A waste can therefore be hazardous in two ways: it is a listed waste, or it meets one of the hazardous characteristics.<ref name="Sev-7-60" /> The RCRA listings name discarded chemicals, residues, by-products of manufacturing and whole waste sources that must be managed as hazardous.<ref name="DG-11-12" /> Low-level radioactive waste and infectious or biomedical waste are handled under other regulations.<ref name="DG-11-12" /> At the time of the handbook, the Nuclear Regulatory Commission (NRC) regulated [[Radioactive material|radioactive waste]]. Biomedical waste management was regulated by state and local agencies rather than at federal level, although the EPA regulated medical waste incinerators and the DOT the off-site transport of biomedical waste.<ref name="DG-11-13">Doucet and Gilyeat (2008), p. 11-13.</ref> Hazardous waste is one of several overlapping legal categories; Hildebrand and Noll count six legal definitions of a hazardous material in seven major federal regulations.<ref name="HN-13-81">Hildebrand and Noll (2008), p. 13-81.</ref> | A waste can therefore be hazardous in two ways: it is a listed waste, or it meets one of the hazardous characteristics.<ref name="Sev-7-60" /> The RCRA listings name discarded chemicals, residues, by-products of manufacturing and whole waste sources that must be managed as hazardous.<ref name="DG-11-12" /> Low-level radioactive waste and infectious or biomedical waste are handled under other regulations.<ref name="DG-11-12" /> At the time of the handbook, the Nuclear Regulatory Commission (NRC) regulated [[Radioactive material|radioactive waste]]. Biomedical waste management was regulated by state and local agencies rather than at federal level, although the EPA regulated medical waste incinerators and the DOT the off-site transport of biomedical waste.<ref name="DG-11-13">Doucet and Gilyeat (2008), p. 11-13.</ref> Hazardous waste is one of several overlapping legal categories; Hildebrand and Noll count six legal definitions of a hazardous material in seven major federal regulations.<ref name="HN-13-81">Hildebrand and Noll (2008), p. 13-81.</ref> | ||
[[File:fse-hazardous-waste-v1.svg|thumb|upright=1.5|alt=Flowchart: discarded material, then listed waste check, then four characteristic tests, leading to hazardous or non-hazardous waste|Two routes to hazardous waste status under US EPA rules as summarised in the 2008 Fire Protection Handbook.]] | |||
== Hazardous characteristics == | == Hazardous characteristics == | ||
| Line 58: | Line 59: | ||
RCRA places the first duties on the generator. A generator must consult the EPA list of hazardous compounds, analyse unlisted wastes for the hazardous characteristics, declare a waste hazardous where appropriate and obtain an EPA identification number. Fire officials and local emergency planning committees can obtain from their EPA regional office a list of the hazardous waste generators in their area.<ref name="HN-13-84">Hildebrand and Noll (2008), p. 13-84.</ref> Generators are classified by the mass of hazardous waste they produce per month, as shown in the table. | RCRA places the first duties on the generator. A generator must consult the EPA list of hazardous compounds, analyse unlisted wastes for the hazardous characteristics, declare a waste hazardous where appropriate and obtain an EPA identification number. Fire officials and local emergency planning committees can obtain from their EPA regional office a list of the hazardous waste generators in their area.<ref name="HN-13-84">Hildebrand and Noll (2008), p. 13-84.</ref> Generators are classified by the mass of hazardous waste they produce per month, as shown in the table. | ||
[[File:fse-hazardous-waste-v3.svg|thumb|upright=1.5|alt=Bar scale of monthly hazardous waste mass with bands for CESQG below 100 kg, SQG 100 to 1000 kg and LQG above 1000 kg|US hazardous waste generator categories by monthly mass, as described in 2008, with the three example sites from the text.]] | |||
{| class="wikitable" | {| class="wikitable" | ||
| Line 73: | Line 75: | ||
Transport is controlled through the manifest. The hazardous waste manifest identifies the material, states its origin and its destination for treatment, storage or disposal, classifies the waste, gives its quantity and flash point and lists special handling instructions.<ref name="HN-13-83-84">Hildebrand and Noll (2008), pp. 13-83–13-84.</ref> Transporters may carry it only to sites licensed under RCRA, and producers and site operators must prepare contingency plans with local fire, police and hospital officials.<ref name="HN-13-84" /> The 1984 amendments also set minimum technological standards for new land-disposal facilities, such as double liners, two leachate collection systems and groundwater monitoring.<ref name="HN-13-84" /> | Transport is controlled through the manifest. The hazardous waste manifest identifies the material, states its origin and its destination for treatment, storage or disposal, classifies the waste, gives its quantity and flash point and lists special handling instructions.<ref name="HN-13-83-84">Hildebrand and Noll (2008), pp. 13-83–13-84.</ref> Transporters may carry it only to sites licensed under RCRA, and producers and site operators must prepare contingency plans with local fire, police and hospital officials.<ref name="HN-13-84" /> The 1984 amendments also set minimum technological standards for new land-disposal facilities, such as double liners, two leachate collection systems and groundwater monitoring.<ref name="HN-13-84" /> | ||
