== Types of protection ==
== Types of protection ==
NFPA 496, as described in the handbook, distinguishes three types of purging by the change in classification they achieve. Type X purging reduces the classification within the enclosure from Division 1 to nonhazardous. Type Y purging reduces it from Division 1 to Division 2. Type Z purging reduces it from Division 2 to nonhazardous.<ref name="UG-17-150" /><ref name="UG-17-151" /> The details of each method are given in NFPA 496 itself, which the handbook does not reproduce.<ref name="UG-17-150" />
NFPA 496, as described in the handbook, distinguishes three types of purging by the change in classification they achieve. Type X purging reduces the classification within the enclosure from Division 1 to nonhazardous. Type Y purging reduces it from Division 1 to Division 2. Type Z purging reduces it from Division 2 to nonhazardous.<ref name="UG-17-150" /><ref name="UG-17-151" /> The details of each method are given in NFPA 496 itself, which the handbook does not reproduce.<ref name="UG-17-150" />
[[File:fse-purged-and-pressurised-enclosure-v2.svg|thumb|upright=1.5|alt=Three panels showing Type X from Division 1 to nonhazardous, Type Y from Division 1 to Division 2 and Type Z from Division 2 to nonhazardous|Type X, Y and Z purging under NFPA 496.]]


The handbook gives Type X as the required type for the control room of an oilseed extraction plant, where computers that are not built for Division 1 are placed in a Division 1 building.<ref name="Kingsbaker-9-138" /> Where a Division 1 area is pressurised to Division 2 and contains equipment that is itself protected by pressurisation, the handbook calls this "double pressurization"; the two protective gas supplies must then be independent.<ref name="Milatovich-8-171" />
The handbook gives Type X as the required type for the control room of an oilseed extraction plant, where computers that are not built for Division 1 are placed in a Division 1 building.<ref name="Kingsbaker-9-138" /> Where a Division 1 area is pressurised to Division 2 and contains equipment that is itself protected by pressurisation, the handbook calls this "double pressurization"; the two protective gas supplies must then be independent.<ref name="Milatovich-8-171" />
Line 19: Line 20:


The protective gas itself must be essentially free of contaminants and may contain no more than trace amounts of flammable gas or vapour. Air of normal instrument quality, nitrogen or another nonflammable gas is acceptable.<ref name="Milatovich-8-171" /> The piping must be protected against mechanical damage. If compressed air is used, the compressor intake must be in an unclassified location. An intake line that passes through a classified location must be noncombustible, protected against damage and corrosion, and designed so that flammable gases, vapours or dusts cannot leak into it.<ref name="Milatovich-8-171" /> The blower or compressor must be powered from a separate source or from the supply of the protected enclosure ahead of any service disconnect.<ref name="Milatovich-8-171" />
The protective gas itself must be essentially free of contaminants and may contain no more than trace amounts of flammable gas or vapour. Air of normal instrument quality, nitrogen or another nonflammable gas is acceptable.<ref name="Milatovich-8-171" /> The piping must be protected against mechanical damage. If compressed air is used, the compressor intake must be in an unclassified location. An intake line that passes through a classified location must be noncombustible, protected against damage and corrosion, and designed so that flammable gases, vapours or dusts cannot leak into it.<ref name="Milatovich-8-171" /> The blower or compressor must be powered from a separate source or from the supply of the protected enclosure ahead of any service disconnect.<ref name="Milatovich-8-171" />
[[File:fse-purged-and-pressurised-enclosure-v1.svg|thumb|upright=1.5|alt=Electrical enclosure in a hazardous area kept at 25 Pa overpressure by clean air from a compressor with its intake in an unclassified area|Pressurising system for an electrical enclosure in a hazardous location.]]


Rotating machines need a further safeguard. This applies to motors, generators and other rotating machines protected by a pressurising or protective gas design. No external surface may exceed 80 percent of the ignition temperature of the gas or vapour, both in degrees Celsius. The ignition temperature is determined by ASTM E659.<ref name="Milatovich-8-171" /> Heat sensors must detect any temperature rise beyond the design limits and automatically de-energise the equipment. These detectors work without the protection of positive pressure, so in a Class I, Division 1 location they must themselves be explosionproof or intrinsically safe.<ref name="Milatovich-8-171" />
Rotating machines need a further safeguard. This applies to motors, generators and other rotating machines protected by a pressurising or protective gas design. No external surface may exceed 80 percent of the ignition temperature of the gas or vapour, both in degrees Celsius. The ignition temperature is determined by ASTM E659.<ref name="Milatovich-8-171" /> Heat sensors must detect any temperature rise beyond the design limits and automatically de-energise the equipment. These detectors work without the protection of positive pressure, so in a Class I, Division 1 location they must themselves be explosionproof or intrinsically safe.<ref name="Milatovich-8-171" />
Line 46: Line 48:


'''Worked example 2.''' The same model puts into perspective the 10 volumes of air that the handbook requires for motors.<ref name="Milatovich-8-171" /> Assume a motor enclosure filled with hexane vapour at 6.9 percent, the upper end of its flammable range of 1.2 to 6.9 percent.<ref name="Kingsbaker-9-137">Kingsbaker (2008), p. 9-137.</ref> In a perfectly mixed enclosure, about 1.75 volumes would bring the concentration down to the lower limit of 1.2 percent. Ten volumes reduce it by a factor of about 22,000, to roughly 3 ppm.<ref name="Beyler-2-181" /> The handbook links the 10-volume rule to the need to purge the voids between the windings, which the well-mixed model does not represent.<ref name="Milatovich-8-171" />
'''Worked example 2.''' The same model puts into perspective the 10 volumes of air that the handbook requires for motors.<ref name="Milatovich-8-171" /> Assume a motor enclosure filled with hexane vapour at 6.9 percent, the upper end of its flammable range of 1.2 to 6.9 percent.<ref name="Kingsbaker-9-137">Kingsbaker (2008), p. 9-137.</ref> In a perfectly mixed enclosure, about 1.75 volumes would bring the concentration down to the lower limit of 1.2 percent. Ten volumes reduce it by a factor of about 22,000, to roughly 3 ppm.<ref name="Beyler-2-181" /> The handbook links the 10-volume rule to the need to purge the voids between the windings, which the well-mixed model does not represent.<ref name="Milatovich-8-171" />
[[File:fse-purged-and-pressurised-enclosure-v3.svg|thumb|upright=1.5|alt=Line chart of hexane concentration against purge volumes on a log scale, falling from 6.9 percent to about 3 ppm after 10 volumes|Hexane concentration in a well-mixed enclosure against the number of purge volumes.]]


Process vessels can also be purged in batches rather than by a continuous flow. In vacuum purging the pressure is lowered from <math>P_1</math> to <math>P_2</math> and then restored with inert gas, so that a fraction <math>X = P_2/P_1</math> of the original gas remains. After <math>n</math> cycles the fraction is <math>X^n</math>.<ref name="UG-17-149" /> Evacuating a vessel from 100 kPa to 20 kPa absolute leaves 0.2 of the original gas per cycle and 0.008 after three cycles. Both relations assume that the gas in the vessel is well mixed.<ref name="UG-17-149" />
Process vessels can also be purged in batches rather than by a continuous flow. In vacuum purging the pressure is lowered from <math>P_1</math> to <math>P_2</math> and then restored with inert gas, so that a fraction <math>X = P_2/P_1</math> of the original gas remains. After <math>n</math> cycles the fraction is <math>X^n</math>.<ref name="UG-17-149" /> Evacuating a vessel from 100 kPa to 20 kPa absolute leaves 0.2 of the original gas per cycle and 0.008 after three cycles. Both relations assume that the gas in the vessel is well mixed.<ref name="UG-17-149" />

Latest revision as of 08:47, 9 November 2026

A purged and pressurised enclosure is an enclosure for electrical equipment that is flushed with clean air or an inert gas and then kept at a slight positive pressure. The surrounding flammable gas or vapour therefore cannot enter it.[1][2] The method allows ordinary, unrated equipment such as control panels, motors and computers to be used in a hazardous location, or reduces the hazard classification inside a room or cabinet.[3][4] In the United States, NFPA 496, Standard for Purged and Pressurized Enclosures for Electrical Equipment, describes three types of protection, as summarised in the Fire Protection Handbook (2008). Type X purging reduces the classification inside the enclosure from Division 1 to nonhazardous, Type Y from Division 1 to Division 2, and Type Z from Division 2 to nonhazardous.[5][3] Safe operation depends on a reliable supply of clean protective gas, on an alarm or automatic shutdown when the pressure is lost and on enough purge flow to reach and keep a safe atmosphere.[1][2] Purging is related to inerting of process equipment, which uses the same dilution principles,[6] and it is one of the main alternatives to explosionproof equipment.[1]

