== System components ==
== System components ==
An exhaust system consists of the hood over the cooking appliances, the ductwork connecting the hood to the exhaust fan, the fan itself, and all grease filtration and other effluent control devices.<ref name="Demers-10-78" /> Within the system the effluent is treated to remove grease, gases and odours. In some newer recirculating units the contaminants are removed so thoroughly that the air can be returned to the kitchen instead of being discharged outside. Makeup air, also called replacement air, is the outside air brought in to balance the exhaust, so that the exhaust can operate within its design pressure differences. A slight negative pressure in the kitchen is usually desirable, to keep cooking odours from migrating to other spaces.
An exhaust system consists of the hood over the cooking appliances, the ductwork connecting the hood to the exhaust fan, the fan itself, and all grease filtration and other effluent control devices.<ref name="Demers-10-78" /> Within the system the effluent is treated to remove grease, gases and odours. In some newer recirculating units the contaminants are removed so thoroughly that the air can be returned to the kitchen instead of being discharged outside. Makeup air, also called replacement air, is the outside air brought in to balance the exhaust, so that the exhaust can operate within its design pressure differences. A slight negative pressure in the kitchen is usually desirable, to keep cooking odours from migrating to other spaces.
[[File:fse-commercial-kitchen-exhaust-v1.svg|thumb|upright=1.5|alt=Section through a kitchen and roof showing fryer, hood with grease filters, welded grease duct with clearances, and hinged upblast fan|Typical commercial cooking exhaust system with its main fire protection features. Based on Demers (2008b), pp. 10-78–10-85.]]


Hoods come in two main families. A canopy hood overhangs the outer edges of the cooking appliance by at least 152 mm (6 in.) on all open sides and is mounted at least 2 m (6.5 ft) above the floor.<ref name="Demers-10-78" /> If its rear side is closed off by a wall it is a wall canopy; if no side is closed off it is an island canopy. Noncanopy hoods, such as backshelf, high-sidewall and high-velocity hoods, are mounted much closer to the cooking surface. Their front lower lip is usually required to be no more than 0.9 m (3 ft) above it.<ref name="Demers-10-79-80">Demers (2008b), pp. 10-79–10-80.</ref> All of these systems still require fire suppression.
Hoods come in two main families. A canopy hood overhangs the outer edges of the cooking appliance by at least 152 mm (6 in.) on all open sides and is mounted at least 2 m (6.5 ft) above the floor.<ref name="Demers-10-78" /> If its rear side is closed off by a wall it is a wall canopy; if no side is closed off it is an island canopy. Noncanopy hoods, such as backshelf, high-sidewall and high-velocity hoods, are mounted much closer to the cooking surface. Their front lower lip is usually required to be no more than 0.9 m (3 ft) above it.<ref name="Demers-10-79-80">Demers (2008b), pp. 10-79–10-80.</ref> All of these systems still require fire suppression.
[[File:fse-commercial-kitchen-exhaust-v2.svg|thumb|upright=1.5|alt=Side views of a wall canopy, an island canopy and a backshelf hood with overhang and height dimensions|Hood types: wall canopy, island canopy and noncanopy backshelf hood, with the main dimensions. Based on Demers (2008b), pp. 10-78–10-80.]]


A single exhaust duct serves one hood and usually has one fire suppression system for the appliances, hood and ductwork. A manifold system serves several hoods through branch ducts that join a common duct.<ref name="Demers-10-80-81">Demers (2008b), pp. 10-80–10-81.</ref> It typically has a separate suppression system for each hood and branch, and all of them operate together to protect the common duct. The fan is usually an upblast fan on the roof, a utility fan, or less often an in-line fan inside the building. Connections between fans and ducts must be liquidtight at all temperatures, and the flexible connections common in other ventilation systems are not permitted.<ref name="Demers-10-81">Demers (2008b), p. 10-81.</ref>
A single exhaust duct serves one hood and usually has one fire suppression system for the appliances, hood and ductwork. A manifold system serves several hoods through branch ducts that join a common duct.<ref name="Demers-10-80-81">Demers (2008b), pp. 10-80–10-81.</ref> It typically has a separate suppression system for each hood and branch, and all of them operate together to protect the common duct. The fan is usually an upblast fan on the roof, a utility fan, or less often an in-line fan inside the building. Connections between fans and ducts must be liquidtight at all temperatures, and the flexible connections common in other ventilation systems are not permitted.<ref name="Demers-10-81">Demers (2008b), p. 10-81.</ref>
Line 48: Line 50:


As an arithmetic illustration, start with vegetable oil whose original <math>T_\text{AI}</math> is 363 °C.<ref name="Lake-17-25" /> Subtracting Demers' 28 K surface margin gives 335 °C; subtracting the UL 300 33 K grease margin gives 330 °C. Both calculations use the original oil value. Lake reports that the oil's autoignition temperature itself falls by about 28 K after ignition, so neither result can be treated as a fixed safe discharge target. UL 300 tests the actual system for prevention of reignition under its specified time and cooling conditions.<ref name="Lake-17-26" /> Late detection leaves hot surfaces that may reignite after the agent breaks down.<ref name="Demers-10-86" />
As an arithmetic illustration, start with vegetable oil whose original <math>T_\text{AI}</math> is 363 °C.<ref name="Lake-17-25" /> Subtracting Demers' 28 K surface margin gives 335 °C; subtracting the UL 300 33 K grease margin gives 330 °C. Both calculations use the original oil value. Lake reports that the oil's autoignition temperature itself falls by about 28 K after ignition, so neither result can be treated as a fixed safe discharge target. UL 300 tests the actual system for prevention of reignition under its specified time and cooling conditions.<ref name="Lake-17-26" /> Late detection leaves hot surfaces that may reignite after the agent breaks down.<ref name="Demers-10-86" />
[[File:fse-commercial-kitchen-exhaust-v3.svg|thumb|upright=1.5|alt=Temperature chart with original and post-fire oil autoignition values and illustrative 28 and 33 K margins|Original and post-ignition vegetable-oil autoignition temperatures and illustrative cooling margins. Based on Lake (2008), pp. 17-25–17-26, and Demers (2008b), p. 10-86.]]