[[File:fse-hazardous-waste-v2.svg|thumb|upright=1.5|alt=Chain of three boxes, generator to transporter to treatment, storage or disposal facility, with a manifest document travelling along|The cradle-to-grave chain for hazardous waste under US RCRA, with the manifest accompanying each shipment.]] | |||
Workers are protected by the [[Occupational Safety and Health Administration]] (OSHA) standard 29 CFR 1910.120, Hazardous Waste Operations and Emergency Response (HAZWOPER). It was developed under Title I of the Superfund Amendments and Reauthorization Act of 1986.<ref name="HN-13-85">Hildebrand and Noll (2008), p. 13-85.</ref> As summarised by Severson, it requires a written safety and health programme, site characterisation, training before work starts, medical surveillance, engineering controls and personal protective equipment, and a written emergency response plan.<ref name="Sev-7-64-65">Severson (2008), pp. 7-64–7-65.</ref> OSHA also requires employers to inform and train employees about the hazards of the chemicals they handle, under the Hazard Communication Standard, 29 CFR 1910.1200.<ref name="Sev-7-59" /> Under Section 311 of the community right-to-know law, facilities submit the [[safety data sheet]] of each covered chemical, or a list of the chemicals, to local planners and the fire department.<ref name="HN-13-86">Hildebrand and Noll (2008), p. 13-86.</ref> | Workers are protected by the [[Occupational Safety and Health Administration]] (OSHA) standard 29 CFR 1910.120, Hazardous Waste Operations and Emergency Response (HAZWOPER). It was developed under Title I of the Superfund Amendments and Reauthorization Act of 1986.<ref name="HN-13-85">Hildebrand and Noll (2008), p. 13-85.</ref> As summarised by Severson, it requires a written safety and health programme, site characterisation, training before work starts, medical surveillance, engineering controls and personal protective equipment, and a written emergency response plan.<ref name="Sev-7-64-65">Severson (2008), pp. 7-64–7-65.</ref> OSHA also requires employers to inform and train employees about the hazards of the chemicals they handle, under the Hazard Communication Standard, 29 CFR 1910.1200.<ref name="Sev-7-59" /> Under Section 311 of the community right-to-know law, facilities submit the [[safety data sheet]] of each covered chemical, or a list of the chemicals, to local planners and the fire department.<ref name="HN-13-86">Hildebrand and Noll (2008), p. 13-86.</ref> | ||
| Line 91: | Line 94: | ||
Firefighting water is itself a potential hazardous waste. Water used at chemical plants or warehouses storing hazardous materials will likely become contaminated, and through the storm-water system it can spread the hazard beyond the plant.<ref name="Sev-7-65" /> The handbook's example is a fire in November 1986 at an agricultural chemicals warehouse on the Rhine in Basel, Switzerland. There the contaminated water caused a massive fish kill and water pollution that spread to Germany and Holland.<ref name="Sev-7-65" /> Severson recommends locating storm-water drains, sewers and the slope of the site in advance.<ref name="Sev-7-65" /> Serapiglia adds that industrial pre-incident plans should record drainage collection points and potable water supply locations.<ref name="Ser-12-298">Serapiglia (2008), p. 12-298.</ref> | Firefighting water is itself a potential hazardous waste. Water used at chemical plants or warehouses storing hazardous materials will likely become contaminated, and through the storm-water system it can spread the hazard beyond the plant.<ref name="Sev-7-65" /> The handbook's example is a fire in November 1986 at an agricultural chemicals warehouse on the Rhine in Basel, Switzerland. There the contaminated water caused a massive fish kill and water pollution that spread to Germany and Holland.<ref name="Sev-7-65" /> Severson recommends locating storm-water drains, sewers and the slope of the site in advance.<ref name="Sev-7-65" /> Serapiglia adds that industrial pre-incident plans should record drainage collection points and potable water supply locations.<ref name="Ser-12-298">Serapiglia (2008), p. 12-298.</ref> | ||
[[File:fse-hazardous-waste-v4.svg|thumb|upright=1.5|alt=Cross-section of a burning chemical warehouse with fire hose water flowing over sloping ground into a storm drain and a river|Contaminated firefighting water can reach surface water through storm drains; pre-incident plans record drains, slope and water supplies.]] | |||
