Textile flammability is the tendency of fibres, yarns, fabrics and textile products such as clothing, curtains and upholstery to ignite, spread flame and release heat when exposed to a flame or other heat source. Almost all fibres are combustible, and textiles are so common that they are involved in many fires, deaths and injuries.[1] In United States statistics given in the 2008 edition of the Fire Protection Handbook, textiles were the first fuel ignited in typically 40 % or more of fatal structure fires.[1]
How a fabric burns depends on the fibre or blend, the weight and construction of the fabric, any flame retardant treatment and its orientation.[2] Cotton chars and burns readily, wool is harder to ignite, and thermoplastic fibres such as polyester and nylon shrink and melt away from a small flame.[3][4] Because no single test describes the whole hazard, flammability is measured with many end-use tests, from small flame tests on clothing and curtain fabrics to full room tests on wall coverings.[5][6] Most of these tests show only resistance to a small ignition source, and fabrics that pass them may still burn readily in a large fire.[2]
Definition and scope
Fibres are the basic components of all textiles. Natural fibres are cellulosic (from plants, most commonly cotton), protein (from animal hair) or mineral, such as mineral wool and glass fibre. Manufactured fibres are made by chemical processes.[3] Fibres are spun into yarns and woven or knitted into fabrics, or processed directly into nonwoven fabrics and battings. Fabrics are then often dyed and finished with chemicals that change their feel, lustre or resistance to flame and weather.[4]
The fire properties that vary between fabrics are ignitability, flame spread and heat release rates, total heat produced, heat shrinkage and ease of extinction.[2] The severity of the hazard of a fabric in a product such as a dress, curtain or carpet depends greatly on its ease of ignition and the speed of flame spread. The amount and rate of heat release, the tendency to melt and the quantity and composition of the smoke also count.[5]
Fire tests on textiles belong to the family of reaction to fire tests. These measure the fire properties of the material or product itself, and they are mainly associated with interior finish, furnishings, contents and consumer products.[7] In the United States, building codes regulate construction, while other codes regulate some furnishings and contents, such as upholstered furniture, mattresses, curtains and drapes.[8] Textile flammability therefore spans consumer products, interior finish and decorations, protective clothing and vehicle interiors.[9][10]
Textiles in fire statistics
Studies of fatal fires in the United States show that textiles provide the initial fuel for the largest share of fatal structure fires. These fires also make up about one-sixth of all structure fires.[1] Many start with a textile product and then spread rapidly to other combustibles, such as the foam plastic filling of textile-covered upholstered furniture.[1] The estimated number of structure fires with a textile as the material first ignited fell from 186,100 in 1980 to 63,100 in 2003, about two-thirds less.[3] The share of all fires and deaths showed no clear trend.[1] The table gives the main textile products first ignited in United States nonconfined structure fires, as annual averages for 1999–2003; the last column was calculated for this article.[11]
| Item first ignited | Fires per year | Civilian deaths per year | Deaths per 1,000 fires |
|---|---|---|---|
| Mattress or bedding | 19,100 | 460 | 24 |
| Clothing or wearing apparel | 14,100 | 190 | 13 |
| Upholstered furniture or vehicle seat | 11,900 | 560 | 47 |
| Floor covering, rug, carpet or mat | 4,900 | 80 | 16 |
| Curtain, blind, drapery or tapestry | 4,100 | 30 | 7 |
| All textile items | 80,300 | 1,550 | 19 |
Mattresses and bedding were the most frequent first items ignited, but the upholstered furniture or vehicle seat category had the most deaths. Among the listed categories, it also had the highest deaths per 1,000 fires. A upholstered furniture fire can penetrate deeply into the materials and smoulder for a long time, producing toxic gases and making extinguishment difficult.[12] In the NFPA statistics on home mattress and bedding fires cited by Stull and Chines (2008), 22 % were started by cigarettes and another 28 % by matches and lighters.[13]
How fibres and fabrics burn