Detection must therefore be fast, not just reliable. Fusible links or electronic sensors must be rated and placed so that they respond promptly to abnormal effluent temperatures.<ref name="Demers-10-86" /> The longest preburn time for systems listed to UL 300 is 2 minutes, yet links installed behind filters can take much longer to reach their rating. Fire can bypass links for 5 minutes or more, so installing more links than seem necessary is recommended. NFPA 17A requires detectors above each appliance or group of appliances protected by a single nozzle and at the entrance to the duct.<ref name="Lake-17-26" /> A manual pull station near the exit from the room serves as backup, and its listing limits the force needed to 178 N (40 lb).
Detection must therefore be fast, not just reliable. Fusible links or electronic sensors must be rated and placed so that they respond promptly to abnormal effluent temperatures.<ref name="Demers-10-86" /> The longest preburn time for systems listed to UL 300 is 2 minutes, yet links installed behind filters can take much longer to reach their rating. Fire can bypass links for 5 minutes or more, so installing more links than seem necessary is recommended. NFPA 17A requires detectors above each appliance or group of appliances protected by a single nozzle and at the entrance to the duct.<ref name="Lake-17-26" /> A manual pull station near the exit from the room serves as backup, and its listing limits the force needed to 178 N (40 lb).
Line 57: Line 60:
== Dampers, makeup air and operation during a fire ==
== Dampers, makeup air and operation during a fire ==
A [[fire damper]] is sometimes placed in the hood at the duct connection to keep fire out of the ductwork, and its use is controversial.<ref name="Demers-10-84" /> In favour, a damper keeps fire out of substandard ducts, confines a fire to the kitchen floor of a multistorey building and adds safety if the suppression system fails. Against it, a properly designed duct can exhaust the fire and smoke safely.<ref name="Demers-10-84-85">Demers (2008b), pp. 10-84–10-85.</ref> A closed damper backs fire and smoke into the kitchen, where they can spread to grease-coated ceilings and walls and hinder fire fighters. A dirty damper may not close fully, giving a false sense of security. Fire dampers in grease exhaust systems should be installed only in listed hoods at the hood-to-duct connection or as part of a listed grease extraction system.<ref name="Demers-10-89" />
A [[fire damper]] is sometimes placed in the hood at the duct connection to keep fire out of the ductwork, and its use is controversial.<ref name="Demers-10-84" /> In favour, a damper keeps fire out of substandard ducts, confines a fire to the kitchen floor of a multistorey building and adds safety if the suppression system fails. Against it, a properly designed duct can exhaust the fire and smoke safely.<ref name="Demers-10-84-85">Demers (2008b), pp. 10-84–10-85.</ref> A closed damper backs fire and smoke into the kitchen, where they can spread to grease-coated ceilings and walls and hinder fire fighters. A dirty damper may not close fully, giving a false sense of security. Fire dampers in grease exhaust systems should be installed only in listed hoods at the hood-to-duct connection or as part of a listed grease extraction system.<ref name="Demers-10-89" />
[[File:fse-commercial-kitchen-exhaust-v4.svg|thumb|upright=1.5|alt=Two-panel diagram of a hood with an open and a closed fire damper showing where fire and smoke go in each case|Fire damper at the hood-to-duct connection: closed, it keeps fire out of the duct but backs fire and smoke into the kitchen. Based on Demers (2008b), pp. 10-84–10-85 and 10-89.]]


Makeup air needs the same care. Makeup air usually moves faster than the exhaust air and approaches the hood at other angles, and these differences should be neutralised by distance before it reaches the hood.<ref name="Demers-10-88" /> Otherwise it can disturb the capture of the hood, so that grease leaves the hood and enters the room.<ref name="Demers-10-86-87">Demers (2008b), pp. 10-86–10-87.</ref> A growing fire can then follow that grease path out of the hood and spread uncontrollably. Some jurisdictions shut down all supply air in a fire, but Demers considers this not always proper. If the hood captures well and has no damper, keeping the makeup air running gives the hood the air it needs to keep exhausting and to contain the fire and smoke.
Makeup air needs the same care. Makeup air usually moves faster than the exhaust air and approaches the hood at other angles, and these differences should be neutralised by distance before it reaches the hood.<ref name="Demers-10-88" /> Otherwise it can disturb the capture of the hood, so that grease leaves the hood and enters the room.<ref name="Demers-10-86-87">Demers (2008b), pp. 10-86–10-87.</ref> A growing fire can then follow that grease path out of the hood and spread uncontrollably. Some jurisdictions shut down all supply air in a fire, but Demers considers this not always proper. If the hood captures well and has no damper, keeping the makeup air running gives the hood the air it needs to keep exhausting and to contain the fire and smoke.

Revision as of 13:09, 12 November 2026

A commercial kitchen exhaust system is the hood, grease removal devices, ductwork and fan that capture the grease-laden effluent of commercial cooking appliances and carry it out of the building. The system is designed to capture all the cooking effluent within the hood, contain it there and transport it through the duct to the outside.[1] Because grease condenses inside hoods and ducts, the exhaust system can also turn a small fire on a fryer or grill into a serious one. The handbook names early spread into the ventilation equipment as one of the factors in severe fires in commercial cooking.[2]

Fire protection of such systems starts with welded steel ducts that keep a clearance to combustibles and grease filters that are cleaned daily. It adds a fixed extinguishing system in the hood and duct and interlocks that shut off the fuel to the appliances. In the United States the requirements are set out in NFPA 96, the Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations. They are described here as summarised in the 20th edition of the Fire Protection Handbook (2008).[3] The same principles apply to industrial cooking establishments such as bakeries.[1]