Foam effluent raises the same question. Facilities protected by foam systems may have containment for it, and such requirements were becoming more widespread in model building and fire codes. An early Factory Mutual review cited by Scheffey found that both [[aqueous film-forming foam]] and protein-based foams present environmental issues. Their effluent should therefore be processed in a sewage treatment facility or diluted before discharge. Large quantities can shock-load a treatment plant.<ref name="Sch02-4-118">Scheffey (2002), p. 4-118.</ref> The handbook advises against uncontrolled release of foam solutions and lists transport to a wastewater treatment plant or hazardous waste facility among the disposal options.<ref name="Sch08-17-69">Scheffey (2008), p. 17-69.</ref> | Foam effluent raises the same question. Facilities protected by foam systems may have containment for it, and such requirements were becoming more widespread in model building and fire codes. An early Factory Mutual review cited by Scheffey found that both [[aqueous film-forming foam]] and protein-based foams present environmental issues. Their effluent should therefore be processed in a sewage treatment facility or diluted before discharge. Large quantities can shock-load a treatment plant.<ref name="Sch02-4-118">Scheffey (2002), p. 4-118.</ref> The handbook advises against uncontrolled release of foam solutions and lists transport to a wastewater treatment plant or hazardous waste facility among the disposal options.<ref name="Sch08-17-69">Scheffey (2008), p. 17-69.</ref> | ||
Latest revision as of 09:01, 9 November 2026
Hazardous waste is discarded material that can harm health, the environment or property if handled or disposed of improperly, because it is toxic, flammable, explosive, reactive, radioactive, corrosive or infectious.[1] Although all waste is a nuisance, not all waste is necessarily hazardous.[1] For fire protection, hazardous waste is a special problem: its composition is often unknown, its components may react, and a fire can release toxic smoke and contaminated firefighting water.[2][3]
In the United States the term also has a legal meaning. The Environmental Protection Agency (EPA) regulates hazardous waste under the Resource Conservation and Recovery Act (RCRA). A waste is hazardous when it is listed or shows ignitability, corrosivity, reactivity or toxicity.[4][5] The rules described in this article are US federal rules as summarised in the Fire Protection Handbook (20th edition, 2008), reflecting practice around 2007–2008.
Definition
Severson defines hazardous waste as waste that "poses a threat to human health, the environment, or public property if handled or disposed of improperly". The hazard arises from the toxicity, flammability, explosivity, reactivity, radioactivity, corrosivity or etiologic (disease-causing) potential of the waste.[1] Doucet and Gilyeat give a broader wording. Hazardous waste is any waste that poses a substantial danger, now or in the future, to human, plant or animal life and that needs special precautions in handling or disposal.[6]
US law adds narrower, legal definitions. Hildebrand and Noll describe hazardous wastes as discarded materials regulated by the EPA because of public health and safety concerns, with the regulatory authority granted under RCRA.[5] The EPA definition summarised by Severson covers waste that might increase mortality or serious illness, or that poses a substantial hazard when improperly treated, stored, transported or disposed of. The hazardous property must be measurable by an available standardised test method or reasonably detectable by the generator through knowledge of the waste.[4] For transport, the US Department of Transportation (DOT) treats as hazardous waste any material that is subject to the EPA hazardous waste manifest requirements in 40 CFR Part 262.[7]
A waste can therefore be hazardous in two ways: it is a listed waste, or it meets one of the hazardous characteristics.[4] The RCRA listings name discarded chemicals, residues, by-products of manufacturing and whole waste sources that must be managed as hazardous.[6] Low-level radioactive waste and infectious or biomedical waste are handled under other regulations.[6] At the time of the handbook, the Nuclear Regulatory Commission (NRC) regulated radioactive waste. Biomedical waste management was regulated by state and local agencies rather than at federal level, although the EPA regulated medical waste incinerators and the DOT the off-site transport of biomedical waste.[8] Hazardous waste is one of several overlapping legal categories; Hildebrand and Noll count six legal definitions of a hazardous material in seven major federal regulations.[9]
Hazardous characteristics
The EPA standards summarised in the handbook use four characteristics: ignitability, corrosivity, reactivity and toxicity.[4] Doucet and Gilyeat list seven characteristics under RCRA and other regulations, adding explosivity, radioactivity and infectiousness.[8] The table gives the criteria as printed in the 2008 handbook.
