== Definition and types of enclosure ==
== Definition and types of enclosure ==
Scarbrough (2008b) defines a spray booth as a power-ventilated structure used to enclose a spraying operation. In most designs the structure surrounds the spraying, but some leave the spray zone open and surround it with a controlled stream of air drawn into the booth.<ref name="Sc08b-9-29" /> The most common type is the open-face or open-front booth: a box-like structure with one open side. Its air moves either horizontally (cross draft) or vertically downwards (downdraft), depending on the process. Car body lines use a tunnel booth with downdraft ventilation, a floor conveyor along the tunnel and makeup air supplied through ceiling diffusers.<ref name="Sc08b-9-29" />
Scarbrough (2008b) defines a spray booth as a power-ventilated structure used to enclose a spraying operation. In most designs the structure surrounds the spraying, but some leave the spray zone open and surround it with a controlled stream of air drawn into the booth.<ref name="Sc08b-9-29" /> The most common type is the open-face or open-front booth: a box-like structure with one open side. Its air moves either horizontally (cross draft) or vertically downwards (downdraft), depending on the process. Car body lines use a tunnel booth with downdraft ventilation, a floor conveyor along the tunnel and makeup air supplied through ceiling diffusers.<ref name="Sc08b-9-29" />
[[File:fse-spray-booth-v1.svg|thumb|upright=1.5|alt=Four schematic cross-sections: open-front cross-draft booth, open-front downdraft booth, tunnel booth with conveyor, spray room with low exhaust|Common spray enclosures and their airflow.]]


A smaller enclosure, called a limited finishing workstation in NFPA 33, is used in vehicle repair shops and similar premises. It was first developed to control dust from sanding and grinding. Its walls are usually movable curtains, it may not exhaust to the outside, and some units stand on wheels. As described in the 2008 handbook, NFPA 33 permits limited spraying in such a workstation, with at most 3.8 L (1 gal) of material in any 8-hour period.<ref name="Sc08b-9-29" />
A smaller enclosure, called a limited finishing workstation in NFPA 33, is used in vehicle repair shops and similar premises. It was first developed to control dust from sanding and grinding. Its walls are usually movable curtains, it may not exhaust to the outside, and some units stand on wheels. As described in the 2008 handbook, NFPA 33 permits limited spraying in such a workstation, with at most 3.8 L (1 gal) of material in any 8-hour period.<ref name="Sc08b-9-29" />
Line 31: Line 32:


Scarbrough (2008b) distinguishes four types of overspray collector. A baffle maze is a set of staggered flat panels on which particles impact and stick; its efficiency is limited. Dry filters of paper or glass fibre, typically about 508 mm (20 in.) square and 51 mm (2 in.) thick, suit low to intermediate production and are replaced when clogged.<ref name="Sc08b-9-30" />
Scarbrough (2008b) distinguishes four types of overspray collector. A baffle maze is a set of staggered flat panels on which particles impact and stick; its efficiency is limited. Dry filters of paper or glass fibre, typically about 508 mm (20 in.) square and 51 mm (2 in.) thick, suit low to intermediate production and are replaced when clogged.<ref name="Sc08b-9-30" />
[[File:fse-spray-booth-v2.svg|thumb|upright=1.5|alt=Four schematic overspray collectors: staggered baffle panels, dry filter pads, waterfall scrubber and venturi scrubber with water spray in a throat|The four types of overspray collector.]]


Waterfall and cascade scrubbers wash the air with sprays or curtains of water and are used for high-volume work. The venturi scrubber, which drives air and a high-velocity water spray through a narrow throat, is perhaps the most efficient collector.<ref name="Sc08b-9-30" /> Scrubber water needs chemical additives to stop paint clogging the nozzles. Without them, open channels form in the water curtain and carry particles onto the stack lining, the fan blades and the roof.<ref name="Sc08b-9-30" />
Waterfall and cascade scrubbers wash the air with sprays or curtains of water and are used for high-volume work. The venturi scrubber, which drives air and a high-velocity water spray through a narrow throat, is perhaps the most efficient collector.<ref name="Sc08b-9-30" /> Scrubber water needs chemical additives to stop paint clogging the nozzles. Without them, open channels form in the water curtain and carry particles onto the stack lining, the fan blades and the roof.<ref name="Sc08b-9-30" />
Line 43: Line 45:


The standard measure is to bond the fluid and spray system, the workpiece and every conductive object within 3 m (10 ft) of the charged elements, and to ground the bond. People are conductors too. An operator can be grounded by holding the grounded gun with a bare hand, or by wearing conductive-soled shoes on a grounded floor. Walking across sticky paint residue can charge a person like walking on a carpet on a dry day, and the resulting spark can ignite flammable vapour.<ref name="Sc08b-9-34" />
The standard measure is to bond the fluid and spray system, the workpiece and every conductive object within 3 m (10 ft) of the charged elements, and to ground the bond. People are conductors too. An operator can be grounded by holding the grounded gun with a bare hand, or by wearing conductive-soled shoes on a grounded floor. Walking across sticky paint residue can charge a person like walking on a carpet on a dry day, and the resulting spark can ignite flammable vapour.<ref name="Sc08b-9-34" />
[[File:fse-spray-booth-v4.svg|thumb|upright=1.5|alt=Plan of a spray station with gun, hose, pump, pressure pot, conveyor hanger, workpiece and operator all bonded to a common ground, with a 3 m circle|Bonding and grounding in an electrostatic spray installation.]]


Whether a spark ignites a mixture depends on the energy it releases. Corona discharge is generally too weak to ignite gases and vapours. Brush discharges can ignite gases and vapours but not common dusts, while spark and propagating brush discharges can ignite gases, vapours and dusts.<ref name="Sc08a-11-61">Scarbrough (2008a), p. 11-61.</ref> The energy stored on an isolated conductor, which a spark can release, follows from its capacitance and voltage:<ref name="Sc08a-11-61" />
Whether a spark ignites a mixture depends on the energy it releases. Corona discharge is generally too weak to ignite gases and vapours. Brush discharges can ignite gases and vapours but not common dusts, while spark and propagating brush discharges can ignite gases, vapours and dusts.<ref name="Sc08a-11-61">Scarbrough (2008a), p. 11-61.</ref> The energy stored on an isolated conductor, which a spark can release, follows from its capacitance and voltage:<ref name="Sc08a-11-61" />
Line 61: Line 64:


'''Worked example.''' Take a conductor with the capacitance of Zalosh's example, 500 pF, and the vapour ignition energy of 0.25 mJ. The voltage needed is V = √(2 × 0.25 × 10⁻³ J / 500 × 10⁻¹² F) = 1.0 kV. Charged to 10 kV, the same object would store 25 mJ, about 100 times the energy needed. Conversely, a conductor charged to 30 kV, the lower end of the handheld gun range, needs a capacitance of only 0.56 pF to store 0.25 mJ.<ref>Calculation with values from Scarbrough (2008a), p. 11-61; Scarbrough (2008b), p. 9-29; and Zalosh (2002), p. 3-405.</ref>
'''Worked example.''' Take a conductor with the capacitance of Zalosh's example, 500 pF, and the vapour ignition energy of 0.25 mJ. The voltage needed is V = √(2 × 0.25 × 10⁻³ J / 500 × 10⁻¹² F) = 1.0 kV. Charged to 10 kV, the same object would store 25 mJ, about 100 times the energy needed. Conversely, a conductor charged to 30 kV, the lower end of the handheld gun range, needs a capacitance of only 0.56 pF to store 0.25 mJ.<ref>Calculation with values from Scarbrough (2008a), p. 11-61; Scarbrough (2008b), p. 9-29; and Zalosh (2002), p. 3-405.</ref>
[[File:fse-spray-booth-v3.svg|thumb|upright=1.5|alt=Log chart of stored spark energy against voltage for 5, 50 and 500 pF, crossing the 0.25 mJ vapour ignition line at low voltages|Stored energy E = ½CV² on an isolated conductor compared with the ignition energy of hydrocarbon vapour.]]