System components

An exhaust system consists of the hood over the cooking appliances, the ductwork connecting the hood to the exhaust fan, the fan itself, and all grease filtration and other effluent control devices.[1] Within the system the effluent is treated to remove grease, gases and odours. In some newer recirculating units the contaminants are removed so thoroughly that the air can be returned to the kitchen instead of being discharged outside. Makeup air, also called replacement air, is the outside air brought in to balance the exhaust, so that the exhaust can operate within its design pressure differences. A slight negative pressure in the kitchen is usually desirable, to keep cooking odours from migrating to other spaces.

Section through a kitchen and roof showing fryer, hood with grease filters, welded grease duct with clearances, and hinged upblast fan
Typical commercial cooking exhaust system with its main fire protection features. Based on Demers (2008b), pp. 10-78–10-85.

Hoods come in two main families. A canopy hood overhangs the outer edges of the cooking appliance by at least 152 mm (6 in.) on all open sides and is mounted at least 2 m (6.5 ft) above the floor.[1] If its rear side is closed off by a wall it is a wall canopy; if no side is closed off it is an island canopy. Noncanopy hoods, such as backshelf, high-sidewall and high-velocity hoods, are mounted much closer to the cooking surface. Their front lower lip is usually required to be no more than 0.9 m (3 ft) above it.[4] All of these systems still require fire suppression.

Side views of a wall canopy, an island canopy and a backshelf hood with overhang and height dimensions
Hood types: wall canopy, island canopy and noncanopy backshelf hood, with the main dimensions. Based on Demers (2008b), pp. 10-78–10-80.

A single exhaust duct serves one hood and usually has one fire suppression system for the appliances, hood and ductwork. A manifold system serves several hoods through branch ducts that join a common duct.[5] It typically has a separate suppression system for each hood and branch, and all of them operate together to protect the common duct. The fan is usually an upblast fan on the roof, a utility fan, or less often an in-line fan inside the building. Connections between fans and ducts must be liquidtight at all temperatures, and the flexible connections common in other ventilation systems are not permitted.[6]

Why kitchen exhaust systems catch fire

Grease condenses in the interior of the ducts. These accumulations may be ignited by sparks from the cooking appliance or by a small fire caused by overheated oil or fat in a deep-fat fryer or on a grill.[7] If the duct held no grease, such appliance fires could often be put out before causing appreciable damage. Frying is especially risky because cooking oils and fats are heated nearly to their flash points, so overheating or spilling them on a hot appliance can bring them to their autoignition temperature. Grease is also an energetic fuel: tabulated calorific values give about 41 MJ/kg for grease against 18 MJ/kg for wood.[8]

Control failures start many of these fires. Failed thermostats and high-limit controls that can no longer shut off an appliance cause fires every year through overheating and autoignition of the oil or shortening.[9] The same happens when pots of oil on manually controlled equipment are left unattended. Where the exhaust fan is not interlocked with the appliance, a fire can start in the hood itself, especially over gas appliances, when flue gases overheat the grease deposits to autoignition. Exhaust flows that are adequate to capture the normal effluent will also contain a small, short fire. In a serious, longer grease fire the hot gases expand until they exceed the capacity of the hood, and the fire escapes into the room.

A cooking fire in a restaurant is frequent but usually small. In US eating and drinking establishments in 1994–2005, nearly 5000 cooking equipment fires a year were reported to local fire departments, with losses of US$42 million a year.[2] They made up 44% of the reported fires in these properties but only 23% of the direct property damage. Demers explains the high frequency by four factors. The cooking itself provides an ignition source, grease and residue provide fuel, the air supply is designed to be effective, and mitigation needs constant inspection and maintenance. In 1999–2002, cooking equipment caused an estimated 4500 fires a year in these establishments, 45% of the total, and 51% of the civilian injuries.[10]

The ducts themselves appear in the statistics of fires that start in ducts. In US structures other than homes in 1999–2003, a grease hood or duct exhaust fan was the equipment involved in ignition in about 50 of the 1130 duct fires a year, or 4%.[11] These estimates exclude fires reported as confined fires, so they do not show the full number of hood and duct fires.