Natural and manufactured fibres
Cotton consists of more than 90 % cellulose. The handbook gives an ignition temperature of 400 °C (752 °F), but also notes a literature value of about 255 °C (490 °F), possibly for aged cotton.[3][14] Plant fibres char but do not melt. Many cellulosic fibres are hollow, so each fibre carries its own air supply, which lets fire burrow deep into bales.[3]
Rayon, made from dissolved cellulose, chars and burns much like cotton.[15] Wool supports combustion only with difficulty: compared with cotton it is harder to ignite, burns more slowly and is easier to extinguish.[3] Measured by one method, the ignition temperatures of 14 fibre types ranged from 400 °C for cotton to 600 °C for wool.[14]
Acetate melts before burning and behaves more like the thermoplastic fibres than like cellulose.[15] Acrylic fibres char, intumesce and burn, and acrylics and nylon produce hydrogen cyanide when they burn.[4] Thermoplastic fibres such as nylon, olefin and polyester do not char. They shrink away from a heat source, melt, form holes or ablate, absorbing heat while they degrade.[4] Compared with cellulosic fabrics, thermoplastics are generally harder to ignite, and their flames travel more slowly or go out by themselves.[4] Glass, metal and carbon fibres resist heat and do not ignite, although a combustible coating can make a glass fabric support flaming.[4][14]
Blends, coatings and fabric weight
The fire behaviour of a fabric depends on the type of fibre, its percentage, the configuration of the fabric, its weight and its construction. A normal finish changes little unless it is a flame retardant.[2] Combinations can burn worse than their components. Thermoplastics burn readily when finishes or heavy dyeing stiffen them, so that they can no longer shrink away from the flame.[16] They also burn readily when blended with char-forming fibres: polyester/cotton blends burn more like 100 % cotton than like 100 % polyester.[16] Coated or laminated fabrics show the combustibility of both the coating and the fibres.[16]
Fabric weight is a major variable for curtains. In the curtain tests by Moore, reported by Babrauskas (2002b), specimens were ignited with a match along the bottom. Lightweight fabrics of about 125 g/m² gave peak heat release rates almost as high as heavy fabrics of about 300 g/m², but were much less able to ignite surrounding panels.[17] Heavy curtains burned about twice as long, and whether a curtain was open or closed made little difference.[17] A closed cotton curtain of 124 g/m², for example, reached a peak heat release rate of 188 kW and ignited one of ten panels. A closed acrylic curtain of 354 g/m² reached 1,177 kW and ignited eight.[17]
Orientation and garment design
Fabrics generally burn faster when vertical than when horizontal. The edge of a fabric ignites much more easily than its surface, because the flame can reach more than one side.[2] Upward spread is fast because the flame preheats the material above the burning part.[18] A pilot flame at the lower end of a window curtain may therefore cause rapid upward spread and fire growth, while the same flame at the top gives slow downward spread.[19]
The shape of a garment matters as much as its fabric. A full-length gown containing several yards of flammable fabric can be far more hazardous than a tightly fitting blouse of the same material.[9] The gown offers more fuel, touches ignition sources more easily and has oxygen on both sides, which speeds up flame spread.[9] Synthetic fabrics that shrink near their melting temperature can press against the skin. This removes the insulating air layer and greatly increases the heat transferred to the skin.[14] Thermoplastics should therefore not be used in garments meant to protect against heat, such as firefighter or industrial uniforms.[16][14]
Flame-retardant treatments
Chemical treatments reduce flammability in five ways, and one chemical usually works in more than one. They may release noncombustible gases that keep oxygen from the burning surface, or degradation products that react endothermically and interfere with chain reactions in the flame.[20] The chemical may itself decompose endothermically, or form a nonvolatile char or liquid that limits the oxygen and heat reaching the fabric. It may also form finely divided particles that change the combustion reactions.[20] No single system works for all fibres, and some treatments change other properties such as colour, absorbency and flexibility.[20]
