref name="GoreWillse-10-41" /><ref name="GoreWillse-10-42">Gore Willse (2008a), p. 10-42.</ref>
[[File:fse-portable-space-heater-v4.svg|thumb|upright=1.5|alt=Two room boxes showing minimum volumes of 14.2 cubic metres for a 2.93 kW bedroom heater and 8.5 cubic metres for a 1.76 kW bathroom heater|Minimum room volumes for listed unvented wall-mounted gas heaters under the 1996 National Fuel Gas Code, as summarised in the 2008 handbook. Based on Gore Willse (2008a), p. 10-41.]]
[[File:fse-portable-space-heater-v4.svg|thumb|upright=1.5|alt=Two room boxes showing minimum volumes of 14.2 cubic metres for a 2.93 kW bedroom heater and 8.5 cubic metres for a 1.76 kW bathroom heater|Minimum room volumes for listed unvented wall-mounted gas heaters under the 1996 National Fuel Gas Code, as summarised in the 2008 handbook.]]


== Safety features and rules of use ==
== Safety features and rules of use ==
Line 81: Line 81:


For installed room heaters in large rooms, the 2008 handbook gives standard clearances unless the appliance listing specifies other values. For circulating heaters fired by oil or gas they are 914 mm (36 in.) above, 610 mm (24 in.) in front and 305 mm (12 in.) at the back and sides.<ref name="GoreWillse-10-29">Gore Willse (2008a), p. 10-29.</ref> Radiant gas heaters need 457 mm (18 in.) at the back and sides, or 305 mm (12 in.) at the back with a double metal or ceramic back.<ref name="GoreWillse-10-29" /> Disaster preparedness guidance in the handbook advises ventilation during use, refuelling outdoors and a distance of at least 0.9 m (3 ft) from flammable objects for kerosene heaters.<ref name="Penney-5-40">Penney (2008), p. 5-40.</ref> In New Zealand, the Building Code clauses on prevention of fire occurring are written for fixed appliances using controlled combustion and other fixed equipment.<ref name="MBIE-14">Ministry of Business, Innovation and Employment (2013), p. 14.</ref>
For installed room heaters in large rooms, the 2008 handbook gives standard clearances unless the appliance listing specifies other values. For circulating heaters fired by oil or gas they are 914 mm (36 in.) above, 610 mm (24 in.) in front and 305 mm (12 in.) at the back and sides.<ref name="GoreWillse-10-29">Gore Willse (2008a), p. 10-29.</ref> Radiant gas heaters need 457 mm (18 in.) at the back and sides, or 305 mm (12 in.) at the back with a double metal or ceramic back.<ref name="GoreWillse-10-29" /> Disaster preparedness guidance in the handbook advises ventilation during use, refuelling outdoors and a distance of at least 0.9 m (3 ft) from flammable objects for kerosene heaters.<ref name="Penney-5-40">Penney (2008), p. 5-40.</ref> In New Zealand, the Building Code clauses on prevention of fire occurring are written for fixed appliances using controlled combustion and other fixed equipment.<ref name="MBIE-14">Ministry of Business, Innovation and Employment (2013), p. 14.</ref>
[[File:fse-portable-space-heater-v3.svg|thumb|upright=1.5|alt=Plan and side views of a room heater with dimensioned clearances of 914 mm above, 610 mm in front and 305 mm at back and sides|Standard clearances to combustibles for circulating oil- or gas-fired room heaters in large rooms, unless the listing gives other values. Based on Gore Willse (2008a), p. 10-29.]]
[[File:fse-portable-space-heater-v3.svg|thumb|upright=1.5|alt=Plan and side views of a room heater with dimensioned clearances of 914 mm above, 610 mm in front and 305 mm at back and sides|Standard clearances to combustibles for circulating oil- or gas-fired room heaters in large rooms, unless the listing gives other values.]]