Construction of hoods and ducts

The hood has three fire tasks: extract and drain as much grease as possible, contain a fire within itself, and keep adjacent combustible surfaces from igniting by radiant heat.[9] For the duct, two requirements are essential. It must be so solidly welded, or assembled as a listed duct, that a fire inside cannot escape through the duct wall into a hidden combustible space.[12] It must also have enough clearance or protection that radiant heat from an internal fire cannot ignite nearby combustibles.

All seams, joints, penetrations and duct-to-hood connections must be liquidtight at all temperatures and have continuous external welds.[12] Ducts must be at least 1.37 mm (0.054 in., No. 16 MSG) thick in carbon steel or 1.09 mm (0.043 in., No. 18 MSG) in stainless steel. Specially listed grease ducts may use other construction. They are built without dips or traps that could hold grease and are pitched to drain back to the hood or to grease drains. A kitchen exhaust system should have no connection with any other ventilating or exhaust system.[7] It should lead directly outside and be designed for an air velocity of at least 7.6 m/s (1500 ft/min) in any duct, to limit grease deposits.

The typical clearance to combustibles is 457 mm (18 in.), 76 mm (3 in.) to limited-combustible materials and zero to noncombustible materials, unless the combustibles are protected as NFPA 96 allows.[13] The clearance may be achieved by insulation and air gaps, by a noncombustible or fire-rated chase, or simply by distance.[14] Where false ceilings or attics containing unprotected ductwork are used for storage, a wire mesh fence around the duct can keep combustibles at least 457 mm (18 in.) away. In buildings of two or more storeys the riser should be outside or enclosed in approved fireproof material. The handbook's typical arrangement shows cleanout doors no more than 6.1 m (20 ft) apart.[7][15]

The fan must not trap grease but drain it to an external covered metal container of no more than 3.785 L (1 US gallon).[16] It must not discharge towards combustible surfaces or towards operable doors, windows or vents. NFPA 96 requires upblast fans to be hinged so that one person can tilt them back to reach the duct for cleaning, although most mechanical codes do not. Inspection panels in ducts and hoods must seal as well as welded ductwork. A panel that leaks can let burning grease escape and spread fire to hidden areas that are difficult to locate.[14]

Fire suppression and detection

In commercial cooking the fixed fire suppression system is the primary means of fire control, and portable extinguishers are secondary.[16] Untrained workers can make a fire worse by throwing water, milk or other liquids on it, or by using flour or cornstarch instead of baking soda. Dry chemical (sodium bicarbonate) systems were once the most common, but they lack the cooling capability needed to pass UL 300, the US fire test for restaurant extinguishing systems.[17] A wet chemical extinguishing system is now the most common type. Automatic sprinklers are also used, carbon dioxide serves large food production lines, and water mist is a newer option for industrial cooking.

The change came with the cooking medium. The autoignition temperature of most vegetable oils is 363 °C (685 °F), as much as 75 K (135 °F) higher than that of animal fats, and modern appliances keep the oil hot for longer.[18] Vegetable oils also contain fewer fatty acids, so dry chemical agents form a weaker smothering foam through saponification (conversion of the fat into soap). After ignition the oils change, and their ignition temperature becomes about 28 K (50 °F) lower than that of the original oil. The whole volume of oil must therefore be cooled below this lower value to prevent reflash. In the 2008 handbook account, wet chemical agents add the cooling effect of their water base to the smothering foam; the chapter says new commercial cooking systems require wet chemical protection.