This explains why bonding cannot be limited to large items, and it matches the handbook's remark that a beverage can, or a painful spark from a fingertip, can ignite hydrocarbon vapour.<ref name="Sc08a-11-61" /> The result holds for a purely capacitive spark and assumes all stored energy reaches the mixture. In reality part of it is lost in heating the electrodes.<ref name="Sc08a-11-61" />
This explains why bonding cannot be limited to large items, and it matches the handbook's remark that a beverage can, or a painful spark from a fingertip, can ignite hydrocarbon vapour.<ref name="Sc08a-11-61" /> The result holds for a purely capacitive spark and assumes all stored energy reaches the mixture. In reality part of it is lost in heating the electrodes.<ref name="Sc08a-11-61" />

Revision as of 09:03, 9 November 2026

A spray booth is a power-ventilated structure that encloses a spraying operation, in which a coating is atomised and applied to workpieces.[1] The coatings used in industrial spray finishing are usually flammable or combustible, are often toxic and are sometimes reactive or unstable, so spray finishing is treated as a hazardous process.[2] Fires in paint spraying areas develop very quickly, have high heat release rates and produce large volumes of toxic smoke.[3]

The booth and its ventilation confine vapour and overspray to the smallest practicable area and exhaust the vapour to the outside.[4][5] Booth and duct are also meant to survive a fire long enough to vent heat and smoke out of the building.[6] Further safeguards are control of ignition sources, including sparks of static electricity, limitation of the fuel present, isolation of the process and a quick means of extinguishing a fire.[3][5] In the United States the subject is governed by NFPA 33, Standard for Spray Application Using Flammable or Combustible Materials, as summarised in the Fire Protection Handbook (2008).[1] The same handbook chapter also covers Powder coating, which uses dry powder instead of liquid coatings and has a different hazard profile.

Definition and types of enclosure

Scarbrough (2008b) defines a spray booth as a power-ventilated structure used to enclose a spraying operation. In most designs the structure surrounds the spraying, but some leave the spray zone open and surround it with a controlled stream of air drawn into the booth.[1] The most common type is the open-face or open-front booth: a box-like structure with one open side. Its air moves either horizontally (cross draft) or vertically downwards (downdraft), depending on the process. Car body lines use a tunnel booth with downdraft ventilation, a floor conveyor along the tunnel and makeup air supplied through ceiling diffusers.[1]

Four schematic cross-sections: open-front cross-draft booth, open-front downdraft booth, tunnel booth with conveyor, spray room with low exhaust
Common spray enclosures and their airflow.

A smaller enclosure, called a limited finishing workstation in NFPA 33, is used in vehicle repair shops and similar premises. It was first developed to control dust from sanding and grinding. Its walls are usually movable curtains, it may not exhaust to the outside, and some units stand on wheels. As described in the 2008 handbook, NFPA 33 permits limited spraying in such a workstation, with at most 3.8 L (1 gal) of material in any 8-hour period.[1]

Some coating machines are engineered enclosures in their own right. In a continuous coater an array of guns coats workpieces passing at 30 to 183 m/min (100 to 600 ft/min). The interior is not exhausted; exhaust shrouds at the entry and exit vestibules capture vapour and drifting overspray, and most overspray is recycled from a sump.[7] Decorating machines, which paint stripes through masks, are totally enclosed and exhausted through internal filters, which strongly reduces the risk of escaping vapour.[4]

Where workpieces are too large for a booth, a whole room may be dedicated to spraying. Such a spray room is classified as a hazardous area. Its ventilation removes vapour but is too slow to capture particles, so overspray settles on the floor as combustible residue. Vapour removal works best with the exhaust intake along one wall within 300 mm (1 ft) of the floor and makeup air entering along the opposite wall.[4]

Spraying without a booth and without a partition from other work is called open-floor spraying. Ventilation must then still prevent flammable vapour concentrations. A buffer zone with a radius of about 6 m (20 ft) around the spray area is common practice.[4]

Spraying is one of several finishing processes that apply flammable coatings. In a Dip tank the workpiece is immersed in the liquid instead of being sprayed; the handbook treats dipping in the next chapter and cross-refers the two.[8] In the United States the electrical hazardous location rules apply to both spraying and dipping of flammable finishes.[9]

Atomisation and coating supply

Spraying turns a liquid coating into a fine mist. A liquid fuel normally has to become a gas or a mist of droplets before it can burn.[10] Mists of flammable and combustible liquids can be ignited by static sparks much like dusts, even below the flash point of the liquid.[11] For very small droplets of a fuel that evaporates completely, the lower flammable limit is about that of the vapour; for larger droplets it is expected to be higher.[12]