The 2008 handbook advises against installing fuel-burning room heaters in sleeping quarters for transient guests, as in hotels and motels, or in homes for the aged and similar institutions.<ref name="GoreWillse-10-23" /> Statistics alone cannot show which designs of portable electric heater are safer, because the databases do not distinguish between designs; such comparisons need tests and models.<ref name="Hall2002b-5-146">Hall (2002b), p. 5-146.</ref> Fire safety education material can be targeted at the places where portable or fixed space heaters are sold, serviced or maintained.<ref name="Hall-5-114">Hall (2008), p. 5-114.</ref>
The 2008 handbook advises against installing fuel-burning room heaters in sleeping quarters for transient guests, as in hotels and motels, or in homes for the aged and similar institutions.<ref name="GoreWillse-10-23" /> Statistics alone cannot show which designs of portable electric heater are safer, because the databases do not distinguish between designs; such comparisons need tests and models.<ref name="Hall2002b-5-146">Hall (2002b), p. 5-146.</ref> Fire safety education material can be targeted at the places where portable or fixed space heaters are sold, serviced or maintained.<ref name="Hall-5-114">Hall (2008), p. 5-114.</ref>

Latest revision as of 08:33, 13 November 2026

A portable space heater is a self-contained heater that warms the room around it directly and can be moved from place to place, powered by electricity or fuelled by kerosene or liquefied petroleum gas (LP-gas).[1][2][3] In United States homes in 1999–2002, most fires caused by heating equipment involved portable or other space heaters.[4] The main hazard is heat from the heater igniting nearby combustibles such as upholstered furniture, bedding, curtains or clothing.[1][5] Fuelled heaters can be misfuelled or refuelled while hot, and those without a flue can cause carbon monoxide poisoning.[2][6] In United States data for 1995–1999, portable liquid-fuelled heaters had the highest fire death rate per million households of five heater types, while portable electric heaters caused the most deaths.[7] Safety guidance includes tested listings, tip-over protection, ventilation and space between the heater and anything that can burn. Historical rules for unvented gas room heaters also set conditions for small rooms.[2][8]

Types and operating principles

A room heater is a self-contained appliance that heats the space around it directly, without pipes or ducts, and it is either circulating or radiant.[1] A fuel-burning circulating heater has an outer jacket around the combustion chamber, and room air flows through the gap between the two shells. From a safety point of view, all other room heaters are classed as radiant.[1] The handbook warns that heaters which can be moved easily must be placed so that their radiating surfaces do not face walls, curtains or furniture nearby.[1] In the United States fire reporting system, portability is a separate data field, so a portable space heater is coded as a heater (code 141) with the box "portable" ticked.[9]

Side sections of a circulating heater with air flowing up between two shells and a radiant heater sending heat rays forward
Circulating and radiant room heaters: the circulating type warms air passing between an inner combustion chamber and an outer jacket, the radiant type sends heat directly to surfaces in front of it.

Electric portable heaters use resistance heating elements: metal alloy wires, nonmetallic carbon rods or printed circuits.[10] Kerosene heaters usually have a wick-type burner built into the fuel reservoir.[2] Kerosene is classed with No. 1 and No. 2 fuel oils as a distillate petroleum fuel; safe fuel storage and handling matter for these heaters.[11] Self-contained kerosene stoves, also called cabinet heaters or space heaters, have integral tanks of at most 7.6 L (2 gal); they are not considered portable but can be moved rather easily.[2] LP-gas cabinet heaters are portable space heaters supplied from a fuel cylinder.[3]

Portable kerosene heaters are not connected to a chimney. All oil-fired appliances are chimney-connected except direct-fired heaters, listed kerosene stoves and portable kerosene heaters.[12] Gas room heaters may be unvented only when they are listed for unvented use.[1] On construction sites the portable heater is often a salamander. In its crudest form it is a metal drum with holes, burning scrap wood, which presents an acute spark hazard and a carbon monoxide hazard because it has no chimney.[2] Underwriters Laboratories and CSA International test and list portable gas- and oil-fired heaters, including salamanders.[13]