Treatments can be durable or nondurable, and laundering and dry cleaning may reduce their effect.[2] Treatments for tents, awnings and other fabrics exposed to the weather must not leach out. Water-soluble treatments need renewal at frequent intervals, and paint on a treated fabric may lessen its flame resistance.[21] Because some businesses use ineffective or nonpermanent chemicals, Stull and Chines (2008) advise testing treated fabrics when the supplier is not of known reliability.[14]
The effect of a treatment is often expressed with the limiting oxygen index (LOI). This is the minimum volume concentration of oxygen in an oxygen–nitrogen mixture that just supports sustained burning of a vertical specimen ignited at its top.[14] Cotton has an LOI of 19 % and untreated wool 28 %, and treatment can raise them to 28 or 32 % and 32 or 34 % respectively.[20] Fibres used in firefighters' protective gear reach 29 (Kevlar), 30 (Nomex) and 38 to 49 (PBI).[20] Use of the LOI test for textiles has declined, because full-scale tests of the finished items are considered more reliable.[14]
Treatments only make fabrics resistant to ignition by small flames, and treated fabrics may burn readily in larger fires.[14][20] Protection against small flames also does not guarantee resistance to smouldering ignition by a cigarette. Flame-retardant treatment of cotton generally lowers its charring temperature but often decreases its resistance to cigarette ignition.[9]
Test methods
No individual test gives a complete evaluation of textile hazard, and in the United States of 2008 there were no nationally recognised methods for some of the hazards.[5] Textile tests differ in specimen orientation, flame type and size, the part of the fabric exposed and the exposure time. They also differ in what they measure, such as flame spread rate, char length, afterflame time or flame spread index.[22]
| Test method | Orientation | Flame and exposure | Measurement | Application |
|---|---|---|---|---|
| 16 CFR Part 1610 | 45 degrees | 16 mm butane flame on fabric face, 1 s | Rate of flame spread | Clothing textiles |
| 16 CFR Parts 1615 and 1616 | Vertical | 38 mm methane flame on cut edge, 3 s | Char length | Children's sleepwear |
| 16 CFR Part 1630 | Horizontal | Methenamine pill on fabric face | Char distance | Carpets and rugs |
| ASTM D6413 | Vertical | 38 mm methane flame on cut edge, 12 s | Afterflame, afterglow, char length | Flame-resistant textiles |
| NFPA 701 Method 1 | Vertical | Tapered Meker burner on cut edge, 45 s | Char length | Building fabrics |
| NFPA 701 Method 2 | Vertical | Burner on cut edge, 2 min | Char length | Outdoor fabrics |
| ASTM E84 | Horizontal | Series of gas burners on fabric face, 10 min | Flame spread index | Interior textiles |
Clothing and protective fabrics
In the United States, the Flammable Fabrics Act of 1953, amended in 1967, prohibits the sale of apparel fabrics classed as "highly flammable" under 16 CFR Part 1610.[5] The act followed serious fires involving rayon-pile fabric made into children's cowboy chaps and sweaters. The test is described in the Consumer Product Safety Commission standard for the flammability of clothing textiles.[9] In it, a 15.9 mm (5/8 in.) gas flame touches the face of a 50.8 by 152 mm (2 by 6 in.) specimen held at 45 degrees for 1 s. If the fabric ignites, the time for the flame to travel 127 mm (5 in.) classifies it.[5]
The test keeps inordinately flammable garments off the market. Pile fabrics such as cotton flannel passed it easily, yet gave much higher burn injury estimates on an instrumented mannequin than almost 60 other apparel fabrics.[5] The stricter vertical tests for nightwear are described in Children's sleepwear flammability.[22]
The principal flame resistance test for protective clothing is ASTM D6413. A 76.2 by 305 mm (3 by 12 in.) vertical specimen is held with its lower edge in a 38.1 mm (1.5 in.) methane flame for 12 s.[23][24] Afterflame time, afterglow time and char length are then recorded. For most primary protective clothing the char length may not exceed 102 mm (4 in.), with an afterflame time of 2 s or less, and fabrics that melt and drip are often prohibited.[24] Heat insulation is measured separately, for example in the thermal protective performance test at 84 kW/m².[25]

Curtains, wall coverings and bench-scale tests