Definition and principle

The handbook does not give a single formal definition, but it describes two steps. Purging means supplying an enclosure with clean air or an inert gas at a sufficient flow to remove a flammable atmosphere that may be present. Pressurising means keeping that clean atmosphere inside at a positive pressure, so that the surrounding mixture cannot leak in.[1][2] NFPA 496 gives information on the design of purged enclosures that eliminate or reduce a Class I hazardous location within the enclosure. Such a location has gases or vapours in air in quantities sufficient to produce explosive or ignitable mixtures.[1][2]

The principle differs from that of an explosionproof enclosure. An explosionproof enclosure assumes that gas will enter and may ignite inside, and it is built to contain the explosion and cool the escaping gases.[1] A purged and pressurised enclosure instead keeps the gas out, so the electrical equipment inside never meets an ignitable mixture. Ural and Garzia (2008) therefore list purging among the four aspects of fuel control in explosion prevention, together with containment, ventilation and housekeeping.[6] In their words, purging is used to prevent the development of ignitable atmospheres in enclosures or equipment.[5]

The concept is tied to the US system of hazardous area classification under the National Electrical Code (NEC). In Class I, Division 1 locations, motors, luminaires, most switches and circuit breakers must be of the explosionproof type or of the purged type, approved for Class I and the proper group.[7] In Class I, Division 2 locations, lamps that operate above the ignition temperature of the gas must have explosionproof or purged enclosures.[8]

Types of protection

NFPA 496, as described in the handbook, distinguishes three types of purging by the change in classification they achieve. Type X purging reduces the classification within the enclosure from Division 1 to nonhazardous. Type Y purging reduces it from Division 1 to Division 2. Type Z purging reduces it from Division 2 to nonhazardous.[5][3] The details of each method are given in NFPA 496 itself, which the handbook does not reproduce.[5]

Three panels showing Type X from Division 1 to nonhazardous, Type Y from Division 1 to Division 2 and Type Z from Division 2 to nonhazardous
Type X, Y and Z purging under NFPA 496.

The handbook gives Type X as the required type for the control room of an oilseed extraction plant, where computers that are not built for Division 1 are placed in a Division 1 building.[4] Where a Division 1 area is pressurised to Division 2 and contains equipment that is itself protected by pressurisation, the handbook calls this "double pressurization"; the two protective gas supplies must then be independent.[1]

Requirements in US practice

The handbook (Milatovich, 2008) describes the US requirements for pressurising systems as they stood around 2007 and 2008, without naming the code or standard they come from or its edition. The protected enclosure must be kept at a positive pressure of at least 25 Pa (0.1 in. of water) above the surrounding atmosphere while the protected equipment operates.[1] If the pressure is not maintained, a device such as an indicator, alarm, cutoff or interlock switch must warn the user or automatically disconnect power from ignition-capable equipment. The type of device depends on the type of pressurisation, and an alarm must show a failure of the protective gas supply.[1]

Electric motors need at least 10 enclosure volumes of air while a positive internal pressure of at least 25 Pa (0.1 in. of water) is maintained. This is needed to purge the voids between the windings properly.[1] For enclosures in general, the protective measures consist of supplying clean air or an inert gas at a flow and positive pressure sufficient to achieve and then maintain a safe atmosphere.[2]

The protective gas itself must be essentially free of contaminants and may contain no more than trace amounts of flammable gas or vapour. Air of normal instrument quality, nitrogen or another nonflammable gas is acceptable.[1] The piping must be protected against mechanical damage. If compressed air is used, the compressor intake must be in an unclassified location. An intake line that passes through a classified location must be noncombustible, protected against damage and corrosion, and designed so that flammable gases, vapours or dusts cannot leak into it.[1] The blower or compressor must be powered from a separate source or from the supply of the protected enclosure ahead of any service disconnect.[1]

Electrical enclosure in a hazardous area kept at 25 Pa overpressure by clean air from a compressor with its intake in an unclassified area
Pressurising system for an electrical enclosure in a hazardous location.