Fire and casualty statistics

Portable heaters are a large part of the heating equipment fire problem. Heating equipment was the second leading cause of United States home fires in 1999–2002, and most of these fires involved portable or other space heaters.[4] Home fires involving portable and space heaters other than solid-fuel stoves rose to a peak in 1983 and then fell steeply until 1998.[14] In 1994–1998 portable space heaters were involved in 850 fires a year caused by electrical failure.[15]

Measured per million households, portable liquid-fuelled heaters such as kerosene heaters had a fire death rate of 9.93–12.41 in 1995–1999, the highest of the five leading heater types.[7] Portable electric heaters followed with 5.95–7.11. In absolute numbers, however, portable electric heaters caused more deaths: about 90, against about 40 for portable liquid-fuelled heaters.[7] Adding non-fire deaths from unvented carbon monoxide raises the rate for portable liquid-fuelled heaters to 12.02–15.02, while the electric rate stays the same.[7] Ratios like these need usage data, such as the number of portable electric heaters in use, and usage studies have indicated significant use of portable electric heaters for primary heating.[16][17]

Portable heaters can ignite upholstered furniture or bedding. Fires starting in these items are dominated by smoking materials, candles, matches and lighters, and radiated heat from nearby equipment such as space heaters.[5] In United States homes in 1999–2002, portable heaters were the equipment involved in about 300 upholstered furniture fires a year, with 28 deaths, and in about 500 mattress or bedding fires, with 18 deaths.[18][19] That is about 93 deaths per 1,000 upholstered furniture fires involving portable heaters, against about 57 for upholstered furniture fires of all causes.

How portable heaters start fires

A space heater is an ignition source by design: fire reporting records it as the equipment involved in ignition whenever it provided the heat, even if it worked as intended.[20] Maintaining clearance to combustibles, whether walls or moveable items such as furniture, bedding and clothing, is a common problem for all portable heating equipment.[21] For portable kerosene heaters the handbook notes that portability increases the hazard.[2] Kerosene stoves that are moved easily can create severe fire and life hazards when they are placed near combustibles or in the path of exits.[2] Some fixed electric heaters are tested for contact with curtains and furniture, but other electric air heaters can be fire hazards when they touch combustible materials or are covered or blocked.[22]

Fuel handling causes a second group of fires. Portable kerosene heaters can be misfuelled, for example with petrol, or refuelled while hot, which can release flammable vapours.[2] The 2008 handbook describes NFPA 31 provisions on oil supply tanks for portable kerosene heaters to prevent contamination with other fuels, which can cause an explosion or flare-up in the heater.[23]

Electric heaters add electrical failure and misuse. Failure to switch off devices such as space heaters when they are no longer needed is a typical lapse.[15] In houses converted to bed-and-breakfast use without electrical upgrades, original wiring might not suit modern appliances such as 900 W space heaters, and too few outlets can lead to extension cords and outlet strips.[24] Where central heating is inadequate, occupants turn to supplemental portable electric, kerosene or fixed space heaters, each with its own hazards.[24] In the southern United States, with milder winters, some households try to heat a whole home with heaters designed only for small spaces.[25]

Radiant heat and time to ignition

Radiated heat is the route by which radiant heaters ignite nearby objects such as upholstered furniture.[5] Radiation dominates heat transfer at high temperatures, from about 400 °C, because the emitted power rises with the fourth power of the absolute temperature; at about 550 °C a surface glows visibly red.[26] The power emitted per square metre of a hot surface is E=εσT4.[26] The part that reaches a target depends on a view factor, set by the size of the radiating surface, the distance and the orientation.[26] A black surface at 550 °C emits σT4 = 5.67 × 10−8 × 8234 ≈ 26 kW/m². That is about 29 times as much as a surface at 82 °C, the handbook's limit for combustibles under long exposure.[27]