| Characteristic | Criterion | Source |
|---|---|---|
| Ignitability (liquid) | Closed-cup flash point below 60 °C (140 °F), excluding wine and latex paint | [4] |
| Ignitability (not a liquid) | Can cause fire through friction, absorption of moisture or spontaneous chemical change at standard temperature and pressure, and burns vigorously and persistently | [4] |
| Ignitability (gas) | Flammable compressed gas: flammable in air below 13 % by volume, or a flammable range in air wider than 12 % | [4] |
| Ignitability (oxidiser) | Oxidiser such as a chlorate, permanganate, inorganic peroxide or nitrate | [4] |
| Corrosivity | Aqueous with pH ≤ 2 or ≥ 12.5, or a liquid that corrodes steel faster than 6.35 mm (¼ in.) per year at 55 °C (130 °F) | [4] |
| Reactivity | Unstable, water-reactive, forms toxic gas with water, cyanide- or sulfide-bearing, or capable of detonation | [10] |
| Toxicity | Oral LD50 (rat) below 50 mg/kg, inhalation LC50 (rat) below 2 mg/L, or dermal LD50 (rabbit) below 200 mg/kg | [11] |
Ignitability is the characteristic most closely linked to fire. A liquid waste is ignitable when its flash point is below 60 °C (140 °F), which corresponds to the Class I and Class II liquids of NFPA 30.[4] The liquid classification used for fire codes and the waste rule therefore overlap. Ignitable liquid wastes are mainly contaminated organic solvents, but they also include oils, plasticisers, complex organic sludges, off-specification chemicals and pharmaceutical by-products.[8] Pyrophoric solids such as phosphorus and aluminium alkyls count as ignitable because they ignite on exposure to air.[8] An oxidiser is included because it yields oxygen readily and so stimulates the combustion of organic matter.[4]
Reactivity covers eight behaviours, from normal instability and violent reaction with water to the release of toxic gases and the ability to detonate.[10] Sodium, potassium and aluminium alkyls are typical reactive wastes: they react violently with water and burn fiercely.[8]
Toxicity is defined by animal test limits, by known fatality to humans in low doses, or by the presence of listed toxic materials.[11] Typical toxic constituents are metals such as arsenic, barium, cadmium, chromium, mercury and lead, and chlorinated organics such as pesticides. RCRA prescribes an extraction procedure test to decide whether they are present in significant concentrations.[8] Explosive waste consists mainly of obsolete ordnance and waste from explosives, propellant and pyrotechnics manufacture.[8] Radioactive waste is mostly ordinary material contaminated with radionuclides, at concentrations from parts per billion to as much as 50 %.[8]
Sources and quantities
The source of a waste largely determines its composition, density, quantity and degree of hazard.[12] A furniture plant, for example, produces scrap wood, sawdust, oily rags, stain, varnish, lacquer and glue. Chemical plants discard off-grade products, by-products, tars, spent catalyst and precipitates, and nuclear power plants produce radioactive waste. Spills, cleaning operations, leaking drums, tank washing and rejected products add to the stream, and water, fire or explosion damage can create substantial amounts of waste.[13]
According to EPA estimates cited by Doucet and Gilyeat, the United States generated more than about 6.8 billion tonnes of industrial waste a year. About 36 million tonnes of this was designated as hazardous.[14] Under Section 313 of the Emergency Planning and Community Right-to-Know Act of 1986, the EPA collects annual release data on more than 570 listed toxic chemicals from over 23,000 qualifying companies. In 2003 these facilities reported on-site and off-site releases to the environment of 2.3 billion kg (5.0 billion lb).[15] This reporting programme belongs to the wider system of community right-to-know.