Rotating machines need a further safeguard. This applies to motors, generators and other rotating machines protected by a pressurising or protective gas design. No external surface may exceed 80 percent of the ignition temperature of the gas or vapour, both in degrees Celsius. The ignition temperature is determined by ASTM E659.[1] Heat sensors must detect any temperature rise beyond the design limits and automatically de-energise the equipment. These detectors work without the protection of positive pressure, so in a Class I, Division 1 location they must themselves be explosionproof or intrinsically safe.[1]

For hexane, with an autoignition temperature of 225 °C, the 80 percent rule limits the external surfaces to 180 °C. For diethyl ether, with an autoignition temperature of 160 °C, the limit is 128 °C.[9][1]

Purging calculations

The amount of purge gas needed depends on how well it mixes with the gas already in the enclosure. If the purge gas could push the original gas out without mixing, the amount needed would follow from simple displacement. In practice the two gases mix, so part of the purge gas leaves with the mixture it is meant to replace.[10] For a well-mixed space, where the concentration is the same everywhere, Beyler (2002b) gives the concentration of the original flammable gas after a volume of purge gas has been added:[11]

C=C0exp⁡(−VNV)

Symbol Description Unit
C Concentration of the flammable gas after purging vol %
C0 Initial concentration of the flammable gas vol %
VN Volume of purge gas added m³
V Volume of the enclosure or room m³

The ratio VN/V is the number of enclosure volumes of purge gas. Each volume lowers the concentration by a factor e, about 2.7, so the concentration falls exponentially with the purge volume. Rearranged, the volume needed to reach a target concentration is VN=−Vln⁡(C/C0).[11]

Worked example 1. Beyler (2002b) considers a 200 m³ room in which a methane leak has raised the concentration to 30 percent by volume. To avoid a flammable mixture when air is later admitted, nitrogen must first lower the methane concentration to 13 percent.[10] If the original mixture could be removed without mixing, 113 m³ of nitrogen would be enough. With complete mixing the equation gives VN=−200ln⁡(13/30)≈167 m³, about 48 percent more.[10][11] The gas leaving the room still contains methane and may burn when it mixes with air, so ignition sources must be kept away from the exhaust, or the exhaust must also be inerted.[11]

Worked example 2. The same model puts into perspective the 10 volumes of air that the handbook requires for motors.[1] Assume a motor enclosure filled with hexane vapour at 6.9 percent, the upper end of its flammable range of 1.2 to 6.9 percent.[12] In a perfectly mixed enclosure, about 1.75 volumes would bring the concentration down to the lower limit of 1.2 percent. Ten volumes reduce it by a factor of about 22,000, to roughly 3 ppm.[11] The handbook links the 10-volume rule to the need to purge the voids between the windings, which the well-mixed model does not represent.[1]

Line chart of hexane concentration against purge volumes on a log scale, falling from 6.9 percent to about 3 ppm after 10 volumes
Hexane concentration in a well-mixed enclosure against the number of purge volumes.

Process vessels can also be purged in batches rather than by a continuous flow. In vacuum purging the pressure is lowered from P1 to P2 and then restored with inert gas, so that a fraction X=P2/P1 of the original gas remains. After n cycles the fraction is Xn.[6] Evacuating a vessel from 100 kPa to 20 kPa absolute leaves 0.2 of the original gas per cycle and 0.008 after three cycles. Both relations assume that the gas in the vessel is well mixed.[6]

Applications

Control rooms are a typical use. In an oilseed solvent extraction plant, programmable logic controllers and computers are now often placed in the control room of the extraction building. They are not built for Class I, Groups C and D, Division 1. Kingsbaker (2008) states that such a control room must then be designed in accordance with NFPA 496, using Type X purging to reduce the classification inside from Division 1 to nonhazardous.[4] In the same plants the solvent is hexane, whose vapour and air mixture passes through its flammable range when the extractor is started up.[12]

The method is also important for the gases whose flames pass through the narrowest gaps. Most flammable gases are in Group C or Group D, for which electrical equipment allows the largest joint gaps. Acetylene is in Group A and hydrogen in Group B, and because little equipment is available for these groups, equipment where they are used might have to be purged and pressurised.[13] In mining and mineral processing, electrical switch rooms and control rooms are pressurised to keep dust or gas out.[14]

Whole rooms can be protected in a similar way by ventilation. Ural and Garzia (2008) note that a continuous supply of clean air can either sweep away contaminants or keep a room or process space under constant positive pressure, so that flammable materials are excluded. NFPA 69, Standard on Explosion Prevention Systems, contains guidance on the concentration control design of such ventilation systems in its Appendix D.[6] A related idea is the purge cycle at the start of a gas turbine, which leaves a nonflammable atmosphere in the turbine and exhaust system before ignition.[15]