In the United States, NFPA 701, Standard Methods of Fire Tests for Flame Propagation of Textiles and Films, is the test most often prescribed by regulators for curtains and draperies.[5] In the 2008 handbook, Method 1 applies to fabrics of 21 oz/yd² (712 g/m², rounded in the handbook to 700 g/m²) or less and uses a 45 s exposure to a tapered Meker burner.[26] Method 2 uses a 2 min exposure for heavier fabrics and outdoor uses.[26] NFPA 701 had recognised that two or three layers of curtain fabric, as often found in motels, may burn vigorously even when each single layer passes.[5] The NFPA 705 field test exposes a small sample to a wooden kitchen match for 12 s. It only screens materials, and a sample that does not ignite has not been shown to comply with any standard.[27]
Textile wall coverings are tested as interior finish. Some reach a flame spread index below 25 in the Steiner tunnel test, yet cause flashover within minutes in a room-corner test.[6] In the NFPA 265 room corner test the specimen lines two or three walls of a 3.66 by 2.44 by 2.44 m (12 by 8 by 8 ft) room. A corner burner runs at 40 kW for 5 min and then at 150 kW for 10 min.[28] A covering passes if flames do not reach the ceiling during the 40 kW stage, do not reach the outer edge of the specimen, form no burning droplets and cause no flashover.[28] NFPA 286 uses 160 kW in the second stage and adds limits of 800 kW on heat release rate and 1,000 m² on total smoke release.[28][29]
The cone calorimeter can also test fabrics. Thin fabrics used for air-supported structures are mounted taut over an air space that simulates their conditions of use.[30] European and international tests mostly follow ISO standards, with different burners, orientations and exposure times from the analogous United States tests.[10]
Requirements by end use
Buildings, decorations and tents
In the United States, as described by Miller and Roether (2008), drapes, hangings and similar decorations in an assembly occupancy must be fire retardant when tested to NFPA 701. This applies if they form a significant part of the decor or a continuous path for fire.[31] Untreated decorations can cause very rapid fire growth in crowded spaces, as in the 1942 Cocoanut Grove nightclub fire in Boston, in which 492 people died.[31] Free-hanging draperies count as decorations under NFPA 101 and are evaluated with NFPA 701, a test less severe than the tunnel test. A drapery fixed to a solid backing is treated as a textile wall covering.[32]
The codes described by Hirschler (2008b) give three options for textile wall coverings: sprinklers with a Class A tunnel rating, a pass in NFPA 265, or a pass in NFPA 286.[6][29] NFPA 101, which applies to existing buildings, does not permit the NFPA 286 option. Textile ceiling coverings may not use NFPA 265, because its burner flame does not reach the ceiling.[29] The International Fire Engineering Guidelines (2005) quote section 803.5 of the United States International Building Code. It accepts interior finishes "other than textiles" that meet the NFPA 286 criteria where a Class A rating is required.[33]
NFPA 102 requires the textiles of tents and air-supported structures used for assembly and similar purposes to meet NFPA 701.[10] Permanent and temporary membrane structures must use flame-resistant membranes tested to NFPA 701, and all membranes are tested in weathered condition.[34] In New Zealand, Verification Method C/VM2 (second edition, 2025) limits the flammability index of suspended flexible fabrics. Fabrics used as underlay to cladding or roofing and exposed to view in occupied spaces other than household units may not exceed 5.[35] Suspended flexible fabrics and membrane structures may not exceed 12 in exitways from sleeping spaces and in occupied spaces within crowd uses.[35] The 2013 commentary on the first edition explains that the index comes from the AS 1530 Part 2 flammability test.[36]
Furniture, bedding and protective clothing
The cover fabric strongly affects the fire of an upholstered item. In tests at NIST, substituting cotton for polyolefin cover fabric on a chair lowered its peak heat release rate from 2 MW to 700 kW.[37] In the United States, 16 CFR Part 1632 tests mattresses with smouldering cigarettes.[12] The newer 16 CFR Part 1633 exposes a whole mattress to two T-shaped gas burners that simulate burning bedclothes. Its peak heat release rate may not exceed 200 kW, and the heat released in the first 10 min may not exceed 15 MJ.[26] These tests are discussed under mattress flammability.