Fire and explosion hazards
Waste is often a mixture of many components with different hazardous properties, and its contents may not be well defined or even known.[2] One component might be a flammable solvent and another a highly toxic pesticide. Incinerating the solvent might then release the pesticide, or its toxic combustion products, to the atmosphere.[2] This links waste fires to pesticide fire hazards and to fire toxicity in general. Polychlorinated biphenyls (PCBs) are a similar case: their improper combustion can produce highly toxic and carcinogenic products.[16] The physical and chemical properties of a mixture are usually close to those of its main component, but its hazard can be governed by small amounts of a highly toxic, radioactive or infectious component.[4]
Severson names self-heating and ignition, corrosion of pipe and tank walls, and reaction with other incompatible wastes as causes of major catastrophic events.[2] Mixing two discarded substances can produce a reaction with severe and unexpected consequences, which makes chemical incompatibility a central concern in waste storage.[4] Systems for liquid chemical wastes must deal with spontaneous ignition, rapid heat release, foaming and the release of low-boiling compounds. Typical safety provisions are spill and runoff containment, static electricity prevention, flame arresters and segregation of incompatible wastes.[17]
Some hazards come from ordinary items in the waste stream. Small butane and LP-gas cylinders discarded in household trash can pose an explosion hazard to trash collectors, compactors and shredder operators.[4] In shredders, the ignition sources are frictional sparks between the shredding teeth, the shredder walls and solid refuse.[18] Methane generated by biological activity in old landfills can build up in buildings constructed over them and cause fires and explosions.[18]
A US Nuclear Regulatory Commission report lists low-level radioactive waste among the combustibles common in nuclear power plants, with paper, plastic, anti-contamination (anti-C) clothing, rubber shoes and gloves as examples. The same list names solidification agents such as bitumen, used to condition compacted radioactive waste.[19] In tanks of radioactive solutions or waste, radiolysis, liner corrosion and chemical decomposition generate hydrogen, methane, ammonia and nitrous oxide. The first three are flammable and the fourth is an oxidiser.[20] The same report gives a lower explosive limit for hydrogen of 4 % for upward and 8 % for downward flame propagation, and notes that explosion overpressures are not observed below 8 %.[20]
Regulation in the United States
The handbook summarises the main US federal laws as they stood around 2007–2008. RCRA (1976, amended 1984) was enacted as an amendment to the Solid Waste Disposal Act. It provides for "cradle-to-grave" tracking of hazardous waste, from generator to transporter to treatment, storage or disposal.[21] Congress intended the states to implement RCRA under federal oversight. A state programme must be fully equivalent to the federal one but may be more stringent or broader in scope.[22]
Subtitle C of RCRA covers hazardous waste. The 1980 Superfund law (CERCLA) set up a fund of $1.6 billion for the cleanup of uncontrolled hazardous waste sites.[22] The Toxic Substances Control Act of 1976 sets, among other things, the disposal requirements for PCBs.[14]
RCRA places the first duties on the generator. A generator must consult the EPA list of hazardous compounds, analyse unlisted wastes for the hazardous characteristics, declare a waste hazardous where appropriate and obtain an EPA identification number. Fire officials and local emergency planning committees can obtain from their EPA regional office a list of the hazardous waste generators in their area.[23] Generators are classified by the mass of hazardous waste they produce per month, as shown in the table.