The most familiar device is the air spray gun, in which jets of high-pressure air break the fluid into a fine mist. The high-volume, low-pressure (HVLP) gun produces a coarser spray with less fine mist. Airless atomisers spray the fluid hydraulically at 2.07 MPa (300 psi) to about 48 MPa (7000 psi).[3] Both types are also built into electrostatic guns, whose charging electrode runs at roughly 35 kV to somewhat over 100 kV. The charged droplets are attracted to the grounded workpiece, so electrostatic spraying produces less overspray.[13]

Rotating atomisers use a sharp-edged disc of 150 to 300 mm (6 to 12 in.) charged to about 100 kV. A variant is the bell of 50 to 76 mm (2 to 3 in.), which can spin at close to 60,000 rpm and is often mounted in banks of 6 to 12.[14] The voltage at the atomiser is 30 to 75 kV for handheld electrostatic guns and 30 to 120 kV for automatic guns. To prevent sparking on accidental contact with a grounded object, the cable usually ends at the gun in a resistance of about 75 to 250 MΩ. Some automatic guns lack this termination and rely on keeping a fixed distance from the workpiece. Discs store considerable energy at 50 to 120 kV and must also be kept far enough from the workpiece.[1]

Coating fluid comes from cups on the gun, from pressure pots of 2 to 227 L (1/2 to 60 gal), or by pump from a bulk tank. Fluid pressures of 21 to 517 kPa (3 to 75 psig) are customary. Solvent is often added shortly before spraying to adjust viscosity, and a safety container reduces the chance of spilling the blend.[14] Waterborne coatings are a special case. Many have a flash point but no fire point and do not sustain a flame, yet their dried residues are combustible. The handbook names the sustained-burning test of ASTM D4206 as a useful check; a coating that supports flame should be treated as a flammable liquid.[3]

Ventilation and overspray collection

Booth ventilation has two tasks. It removes solvent vapour so that flammable concentrations cannot build up, and it captures overspray so that the residue stays in the booth and its collector.[15][4] The vapour concentrations that matter are set by the flammable limits of the solvent. These are the composition limits within which a flame can propagate; methane, for example, burns in air between 5 and 15 percent by volume.[16]

In wood finishing, Cholin (2008d) calls booths built to NFPA 33 with adequate mechanical ventilation the ideal way to discharge vapour to a safe location. The airflow should keep a sufficient average velocity over the whole open face to confine overspray inside the booth. Large booths in that industry exhaust more than 708 m³/min (25,000 cfm), so the makeup air supply needs careful management.[15] Fan, collector and duct together form an Industrial exhaust system that discharges the vapour outdoors.[4] The ventilation should be checked often to confirm that the specified flow rates are maintained.[5]

Scarbrough (2008b) distinguishes four types of overspray collector. A baffle maze is a set of staggered flat panels on which particles impact and stick; its efficiency is limited. Dry filters of paper or glass fibre, typically about 508 mm (20 in.) square and 51 mm (2 in.) thick, suit low to intermediate production and are replaced when clogged.[4]

Four schematic overspray collectors: staggered baffle panels, dry filter pads, waterfall scrubber and venturi scrubber with water spray in a throat
The four types of overspray collector.

Waterfall and cascade scrubbers wash the air with sprays or curtains of water and are used for high-volume work. The venturi scrubber, which drives air and a high-velocity water spray through a narrow throat, is perhaps the most efficient collector.[4] Scrubber water needs chemical additives to stop paint clogging the nozzles. Without them, open channels form in the water curtain and carry particles onto the stack lining, the fan blades and the roof.[4]

Ignition sources and electrical classification

Ignition sources in and near a booth are controlled by area. In the United States, the National Electrical Code (NFPA 70) defines Division 1 and Division 2 areas, from which all ignition sources should be barred or in which they should be controlled.[5] The code's rules apply wherever flammable finishes are regularly applied by spraying or dipping, or where readily ignitable residues may occur. The classified areas for these processes are defined in Article 516 of the code.[9] The general method is described under Hazardous area classification.