The key quantity is the temperature to which surfaces and oil must fall after discharge. Demers states that greasy surfaces must cool at least 28 K (50 °F) below their autoignition temperature if they are not to reignite.[17] For fryers, woks and ranges, the UL 300 tests require the agent to prevent reignition for 20 minutes or until the grease is at least 33 K (60 °F) below its autoignition temperature. Whichever takes longer applies.[19] An illustrative temperature threshold follows from a simple margin, provided the relevant post-fire autoignition temperature is known:

Tmax=TAI−ΔT

Symbol Description Unit
Tmax Illustrative threshold for the selected autoignition temperature and margin °C
TAI Autoignition temperature of the oil or greasy surface °C
ΔT Required cooling margin below the autoignition temperature K

As an arithmetic illustration, start with vegetable oil whose original TAI is 363 °C.[18] Subtracting Demers' 28 K surface margin gives 335 °C; subtracting the UL 300 33 K grease margin gives 330 °C. Both calculations use the original oil value. Lake reports that the oil's autoignition temperature itself falls by about 28 K after ignition, so neither result can be treated as a fixed safe discharge target. UL 300 tests the actual system for prevention of reignition under its specified time and cooling conditions.[19] Late detection leaves hot surfaces that may reignite after the agent breaks down.[17]

Temperature chart with original and post-fire oil autoignition values and illustrative 28 and 33 K margins
Original and post-ignition vegetable-oil autoignition temperatures and illustrative cooling margins. Based on Lake (2008), pp. 17-25–17-26, and Demers (2008b), p. 10-86.

Detection must therefore be fast, not just reliable. Fusible links or electronic sensors must be rated and placed so that they respond promptly to abnormal effluent temperatures.[17] The longest preburn time for systems listed to UL 300 is 2 minutes, yet links installed behind filters can take much longer to reach their rating. Fire can bypass links for 5 minutes or more, so installing more links than seem necessary is recommended. NFPA 17A requires detectors above each appliance or group of appliances protected by a single nozzle and at the entrance to the duct.[19] A manual pull station near the exit from the room serves as backup, and its listing limits the force needed to 178 N (40 lb).

On operation, the system must shut down all sources of fuel and power to the heat-producing equipment under the hood.[19] Gas valves close and a shunt trip breaker de-energises electrical appliances.[19][3] Codes require only this shutdown interlock, but it is also recommended that cooking cannot start unless the suppression system is armed and the exhaust and makeup air fans are running.[20] A kitchen hood and duct suppression system must also be connected to the building fire alarm system so that its operation initiates an alarm.[21]

Wet chemical portable extinguishers are listed for cooking oil fires in commercial fryers.[22] Other agents have limits: monoammonium phosphate dry chemical is not recommended for hot cooking oil because it forms no foam.[23] Where carbon dioxide is used on oils whose autoignition temperature is below their boiling point, the local application must last at least 3 minutes to cool the liquid.[24] The SFPE Handbook adds that local application water mist may be considered for deep-fat fryers.[25]

Dampers, makeup air and operation during a fire

A fire damper is sometimes placed in the hood at the duct connection to keep fire out of the ductwork, and its use is controversial.[12] In favour, a damper keeps fire out of substandard ducts, confines a fire to the kitchen floor of a multistorey building and adds safety if the suppression system fails. Against it, a properly designed duct can exhaust the fire and smoke safely.[26] A closed damper backs fire and smoke into the kitchen, where they can spread to grease-coated ceilings and walls and hinder fire fighters. A dirty damper may not close fully, giving a false sense of security. Fire dampers in grease exhaust systems should be installed only in listed hoods at the hood-to-duct connection or as part of a listed grease extraction system.[3]

Two-panel diagram of a hood with an open and a closed fire damper showing where fire and smoke go in each case
Fire damper at the hood-to-duct connection: closed, it keeps fire out of the duct but backs fire and smoke into the kitchen. Based on Demers (2008b), pp. 10-84–10-85 and 10-89.