| Category | Hazardous waste per month | Acutely hazardous waste per month |
|---|---|---|
| Large-quantity generator (LQG) | More than 1,000 kg (2,200 lb) | More than 1 kg (2.2 lb) |
| Small-quantity generator (SQG) | Less than 1,000 kg (2,200 lb) | Less than 1 kg (2.2 lb) |
| Conditionally exempt small-quantity generator (CESQG) | Less than 100 kg (220 lb) | Less than 1 kg (2.2 lb) |
A large-quantity generator must ship its waste within 90 days once the first 1,000 kg has been accumulated. Waste that stays on the generator's property for more than 90 days is considered stored, and the generator then needs a storage facility permit under RCRA Section 3005.[23] As a worked example, consider three sites. A paint shop producing 60 kg of waste solvent a month and no acutely hazardous waste falls in the CESQG class. A plant producing 450 kg a month is a small-quantity generator, the class that the Hazardous and Solid Waste Amendments of 1984 brought under RCRA's authority.[23] A plant producing 1,400 kg a month, or only 60 kg of other hazardous waste plus 1.5 kg of acutely hazardous waste, is a large-quantity generator.[23]
Transport is controlled through the manifest. The hazardous waste manifest identifies the material, states its origin and its destination for treatment, storage or disposal, classifies the waste, gives its quantity and flash point and lists special handling instructions.[24] Transporters may carry it only to sites licensed under RCRA, and producers and site operators must prepare contingency plans with local fire, police and hospital officials.[23] The 1984 amendments also set minimum technological standards for new land-disposal facilities, such as double liners, two leachate collection systems and groundwater monitoring.[23]
Workers are protected by the Occupational Safety and Health Administration (OSHA) standard 29 CFR 1910.120, Hazardous Waste Operations and Emergency Response (HAZWOPER). It was developed under Title I of the Superfund Amendments and Reauthorization Act of 1986.[25] As summarised by Severson, it requires a written safety and health programme, site characterisation, training before work starts, medical surveillance, engineering controls and personal protective equipment, and a written emergency response plan.[26] OSHA also requires employers to inform and train employees about the hazards of the chemicals they handle, under the Hazard Communication Standard, 29 CFR 1910.1200.[21] Under Section 311 of the community right-to-know law, facilities submit the safety data sheet of each covered chemical, or a list of the chemicals, to local planners and the fire department.[27]
Treatment and disposal
The preferred order for dealing with waste is reduction or reuse at the source first, recycling second, and treatment or disposal last.[12] Treatment processes are physical, chemical, biological or thermal. They reduce volume, separate waste components, or destroy and detoxify hazardous constituents, and several processes are often linked in series. Residues that still have hazardous characteristics must go to a permitted hazardous waste landfill or disposal site.[17]
Hazardous wastes must not be disposed of in a sanitary landfill. They must be chemically treated, incinerated in properly designed furnaces that ensure complete degradation of the hazardous components, or placed in secure landfills. Transport to the disposal site requires special permits, approved containers and a manifest.[28] Secure landfills are regulated under RCRA and need special liners, caps, gas venting and monitoring wells.[29] Deep-well injection pumps liquid waste into geologically isolated reservoirs below potable aquifers. Average well depths are about 1,525 m (5,000 ft), and some wells reach 3,050 m (10,000 ft).[29]
Burning in an incinerator brings its own fire hazards. Severson lists overheating from large amounts of volatiles or a higher heat of combustion, structural failure from overheating or corrosion, and scrubber corrosion or failure.[18] Waste solvents have variable flash points and are disposed of by incineration, recycling or fuel blending; a contractor must be told their approximate composition. An on-site solvent incinerator needs an auxiliary gas or oil burner to maintain the destruction temperature, and NFPA 82 covers industrial incinerator installations.[16]
Several waste types need specific methods. Rags or paper soaked with drying oils such as linseed oil are subject to spontaneous heating and should be kept in covered metal cans.[16] Quantity storage of highly combustible refuse should be at least 15 m (50 ft) from buildings, roadways and ignition sources.[16] Fine magnesium chips and dust-collector sludge can be burned outdoors in a layer about 102 mm (4 in.) thick. Magnesium sludge can also be deactivated with a 0.5 % ferrous chloride solution, outdoors, because the reaction releases hydrogen.[16]
Medical and radioactive wastes follow separate rules. Incineration of infectious medical waste reduces its volume by up to 95 %, while steam sterilisation is the most commonly used method for destroying pathogens.[28] Radioactive medical waste with a half-life of less than 65 days may be stored in a secure area for at least 10 half-lives and then discarded as sanitary waste.[30] Ten half-lives reduce the activity to 0.510, or about 0.1 %, of its initial value. Combustible radioactive waste should not be allowed to accumulate and should not be stored near an air intake.[30]