In Division 1 and Division 2 areas, open flames, spark-producing equipment and surfaces hotter than the ignition temperature of the sprayed material should be prohibited. Only wiring and devices listed for the location should be used. Light fittings above a classified area should be totally enclosed or guarded so that hot particles cannot fall into it. Exhaust fans should be non-sparking and meet Class C of the Air Movement and Control Association (AMCA). Careless smoking and poorly supervised welding or cutting are major threats, so a hot work permit system and a smoking ban are expected.[5]

Static electricity and spark energy

Static electricity remains a common cause of vapour ignition in electrostatic spray finishing. Energised electrodes send large amounts of charge into the air, which collects on nearby surfaces and can raise them to a high voltage. Interlocks should therefore switch off the high-voltage supply whenever the guns are not spraying. Most modern electrostatic guns listed for flammable coatings limit the energy of a discharge arc to below the ignition level. Ordinary air and airless guns also generate charge, so apparatus and sprayed object must be bonded and grounded as well.[5]

The standard measure is to bond the fluid and spray system, the workpiece and every conductive object within 3 m (10 ft) of the charged elements, and to ground the bond. People are conductors too. An operator can be grounded by holding the grounded gun with a bare hand, or by wearing conductive-soled shoes on a grounded floor. Walking across sticky paint residue can charge a person like walking on a carpet on a dry day, and the resulting spark can ignite flammable vapour.[5]

Plan of a spray station with gun, hose, pump, pressure pot, conveyor hanger, workpiece and operator all bonded to a common ground, with a 3 m circle
Bonding and grounding in an electrostatic spray installation.

Whether a spark ignites a mixture depends on the energy it releases. Corona discharge is generally too weak to ignite gases and vapours. Brush discharges can ignite gases and vapours but not common dusts, while spark and propagating brush discharges can ignite gases, vapours and dusts.[17] The energy stored on an isolated conductor, which a spark can release, follows from its capacitance and voltage:[17]

E=12CV2and soV=2EC

Symbol Description Unit
E Energy stored on the conductor and released by the spark J
C Capacitance of the isolated conductor (workpiece, container, person) F
V Voltage of the conductor relative to ground before discharge V

Optimum mixtures of saturated hydrocarbon vapours with air need about 0.25 mJ of discharge energy at the most favourable electrode spacing.[17] Zalosh (2002) uses the same equation to find the voltage at which an ungrounded silo of 500 pF can ignite a powder cloud. For such capacitive sparks, the stored energy should be compared with ignition energies measured for short capacitive discharges.[18]

Worked example. Take a conductor with the capacitance of Zalosh's example, 500 pF, and the vapour ignition energy of 0.25 mJ. The voltage needed is V = √(2 × 0.25 × 10⁻³ J / 500 × 10⁻¹² F) = 1.0 kV. Charged to 10 kV, the same object would store 25 mJ, about 100 times the energy needed. Conversely, a conductor charged to 30 kV, the lower end of the handheld gun range, needs a capacitance of only 0.56 pF to store 0.25 mJ.[19]

Log chart of stored spark energy against voltage for 5, 50 and 500 pF, crossing the 0.25 mJ vapour ignition line at low voltages
Stored energy E = ½CV² on an isolated conductor compared with the ignition energy of hydrocarbon vapour.

This explains why bonding cannot be limited to large items, and it matches the handbook's remark that a beverage can, or a painful spark from a fingertip, can ignite hydrocarbon vapour.[17] The result holds for a purely capacitive spark and assumes all stored energy reaches the mixture. In reality part of it is lost in heating the electrodes.[17]

Fire development and protection

A fire in a spray pattern radiates heat at an extremely high rate. Scarbrough (2008b) reports that surfaces 900 mm (3 ft) from the gun have been shown to heat up by more than 150 °F per second, which is about 83 K per second. Residues exposed to such radiation ignite within a few seconds; both findings come from unpublished research by the author.[6] Fast optical flame detectors can therefore stop the spray within a small fraction of a second, before the surrounding residue ignites. As described in the 2008 handbook, NFPA 33 requires such detectors for automatic electrostatic installations.[6]

Limiting the fuel supply is the next step. Pump or pressure-vessel supply systems for flammable coatings should have emergency shutdown and an interlock with the fire alarm and flame detector. "Panic button" switches belong at the operator station and at the exit door.[6] Runaway pumps can keep feeding a fire after the hoses have burned off, so every hose connection on the supply piping should have a shutoff valve.[2] Polyethylene tubing melts at once in a fire, rubber hose lasts longer and polytetrafluoroethylene (PTFE) hose longer still.[6]