Relation to inerting

Purging an electrical enclosure and inerting a process vessel use the same gases and the same dilution principles, but they have different aims. Inerting keeps the oxygen concentration below the limiting oxygen concentration, so that premixed burning cannot occur, while a purged electrical enclosure aims to keep the flammable gas out.[16][6] The design of inerting systems is covered by NFPA 69, whose 2008 edition lists limiting oxidant concentrations for many gases, metals and dusts, as summarised by Ural and Garzia (2008).[6]

Nitrogen is the most common inerting gas.[6] Because oxygen is essential to life, inert gas systems carry a risk for personnel. Ural and Garzia (2008) point to the US OSHA rules for entry into protected equipment, and to the hidden risk of inert gas leaking into unventilated areas.[6]

Purging does not guarantee safety under all conditions. Kingsbaker (2008) warns that inert gas purging of an extractor that has failed while full of solvent-laden flakes does not ensure a nonflammable condition. Such an extractor is purged with air from a sparkproof purge blower. For a normal shutdown, steam purging is described as a surer method than inert gas purging for removing solvent vapour.[12] The term pressurisation is also used in smoke control, where a smoke management system can keep an area free of smoke by overpressure.[17] That use concerns smoke movement in buildings, not the exclusion of flammable gas from electrical equipment.

Limits of the sources

The requirements above describe US practice as summarised in the 2008 handbook. The handbook does not give the purge flow rates, purge times or detailed rules of NFPA 496 for Types X, Y and Z, and it names no edition of NFPA 496.[5][1] The dilution model of Beyler (2002b) assumes that the space is well mixed, so that the concentration is the same everywhere. For motors, the handbook relates the large purge volume to the voids between the windings.[11][1]

See also

Notes

  1. ↑ 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 1.10 1.11 1.12 1.13 1.14 1.15 1.16 1.17 1.18 1.19 Milatovich (2008), p. 8-171.
  2. ↑ 2.0 2.1 2.2 2.3 2.4 Milatovich (2008), p. 8-172.
  3. ↑ 3.0 3.1 3.2 Ural and Garzia (2008), p. 17-151.
  4. ↑ 4.0 4.1 4.2 Kingsbaker (2008), p. 9-138.
  5. ↑ 5.0 5.1 5.2 5.3 5.4 Ural and Garzia (2008), p. 17-150.
  6. ↑ 6.0 6.1 6.2 6.3 6.4 6.5 6.6 6.7 6.8 Ural and Garzia (2008), p. 17-149.
  7. ↑ Milatovich (2008), p. 8-169.
  8. ↑ Milatovich (2008), p. 8-170.
  9. ↑ Milatovich (2008), p. 8-165.
  10. ↑ 10.0 10.1 10.2 Beyler (2002b), p. 2-180.
  11. ↑ 11.0 11.1 11.2 11.3 11.4 11.5 Beyler (2002b), p. 2-181.
  12. ↑ 12.0 12.1 12.2 Kingsbaker (2008), p. 9-137.
  13. ↑ Lemoff and Rivkin (2008), p. 7-41.
  14. ↑ L. J. Moore (2008), p. 9-217.
  15. ↑ Biggins (2008), p. 8-108.
  16. ↑ Beyler (2002b), p. 2-179.
  17. ↑ Van Rossum (2027), §6.6.

References

  • Beyler, C. L. (2002b). Flammability limits of premixed and diffusion flames. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-172–2-187). National Fire Protection Association; Society of Fire Protection Engineers.
  • Biggins, J. B. (2008). Stationary combustion engines and fuel cells. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-105–8-111). National Fire Protection Association.
  • Kingsbaker, C. L. (2008). Oilseed solvent extraction plants. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-131–9-140). National Fire Protection Association.
  • Lemoff, T. C., & Rivkin, C. H. (2008). Storage of gases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-35–7-42). National Fire Protection Association.
  • Milatovich, R. M. (2008). Electrical systems and appliances. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-127–8-173). National Fire Protection Association.
  • Moore, L. J. (2008). Mining and mineral processing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-203–9-223). National Fire Protection Association.
  • Ural, E. A., & Garzia, H. W. (2008). Explosion prevention and protection. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-141–17-165). National Fire Protection Association.
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.