Whether a target ignites depends on the heat flux it receives, and the flux needed differs from one material to another.[28] The critical heat flux for ignition is the flux that just raises the surface of the material to its ignition temperature.[28] Within this model, ignition time tends to infinity as the incident flux approaches the critical value from above. For a thermally thick material exposed above that value, NUREG-1805 gives the following equation:[29]

tig=π4(TRPq˙′'e−CHF)2

Symbol Description Unit
tig time to ignition s
TRP thermal response parameter of the material kW·s1/2/m²
q˙′'e external (incident) heat flux kW/m²
CHF critical heat flux for ignition kW/m²
E emitted radiant power per unit area W/m²
ε emissivity (1 for a black surface) –
σ Stefan–Boltzmann constant, 5.67 × 10−8 W/(m²·K4)
T absolute surface temperature K

The equation applies to thermally thick materials during the transient period before steady state. Its critical heat flux is an extrapolated model parameter, distinct from a measured minimum heat flux for ignition.[29] Worked example: Douglas fir has a critical heat flux of 10 kW/m² and a thermal response parameter of 138 kW·s1/2/m².[30] At 20 kW/m², tig = (π/4) × (138 / 10)² ≈ 149 s, or about 2.5 minutes. At 15 kW/m² the calculated time grows to about 600 s, or 10 minutes. Light corrugated paper, with a critical heat flux of 10 kW/m² and a thermal response parameter of 152 kW·s1/2/m², ignites after about 3 minutes at 20 kW/m².[30] Polyurethane foam, by far the dominant padding of upholstered furniture, is listed with an ignition time of 300 s at only 10 kW/m².[18][28]

Line chart of calculated time to ignition against heat flux for Douglas fir, red oak and light corrugated paper, rising steeply near 10 kW per m²
Calculated time to ignition of three thermally thick materials against incident heat flux (Tewarson method).

The example shows why the incident flux matters. The 26 kW/m² value is emission from an ideal black surface at 550 °C, not a measured flux from a portable heater. The flux reaching an object depends on the heater's emissivity, size, distance and orientation. Within the transient model, lower incident flux gives a longer calculated ignition time.[26][29] The model ignores long-term chemical change of wood: under prolonged low-level heating wood can ignite at temperatures well below its usual ignition temperature.[31]

Unvented fuel-burning heaters and carbon monoxide

A fuelled heater without a flue releases its combustion products into the room. Incomplete combustion produces hazardous carbon monoxide when the air supply is inadequate, air and gas are poorly mixed or the temperature is too low.[32] Carbon monoxide is colourless and odourless, and once inhaled it replaces oxygen in the haemoglobin of the blood.[6] The 2008 handbook reported that most United States carbon monoxide deaths occurred in one- and two-family dwellings, generally involving improperly operating heating appliances, insufficient make-up air or blocked, poorly installed or missing vents.[6] For healthy adults, 200 ppm causes a mild headache after 2–3 hours, 800 ppm can cause collapse after 2 hours, and 6,400 ppm brings danger of death within 10–15 minutes.[33] Older people are particularly susceptible, and some victims have died at carboxyhaemoglobin levels below 30 %.[34]

Non-fire carbon monoxide deaths from LP-gas space heaters or furnaces numbered 83 in 1993 and 50 in 2002 in the United States. Deaths from liquid-fuelled devices, mainly oil furnaces and portable kerosene heaters, ranged from 2 to 21 a year in 1993–2002.[35] The 2008 handbook describes listed unvented gas room heaters with an oxygen depletion safety shutoff that closes the gas supply if room oxygen falls below about 18 %.[8] Normal air contains about 21 % oxygen by volume.[36] The same handbook advises against unvented room heaters in institutions such as convalescent homes and orphanages.[8]