Automatic sprinklers inside the booth, inside the exhaust ducts and at the ceiling contribute considerably to fire control.[6] In the NFPA 13 occupancy hazard classes summarised in the handbook, flammable liquids spraying is an example of Extra Hazard (Group 2). Group 2 categories typically contain larger quantities of fuel than Group 1.[20] The NIST investigation report on fire suppression systems (NCSTAR 1-4B) names flammable liquid spray booths as an example of the same group.[21] Draft curtains around open spraying areas, together with smoke and heat vents, slow the spread of hot gases under the ceiling so that fewer sprinklers open.[6]

Where an enclosure is too open for total flooding, carbon dioxide can be discharged directly at the hazard, and NUREG-1805 names spray booths among the hazards that such local application can protect.[22] The SFPE Handbook also lists spray booths among the examples of halon local application.[23] Enclosed coaters and decorating machines can be protected by automatic systems that flood their interior. Portable extinguishers help against small fires, but fire can spread across residue beyond their reach within a few seconds. This applies especially to baffle and dry-filter booths and to floors with residue.[6]

A booth and its exhaust duct should stay intact in a fire of nominal size, so that most of the flame, heat and smoke leave the building through the duct. Exhaust fans and makeup air units should keep running during a fire to remove smoke. As described in the 2008 handbook, various US codes and standards require booths and ducts of steel, masonry or material of equivalent fire resistance, and sprinklers in booth and stack help the structure survive. Clearances to combustible construction or storage, given in NFPA 33, reduce the chance of ignition nearby. Spray rooms are usually required to be separated from other occupancies by construction with a fire resistance rating of at least 2 hours.[6] For comparison of fuel loads, the International Fire Engineering Guidelines (2005) list a fire load density of 500 MJ/m² for spray painting of wood products.[24]

Housekeeping, storage and operation

Dried overspray is a solid fuel that ignites easily. A maintenance programme should remove residue from the walls, floor and ceiling of the booth, from conveyors and from inside the ducts. Residue on conveyors can insulate the hangers and spoil the grounding of workpieces.[5] The housekeeping chapter of the handbook adds the area outside the booth, the space behind the filter bank of a dry booth and the exhaust stacks. Only non-ferrous scraping tools should be used, with the scrapings kept in a closed non-combustible container.[25]

Industrial open-front paint spray booth with a back wall of dry filter pads and an overhead exhaust duct
An open-front dry-filter spray booth. Residue on the filters, walls and exhaust is readily ignitable fuel.

Used filters and rags present a serious spontaneous heating hazard. Only a few hours of "fermenting" can make a container of paint-fouled filters or rags hot enough to burst into flame. Fouled filters should leave the building as soon as they are replaced or be kept under water until disposal. Alternatively, the paint in them can be cured by passing them through a bake oven.[5]

Bulk flammable liquids should be stored outdoors or in special indoor storage. Smaller quantities are prepared in a mixing room next to an outside wall with explosion-relief vents, cut off by fire-resistant construction and ventilated. Indoor containers larger than 19 L (5 gal) should have a plug with pressure relief, vacuum relief and a flame arrester. The amount near the process should be limited to one shift, in closed containers placed 1 or 2 m away from the booth.[2]

Liquids should never be transferred by pressurising a shipping container with air, because it may rupture. Hoses for electrostatic equipment with conductive paint must resist both the fluid and high-voltage stress; ordinary hose fails with pinholes that ignite fires. Operators should be trained at the start and at intervals, and drilled in bonding, grounding and emergency procedures.[5]

Regulation, scope and limits of the sources

The requirements in this article are US standards and federal rules as described in the 2008 handbook, not current or universal rules. In the United States, NFPA 33 sets the minimum design criteria and operating procedures for spray application of flammable coatings. Cholin (2008d) recommends applying it to all finishing areas.[15] NFPA 33 also covers chopper-gun and hand lay-up production of glass-fibre-reinforced plastics.[9]

At federal level, the Occupational Safety and Health Administration (OSHA) regulates spray finishing in 29 CFR 1910.107. Many of these OSHA rules derive from older editions of NFPA standards.[26] The handbook does not state which edition of NFPA 33 it describes.[27]

Some quantitative statements rest on thin evidence. The radiant heating rate and the residue ignition time come from unpublished research by the chapter author.[6] The handbook prints 66 °C in brackets after the heating rate of 150 °F per second. That value converts a temperature, whereas the rate corresponds to about 83 K per second.[28] The capacitance in the worked example is borrowed from a silo example and only shows orders of magnitude.[18] Plant scale also varies widely: Cholin (2008d) describes woodworking plants with as many as 20 spray booths in one conveyorised finishing line.[29]