Makeup air needs the same care. Makeup air usually moves faster than the exhaust air and approaches the hood at other angles, and these differences should be neutralised by distance before it reaches the hood.[14] Otherwise it can disturb the capture of the hood, so that grease leaves the hood and enters the room.[27] A growing fire can then follow that grease path out of the hood and spread uncontrollably. Some jurisdictions shut down all supply air in a fire, but Demers considers this not always proper. If the hood captures well and has no damper, keeping the makeup air running gives the hood the air it needs to keep exhausting and to contain the fire and smoke.

Guidance on the exhaust fan differs between handbook chapters. Lataille calls automatic shutdown of the fan motor by a heat-sensitive device in the hood "desirable", and recommends manual fan controls near the motor and near the hood.[7] Demers, writing on the same equipment, argues that a properly designed duct system can exhaust a fire out of the building safely.[12] For dampers, Demers notes that much of the debate turns on the condition of the ductwork beyond the hood, including its integrity and clearance to combustibles.[26]

Inspection, cleaning and maintenance

Maintenance is essential to keep the system performing as designed, and much of it is cleaning.[28] Filters should be cleaned at least once a day, and the interior surfaces of the hood, in front of and behind the filters, cleaned to bare metal at least once a week.[28] If the hood surfaces and filters are clean, there is little chance of an appliance fire spreading to the ductwork. The hood must never be operated without filters, and damaged filters must be replaced at once because they cannot stop flame penetration into the hood. Mesh filters are not acceptable.[28][7] Grease containers should hold no more than one busy period's grease and be capped, so that a fire inside would smother itself.[16]

The suppression and control equipment has fixed intervals. Fire detectors should be inspected at least every 6 months and mechanical links changed at least every 6 months. Detection lines should be tested by cutting the terminal link, because hardened grease can jam the cable in its pulley elbows.[17] Mechanical gas valves must be operated every 6 months, and airflows of exhaust and makeup air checked at least once a year.[3][28] Any repositioning or replacement of appliances, even one that only changes the fuel or input rating, requires the authority having jurisdiction to review the suppression system. Menu changes often lead to such changes.[29]

Duct cleaning is a difficult job, and specialist commercial firms are one source of help. Housekeeping guidance warns never to try burning the grease out, even though ducts built to NFPA standards are designed to withstand burnout.[30] Before cleaning, the switches, detection devices and extinguishing system cylinders should be locked out so that neither the fan nor the suppression system operates by accident. Should a fire occur during cleaning, the extinguishing system must then be operated manually. A compound of one part calcium hydroxide and two parts calcium carbonate converts the grease to soap and makes it easier to remove.

Occupancies and examples

Commercial cooking is common in assembly occupancies, educational and health care occupancies, where a fire can expose many people.[2] In an institution, losing the kitchen can force the relocation of residents. The handbook's occupancy chapters refer to NFPA 96 for kitchens in assembly occupancies, where automatic extinguishing systems and proper vapour removal are described as the means to handle the hazard.[10] NFPA 96 covers the ventilation of fixed restaurant cooking equipment, while NFPA 54 covers the installation of gas-fired restaurant appliances.[31]

The World Trade Center towers in New York illustrate an older arrangement. Their restaurant cooking appliances were protected by dry chemical systems, released by a thermal link above the appliance or within the exhaust duct and fitted with manual release.[32] Ventilation and grease extraction systems were installed above the fryers, griddles, ranges, boilers and ovens, and some kitchens also had steam smothering systems.[33] Under the 2008 handbook, dry chemical systems may still protect kitchen equipment that has not changed since the system was installed, but new cooking systems require wet chemical protection.[18]