The 1996 edition of the National Fuel Gas Code (NFPA 54), as summarised in the 2008 handbook, allowed listed unvented wall-mounted gas heaters in bedrooms and bathrooms under limits.[8] The authority having jurisdiction must approve the installation. The input may not exceed 6,000 Btu/h (1.76 kW) in a bathroom or 10,000 Btu/h (2.93 kW) in a bedroom, and the room must count as an unconfined space.[8] An unconfined space has at least 1.42 m³ (50 ft³) of volume for each 0.293 kW (1,000 Btu/h) of heater input, which the handbook gives as 4.8 m³ per kW:[8]

Vmin=v⋅Q˙

Symbol Description Unit
Vmin minimum room volume for an unvented heater m³
v required volume per unit input, 4.8 m³/kW
Q˙ heater input rating kW

Worked example: a bedroom heater at the maximum input of 2.93 kW needs Vmin = 4.8 × 2.93 ≈ 14.1 m³, or 14.2 m³ (500 ft³) when calculated in the original units. Assuming a room height of 2.4 m (8 ft) for this illustration, the minimum volume corresponds to a floor area of at least 5.9 m². A bathroom heater at 1.76 kW needs at least 8.5 m³, or about 3.6 m² of floor. The inverse of 4.8 m³/kW is about 0.2 kW/m³ (20 Btu/h per ft³). Separately, the handbook says appliances that normally do not need venting may require it above this aggregate input density.[8] The rule resulted from problems in the southern United States, where old unvented gas heaters, many installed before 1940, could neither be repaired nor replaced under the earlier prohibition.[8] The listing standard requires an oxygen depletion sensor, and wall mounting addresses the concern that heaters in small rooms would be used to dry towels and clothing.[8][37]

Two room boxes showing minimum volumes of 14.2 cubic metres for a 2.93 kW bedroom heater and 8.5 cubic metres for a 1.76 kW bathroom heater
Minimum room volumes for listed unvented wall-mounted gas heaters under the 1996 National Fuel Gas Code, as summarised in the 2008 handbook.

Safety features and rules of use

Many safeguards are built into listed heaters. Listed kerosene stoves include fire protection features that unlisted ones may lack, notably suitable construction materials, primary control valves and drip pans.[2] The safest portable kerosene heaters have special latching devices and sheet-metal trays under the burner to catch oil drips.[2] They should also have a tip-over switch that snuffs the burner if the heater is jostled or tipped.[2] The handbook calls for all electric heating devices to be tested and listed by qualified electrical testing laboratories.[22] The 2008 handbook stated that approved gas space heaters with automatic fuel shutoffs and oxygen depletion alarms were permitted in United States apartments under conditions matching their listing.[38]

For installed room heaters in large rooms, the 2008 handbook gives standard clearances unless the appliance listing specifies other values. For circulating heaters fired by oil or gas they are 914 mm (36 in.) above, 610 mm (24 in.) in front and 305 mm (12 in.) at the back and sides.[39] Radiant gas heaters need 457 mm (18 in.) at the back and sides, or 305 mm (12 in.) at the back with a double metal or ceramic back.[39] Disaster preparedness guidance in the handbook advises ventilation during use, refuelling outdoors and a distance of at least 0.9 m (3 ft) from flammable objects for kerosene heaters.[40] In New Zealand, the Building Code clauses on prevention of fire occurring are written for fixed appliances using controlled combustion and other fixed equipment.[41]

Plan and side views of a room heater with dimensioned clearances of 914 mm above, 610 mm in front and 305 mm at back and sides
Standard clearances to combustibles for circulating oil- or gas-fired room heaters in large rooms, unless the listing gives other values.