Fire prevention and emergency response
Severson lists seven preventive measures for waste handling and storage. They are segregating incompatible wastes, such as combustible waste from self-heating or oxidising materials, and disposing of waste promptly so that large quantities do not accumulate. Combustible waste piles should be kept away from buildings, roadways and ignition sources, and flammable or corrosive liquid wastes kept in approved metal containers. The remaining measures are regular container inspection, clear hazard marking on every container, tank, vehicle and building, and training with drills of credible release scenarios.[3] In the US practice described in the handbook, fire departments are expected to coordinate pre-incident planning with every waste-generating industry and disposal facility in their area. They should know the types, quantities and hazards of the raw materials, products and wastes on each site.[26]
Firefighting water is itself a potential hazardous waste. Water used at chemical plants or warehouses storing hazardous materials will likely become contaminated, and through the storm-water system it can spread the hazard beyond the plant.[3] The handbook's example is a fire in November 1986 at an agricultural chemicals warehouse on the Rhine in Basel, Switzerland. There the contaminated water caused a massive fish kill and water pollution that spread to Germany and Holland.[3] Severson recommends locating storm-water drains, sewers and the slope of the site in advance.[3] Serapiglia adds that industrial pre-incident plans should record drainage collection points and potable water supply locations.[31]
Foam effluent raises the same question. Facilities protected by foam systems may have containment for it, and such requirements were becoming more widespread in model building and fire codes. An early Factory Mutual review cited by Scheffey found that both aqueous film-forming foam and protein-based foams present environmental issues. Their effluent should therefore be processed in a sewage treatment facility or diluted before discharge. Large quantities can shock-load a treatment plant.[32] The handbook advises against uncontrolled release of foam solutions and lists transport to a wastewater treatment plant or hazardous waste facility among the disposal options.[33]
When a release occurs and the waste components are unknown, Severson advises treating the waste as an extreme hazard until better information is available. The response measures he lists are full protective clothing and breathing apparatus, detection of flammability, toxicity or radioactivity, stopping the flow at the source and containing liquid spills. Responders should stay upwind, control ignition sources and evacuate people downwind.[3] These steps are part of hazardous materials response in general.
The decision to extinguish burning waste should follow a full assessment. It should consider whether the agent is compatible with the waste, whether sealed drums or gas cylinders are exposed, and whether radioactive, explosive or oxidising materials are present. Extinguishment may also release flammable or toxic vapours, and water may cause severe pollution.[34]
Limits and common misconceptions
The term has no single meaning. The technical definitions in the handbook are broader than the legal US definitions, and Hildebrand and Noll note that the overlapping federal regulations contain at least six legal definitions of a hazardous material.[9] The numerical criteria in this article are US federal rules as summarised in 2008, not current values or rules for other countries. Even within the United States, states could set stricter requirements, and medical waste standards differed from state to state.[22][28]
The handbook is not fully consistent. Severson and Mattern give the upper pH limit for corrosive waste as 12.5, whereas Doucet and Gilyeat give 12.[4][35][8] Severson and Doucet and Gilyeat word the ignitability limit as a flash point "less than" 60 °C (140 °F), whereas Mattern writes 60 °C (140 °F) "or less".[4][8][35] Severson prints the corrosion test temperature of 130 °F as 55 °C; the exact conversion is 54.4 °C.[4] Severson's summary of the characteristics rests on 40 CFR Part 261, Subpart C, in the 1995 edition of the Code of Federal Regulations.[36]
A common misconception is that a waste mixture behaves like its largest component. This holds for physical and chemical properties, but not for hazards, which a small toxic or radioactive fraction can dominate.[4] Another is that putting out a waste fire is always the best course; the questions above show that extinguishment can make the outcome worse.[34]
A third misconception concerns firefighting foam. The carbon–fluorine chain of the fluorinated surfactants in AFFF apparently does not break down in the biological or chemical oxygen demand (BOD or COD) tests used to assess biodegradability. A foam can therefore appear completely biodegradable while that chain remains. A study of fire-training facilities detected perfluorocarboxylates at sites that had been inactive for 7 to 10 years.[32]
See also
Notes
- ↑ 1.0 1.1 1.2 Severson (2008), p. 7-57.