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 Demers (2008b), p. 10-78.
  2. ↑ 2.0 2.1 2.2 Demers (2008b), p. 10-77.
  3. ↑ 3.0 3.1 3.2 3.3 Demers (2008b), p. 10-89.
  4. ↑ Demers (2008b), pp. 10-79–10-80.
  5. ↑ Demers (2008b), pp. 10-80–10-81.
  6. ↑ Demers (2008b), p. 10-81.
  7. ↑ 7.0 7.1 7.2 7.3 7.4 Lataille (2008), p. 8-8.
  8. ↑ CIB (1983), as cited in National Research Council of Canada et al. (2005), p. 3.3-6.
  9. ↑ 9.0 9.1 Demers (2008b), p. 10-83.
  10. ↑ 10.0 10.1 Miller and Roether (2008), p. 20-90.
  11. ↑ Lataille (2008), p. 8-6.
  12. ↑ 12.0 12.1 12.2 12.3 Demers (2008b), p. 10-84.
  13. ↑ Demers (2008b), p. 10-79.
  14. ↑ 14.0 14.1 14.2 Demers (2008b), p. 10-88.
  15. ↑ Lataille (2008), p. 8-10.
  16. ↑ 16.0 16.1 16.2 Demers (2008b), p. 10-85.
  17. ↑ 17.0 17.1 17.2 17.3 17.4 Demers (2008b), p. 10-86.
  18. ↑ 18.0 18.1 18.2 Lake (2008), p. 17-25.
  19. ↑ 19.0 19.1 19.2 19.3 19.4 Lake (2008), p. 17-26.
  20. ↑ Demers (2008b), p. 10-82.
  21. ↑ Leber (2008), p. 14-45.
  22. ↑ Conroy (2008), p. 17-76.
  23. ↑ Yu and Newman (2008), p. 2-90.
  24. ↑ Wysocki (2008), p. 17-13.
  25. ↑ Mawhinney and Back (2002), p. 4-328.
  26. ↑ 26.0 26.1 Demers (2008b), pp. 10-84–10-85.
  27. ↑ Demers (2008b), pp. 10-86–10-87.
  28. ↑ 28.0 28.1 28.2 28.3 Demers (2008b), p. 10-87.
  29. ↑ Demers (2008b), pp. 10-88–10-89.
  30. ↑ Mattern (2008b), p. 11-32.
  31. ↑ Gore Willse (2008a), p. 10-25.
  32. ↑ Evans et al. (2005), p. 15.
  33. ↑ Hopkins et al. (2005), p. xxxv.

References

  • Conroy, M. T. (2008). Fire extinguisher use and maintenance. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-71–17-92). National Fire Protection Association.
  • Demers, D. P. (2008b). Ventilation of commercial cooking operations. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 10-77–10-89). National Fire Protection Association.
  • Evans, D. D., Peacock, R. D., Kuligowski, E. D., Dols, W. S., & Grosshandler, W. L. (2005). Active fire protection systems (NIST NCSTAR 1-4). National Institute of Standards and Technology.
  • Gore Willse, P. J. (2008a). Heating systems and appliances. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 10-9–10-56). National Fire Protection Association.
  • Hopkins, M., Schoenrock, J., & Budnick, E. (2005). Fire suppression systems (NIST NCSTAR 1-4B). National Institute of Standards and Technology.
  • Lake, J. D. (2008). Chemical extinguishing agents and application systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-17–17-29). National Fire Protection Association.
  • Lataille, J. I. (2008). Air-Moving equipment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-3–8-15). National Fire Protection Association.
  • Leber, F. (2008). Fire alarm system interconnections. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 14-39–14-51). National Fire Protection Association.
  • Mattern, L. J. (2008b). Housekeeping practices. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-27–11-38). National Fire Protection Association.
  • Mawhinney, J. R., & Back, G. G., III. (2002). Water mist fire suppression systems. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 4-311–4-337). National Fire Protection Association; Society of Fire Protection Engineers.
  • Miller, G., & Roether, E. (2008). Assembly occupancies. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-85–20-95). National Fire Protection Association.
  • National Research Council of Canada, International Code Council, Department of Building and Housing, & Australian Building Codes Board. (2005). International fire engineering guidelines (2005 ed.). Australian Building Codes Board.
  • Wysocki, T. J. (2008). Carbon dioxide and application systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-3–17-15). National Fire Protection Association.
  • Yu, H.-Z., & Newman, J. S. (2008). Theory of fire extinguishment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-79–2-92). National Fire Protection Association.