The 2008 handbook advises against installing fuel-burning room heaters in sleeping quarters for transient guests, as in hotels and motels, or in homes for the aged and similar institutions.[1] Statistics alone cannot show which designs of portable electric heater are safer, because the databases do not distinguish between designs; such comparisons need tests and models.[42] Fire safety education material can be targeted at the places where portable or fixed space heaters are sold, serviced or maintained.[43]

Workplaces, construction sites and institutions

In industry, portable heaters often point to a local shortcoming of the central heating.[44] In woodworking plants, small portable space heaters present a much higher fire hazard than engineered central heating, and employees often bring them in against local discomfort.[44] The heating plant should be designed to eliminate any need for space heaters, and winter inspections can remove them.[45][44] A housekeeping checklist in the handbook requires portable heaters to have ample horizontal and overhead clearances, to stand on a noncombustible surface and to be secured against tipping.[46] The same checklist states that they must not be used as rubbish burners and that the use of steel drums is prohibited.[46]

Salamanders and other temporary heating devices have caused numerous construction fires with losses of millions of dollars.[47] Davis recommends inspecting them every half hour, attending them constantly in windy weather and securing their LP-gas cylinders against falling.[48] Permanent heating plants or temporary nonfired heat exchangers can often replace them.[48] In repair garages, space heaters are typically not an approved type of heat-producing appliance.[49] Approved appliances there must be separated from areas where petrol or other Class I liquids are dispensed, in another room or at least 2.4 m (8 ft) above the floor.[49] In libraries and museums, space heaters should not be used in combustible collection storage areas.[50]

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 1.4 1.5 1.6 Gore Willse (2008a), p. 10-23.
  2. ↑ 2.00 2.01 2.02 2.03 2.04 2.05 2.06 2.07 2.08 2.09 2.10 2.11 Gore Willse (2008a), p. 10-25.
  3. ↑ 3.0 3.1 Lemoff and Rivkin (2008), p. 7-36.
  4. ↑ 4.0 4.1 Hall and Cote (2008), p. 3-15.
  5. ↑ 5.0 5.1 5.2 Babrauskas (2008b), p. 6-103.
  6. ↑ 6.0 6.1 6.2 Black (2008), p. 14-113.
  7. ↑ 7.0 7.1 7.2 7.3 Hall (2008), p. 5-106.
  8. ↑ 8.0 8.1 8.2 8.3 8.4 8.5 8.6 8.7 8.8 Gore Willse (2008a), p. 10-41.
  9. ↑ Ahrens and Stewart (2008), p. 3-53.
  10. ↑ Gore Willse (2008a), p. 10-17.
  11. ↑ Gore Willse (2008a), p. 10-11.
  12. ↑ Gore Willse (2008a), p. 10-39.
  13. ↑ Gore Willse (2008a), p. 10-26.
  14. ↑ Gore Willse (2008a), p. 10-24.
  15. ↑ 15.0 15.1 Milatovich (2008), p. 8-136.
  16. ↑ Hall and Ahrens (2002), p. 5-65.
  17. ↑ Hall and Ahrens (2002), p. 5-72.
  18. ↑ 18.0 18.1 Babrauskas (2008b), p. 6-109.
  19. ↑ Babrauskas (2008b), p. 6-110.
  20. ↑ Ahrens and Stewart (2008), p. 3-49.
  21. ↑ Lathrop (2008b), p. 20-58.
  22. ↑ 22.0 22.1 Milatovich (2008), p. 8-153.
  23. ↑ Gore Willse (2008a), p. 10-16.
  24. ↑ 24.0 24.1 Anderson (2008b), p. 20-50.
  25. ↑ Gamache (2008), p. 5-72.
  26. ↑ 26.0 26.1 26.2 26.3 Van Rossum (2027), §5.4.
  27. ↑ Gore Willse (2008a), p. 10-31.
  28. ↑ 28.0 28.1 28.2 Iqbal and Salley (2004), p. 6-4.
  29. ↑ 29.0 29.1 29.2 Iqbal and Salley (2004), p. 6-5.
  30. ↑ 30.0 30.1 Iqbal and Salley (2004), p. 6-6.
  31. ↑ Gore Willse (2008a), p. 10-28.
  32. ↑ Gore Willse (2008a), p. 10-9.
  33. ↑ Black (2008), p. 14-114.
  34. ↑ Purser (2002), p. 2-90.
  35. ↑ Hall and Twomey (2008), p. 1-24.
  36. ↑ Van Rossum (2027), §4.2.
  37. ↑ Gore Willse (2008a), p. 10-42.
  38. ↑ Bush (2008), p. 20-47.
  39. ↑ 39.0 39.1 Gore Willse (2008a), p. 10-29.
  40. ↑ Penney (2008), p. 5-40.
  41. ↑ Ministry of Business, Innovation and Employment (2013), p. 14.
  42. ↑ Hall (2002b), p. 5-146.
  43. ↑ Hall (2008), p. 5-114.
  44. ↑ 44.0 44.1 44.2 Cholin (2008d), p. 9-17.
  45. ↑ Cholin (2008d), p. 9-15.
  46. ↑ 46.0 46.1 Mattern (2008b), p. 11-37.
  47. ↑ Davis (2008a), p. 11-52.
  48. ↑ 48.0 48.1 Davis (2008a), p. 11-54.
  49. ↑ 49.0 49.1 Rivkin (2008a), p. 21-33.
  50. ↑ McDaniel (2008), p. 20-185.