- ↑ 2.0 2.1 2.2 2.3 Severson (2008), p. 7-62.
- ↑ 3.0 3.1 3.2 3.3 3.4 3.5 Severson (2008), p. 7-65.
- ↑ 4.00 4.01 4.02 4.03 4.04 4.05 4.06 4.07 4.08 4.09 4.10 4.11 4.12 4.13 4.14 4.15 4.16 4.17 Severson (2008), p. 7-60.
- ↑ 5.0 5.1 Hildebrand and Noll (2008), p. 13-82.
- ↑ 6.0 6.1 6.2 Doucet and Gilyeat (2008), p. 11-12.
- ↑ C. J. Wright (2008a), p. 13-118.
- ↑ 8.00 8.01 8.02 8.03 8.04 8.05 8.06 8.07 8.08 8.09 Doucet and Gilyeat (2008), p. 11-13.
- ↑ 9.0 9.1 Hildebrand and Noll (2008), p. 13-81.
- ↑ 10.0 10.1 Severson (2008), pp. 7-60–7-61.
- ↑ 11.0 11.1 Severson (2008), p. 7-61.
- ↑ 12.0 12.1 Severson (2008), p. 7-58.
- ↑ Severson (2008), pp. 7-58–7-59.
- ↑ 14.0 14.1 Doucet and Gilyeat (2008), p. 11-11.
- ↑ Severson (2008), pp. 7-57–7-58.
- ↑ 16.0 16.1 16.2 16.3 16.4 Severson (2008), p. 7-66.
- ↑ 17.0 17.1 Doucet and Gilyeat (2008), p. 11-17.
- ↑ 18.0 18.1 18.2 Severson (2008), p. 7-63.
- ↑ Iqbal and Salley (2004), p. 1-6.
- ↑ 20.0 20.1 Iqbal and Salley (2004), p. B-26.
- ↑ 21.0 21.1 Severson (2008), p. 7-59.
- ↑ 22.0 22.1 22.2 Hildebrand and Noll (2008), p. 13-83.
- ↑ 23.0 23.1 23.2 23.3 23.4 23.5 Hildebrand and Noll (2008), p. 13-84.
- ↑ Hildebrand and Noll (2008), pp. 13-83–13-84.
- ↑ Hildebrand and Noll (2008), p. 13-85.
- ↑ 26.0 26.1 Severson (2008), pp. 7-64–7-65.
- ↑ Hildebrand and Noll (2008), p. 13-86.
- ↑ 28.0 28.1 28.2 Severson (2008), p. 7-64.
- ↑ 29.0 29.1 Doucet and Gilyeat (2008), p. 11-23.
- ↑ 30.0 30.1 Severson (2008), p. 7-67.
- ↑ Serapiglia (2008), p. 12-298.
- ↑ 32.0 32.1 Scheffey (2002), p. 4-118.
- ↑ Scheffey (2008), p. 17-69.
- ↑ 34.0 34.1 Severson (2008), pp. 7-65–7-66.
- ↑ 35.0 35.1 Mattern (2008b), p. 11-35.
- ↑ Severson (2008), p. 7-68.
References
- Doucet, L. G., & Gilyeat, S. S. (2008). Waste handling and control. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-3–11-25). National Fire Protection Association.
- Hildebrand, M. S., & Noll, G. G. (2008). Public fire protection and hazmat management. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 13-81–13-98). National Fire Protection Association.
- Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
- Mattern, L. J. (2008b). Housekeeping practices. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-27–11-38). National Fire Protection Association.
- Scheffey, J. L. (2002). Foam agents and AFFF system design considerations. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 4-88–4-122). National Fire Protection Association; Society of Fire Protection Engineers.
- Scheffey, J. L. (2008). Foam extinguishing agents and systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-45–17-70). National Fire Protection Association.
- Serapiglia, M. J. (2008). Pre-Incident planning for industrial and municipal emergency response. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 12-289–12-298). National Fire Protection Association.
- Severson, P. R. (2008). Hazardous waste control. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-57–7-69). National Fire Protection Association.
- Wright, C. J. (2008a). Managing the response to hazardous material incidents. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 13-117–13-144). National Fire Protection Association.