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 1.4 1.5 Scarbrough (2008b), p. 9-29.
  2. ↑ 2.0 2.1 2.2 Scarbrough (2008b), p. 9-33.
  3. ↑ 3.0 3.1 3.2 3.3 Scarbrough (2008b), p. 9-27.
  4. ↑ 4.0 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 Scarbrough (2008b), p. 9-30.
  5. ↑ 5.00 5.01 5.02 5.03 5.04 5.05 5.06 5.07 5.08 5.09 Scarbrough (2008b), p. 9-34.
  6. ↑ 6.00 6.01 6.02 6.03 6.04 6.05 6.06 6.07 6.08 6.09 Scarbrough (2008b), p. 9-35.
  7. ↑ Scarbrough (2008b), pp. 9-29–9-30.
  8. ↑ Katunar (2008), p. 9-39.
  9. ↑ 9.0 9.1 9.2 Milatovich (2008), p. 8-172.
  10. ↑ Van Rossum (2027), §4.1.
  11. ↑ Scarbrough (2008a), p. 11-65.
  12. ↑ Beyler (2002b), p. 2-182.
  13. ↑ Scarbrough (2008b), pp. 9-27–9-28.
  14. ↑ 14.0 14.1 Scarbrough (2008b), p. 9-28.
  15. ↑ 15.0 15.1 15.2 Cholin (2008d), pp. 9-18–9-19.
  16. ↑ Beyler (2002b), p. 2-172.
  17. ↑ 17.0 17.1 17.2 17.3 17.4 Scarbrough (2008a), p. 11-61.
  18. ↑ 18.0 18.1 Zalosh (2002), p. 3-405.
  19. ↑ Calculation with values from Scarbrough (2008a), p. 11-61; Scarbrough (2008b), p. 9-29; and Zalosh (2002), p. 3-405.
  20. ↑ Huggins (2008), pp. 16-38–16-39.
  21. ↑ Hopkins et al. (2005), p. 17.
  22. ↑ Iqbal and Salley (2004), p. B-47.
  23. ↑ Grant (2002), p. 4-158.
  24. ↑ National Research Council of Canada et al. (2005), p. 3.4-7.
  25. ↑ Mattern (2008b), p. 11-35.
  26. ↑ Snyder (2008), p. 12-183.
  27. ↑ Scarbrough (2008b), p. 9-37.
  28. ↑ Calculation based on Scarbrough (2008b), p. 9-35.
  29. ↑ Cholin (2008d), p. 9-11.

References

  • Beyler, C. L. (2002b). Flammability limits of premixed and diffusion flames. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-172–2-187). National Fire Protection Association; Society of Fire Protection Engineers.
  • Cholin, J. M. (2008d). Woodworking facilities and processes. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-3–9-25). National Fire Protection Association.
  • Grant, C. C. (2002). Halon design calculations. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 4-149–4-172). National Fire Protection Association; Society of Fire Protection Engineers.
  • Hopkins, M., Schoenrock, J., & Budnick, E. (2005). Fire suppression systems (NIST NCSTAR 1-4B). National Institute of Standards and Technology.
  • Huggins, R. (2008). Automatic sprinkler systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 16-29–16-53). National Fire Protection Association.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Katunar, J., III (2008). Dipping and coating processes. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-39–9-51). National Fire Protection Association.
  • Mattern, L. J. (2008b). Housekeeping practices. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-27–11-38). National Fire Protection Association.
  • Milatovich, R. M. (2008). Electrical systems and appliances. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-127–8-173). National Fire Protection Association.
  • National Research Council of Canada, International Code Council, Department of Building and Housing, & Australian Building Codes Board. (2005). International fire engineering guidelines (2005 ed.). Australian Building Codes Board.
  • Scarbrough, D. R. (2008a). Control of electrostatic ignition sources. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-59–11-68). National Fire Protection Association.
  • Scarbrough, D. R. (2008b). Spray finishing and powder coating. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-27–9-37). National Fire Protection Association.
  • Snyder, M. (2008). Industrial fire loss prevention. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 12-177–12-198). National Fire Protection Association.
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.
  • Zalosh, R. (2002). Explosion protection. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-402–3-421). National Fire Protection Association; Society of Fire Protection Engineers.