References

  • Ahrens, M., & Stewart, S. (2008). Fire data collection and databases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-43–3-59). National Fire Protection Association.
  • Anderson, R. R. (2008b). Lodging or rooming houses. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-49–20-54). National Fire Protection Association.
  • Babrauskas, V. (2008b). Upholstered furniture and mattresses. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-103–6-128). National Fire Protection Association.
  • Black, A. (2008). Carbon monoxide detection in residential occupancies. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 14-113–14-117). National Fire Protection Association.
  • Bush, K. (2008). Apartment buildings. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-37–20-47). National Fire Protection Association.
  • Cholin, J. M. (2008d). Woodworking facilities and processes. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-3–9-25). National Fire Protection Association.
  • Davis, R. J. (2008a). Fire hazards of construction, alteration, and demolition of buildings. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-47–11-58). National Fire Protection Association.
  • Gamache, S. (2008). Reaching high-risk groups. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 5-63–5-85). National Fire Protection Association.
  • Gore Willse, P. J. (2008a). Heating systems and appliances. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 10-9–10-56). National Fire Protection Association.
  • Hall, J. R., Jr. (2002b). Product fire risk. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 5-143–5-152). National Fire Protection Association; Society of Fire Protection Engineers.
  • Hall, J. R., Jr. (2008). Using data for public education planning and decision making. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 5-103–5-118). National Fire Protection Association.
  • Hall, J. R., Jr., & Ahrens, M. J. (2002). Data for engineering analysis. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 5-65–5-78). National Fire Protection Association; Society of Fire Protection Engineers.
  • Hall, J. R., Jr., & Cote, A. E. (2008). An overview of the fire problem and fire protection. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-3–3-30). National Fire Protection Association.
  • Hall, J. R., Jr., & Twomey, E. R. (2008). Challenges to safety in the built environment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 1-3–1-29). National Fire Protection Association.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Lathrop, J. K. (2008b). One- and two-family dwellings. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-55–20-61). National Fire Protection Association.
  • Lemoff, T. C., & Rivkin, C. H. (2008). Storage of gases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-35–7-42). National Fire Protection Association.
  • Mattern, L. J. (2008b). Housekeeping practices. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-27–11-38). National Fire Protection Association.
  • McDaniel, D. L. (2008). Library and museum collections. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-179–20-202). National Fire Protection Association.
  • Milatovich, R. M. (2008). Electrical systems and appliances. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-127–8-173). National Fire Protection Association.
  • Ministry of Business, Innovation and Employment. (2013). Commentary for Building Code clauses C1–C6 and Verification Method C/VM2.
  • Penney, G. (2008). Disaster preparedness education. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 5-29–5-43). National Fire Protection Association.
  • Purser, D. A. (2002). Toxicity assessment of combustion products. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-83–2-171). National Fire Protection Association; Society of Fire Protection Engineers.
  • Rivkin, C. H. (2008a). Automotive and marine service station operations. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-29–21-40). National Fire Protection Association.
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.