Clothing for thermal hazards is divided into primary protective clothing, where exposure is likely, and secondary protective clothing, where exposure is incidental. Firefighter turnout gear is an example of the first, and petrochemical workers' uniforms of the second.[13] In structural firefighting protective clothing, every layer must resist flame and heat, and the composite must also insulate the wearer.[13] For workers exposed to a flash fire, early studies found that most injuries came from the continued burning of their clothing rather than from the flash fire itself.[13] Garments that resist ignition during the short flash therefore give a much larger safety margin.[13]
Vehicles and oxygen-enriched atmospheres
Materials in the occupant compartments of United States motor vehicles may not burn faster than 102 mm (4 in.) per minute in a horizontal test, which the handbook regards as only minimum protection.[10] In an oxygen-enriched atmosphere, clothing presents a high fire hazard.[21] Cotton and wool clothing fabrics can be ignited by a spark of 2.3 J in 100 % oxygen, whereas in normal air at least 193 J is needed.[38] Flame-retardant additives have been found effective for many materials in atmospheres with up to 30 to 35 % oxygen.[38] Fabrics for hospital operating rooms and other atmospheres with flammable gas should be electrically conductive, so that static charge cannot build up into an igniting spark.[21]
Limitations and uncertainty
Most descriptions of textile burning behaviour come from small-scale tests. These may mislead when large fires or strong radiation sources are involved, and fabrics considered flame retardant may then burn readily.[2] Traditional pass/fail tests also cannot assess heat release, which sets the intensity of a fire.[8] Results depend strongly on the test arrangement. The tunnel test mounts wall coverings horizontally, which is unrealistic, and coverings that pass it may still cause flashover in a room.[28][6]
Laboratory rankings do not always match injuries. Flame spread rates measured on the remains of garments from real incidents did not correlate with the size of the victims' burns.[23] Treatments may lose their effect through laundering, dry cleaning or weathering, so a fabric that passed when new may not pass in service.[2][21] The requirements in this article describe United States practice as reported in the 2008 handbook and New Zealand practice in 2013 and 2025. NFPA 702, a former apparel standard described in the handbook, had already been withdrawn by 2008.[5]
See also
- Aircraft cabin fire
- Burn injury
- Flooring radiant panel test
- Methenamine pill test
- Tent and membrane structure
Notes
- ↑ 1.0 1.1 1.2 1.3 1.4 Stull and Chines (2008), p. 6-75.
- ↑ 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 Stull and Chines (2008), p. 6-81.
- ↑ 3.0 3.1 3.2 3.3 3.4 3.5 Stull and Chines (2008), p. 6-76.
- ↑ 4.0 4.1 4.2 4.3 4.4 4.5 Stull and Chines (2008), p. 6-79.
- ↑ 5.0 5.1 5.2 5.3 5.4 5.5 5.6 5.7 5.8 Stull and Chines (2008), p. 6-89.
- ↑ 6.0 6.1 6.2 6.3 Hirschler (2008b), p. 18-35.
- ↑ Hirschler (2008a), p. 6-37.
- ↑ 8.0 8.1 Hirschler (2008a), p. 6-35.
- ↑ 9.0 9.1 9.2 9.3 9.4 Stull and Chines (2008), p. 6-86.
- ↑ 10.0 10.1 10.2 10.3 Stull and Chines (2008), p. 6-98.
- ↑ 11.0 11.1 Stull and Chines (2008), p. 6-78.
- ↑ 12.0 12.1 Stull and Chines (2008), p. 6-88.
- ↑ 13.0 13.1 13.2 13.3 13.4 Stull and Chines (2008), p. 6-87.
- ↑ 14.0 14.1 14.2 14.3 14.4 14.5 14.6 14.7 14.8 Stull and Chines (2008), p. 6-84.
- ↑ 15.0 15.1 Stull and Chines (2008), p. 6-77.
- ↑ 16.0 16.1 16.2 16.3 Stull and Chines (2008), p. 6-83.
- ↑ 17.0 17.1 17.2 Babrauskas (2002b), p. 3-15.
- ↑ Van Rossum (2027), §4.3.
- ↑ Iqbal and Salley (2004), p. 6-3.
- ↑ 20.0 20.1 20.2 20.3 20.4 20.5 Stull and Chines (2008), p. 6-85.
- ↑ 21.0 21.1 21.2 21.3 Stull and Chines (2008), p. 6-99.
- ↑ 22.0 22.1 22.2 Stull and Chines (2008), p. 6-90.
- ↑ 23.0 23.1 Stull and Chines (2008), p. 6-91.
- ↑ 24.0 24.1 Stull and Chines (2008), p. 6-92.
- ↑ Stull and Chines (2008), p. 6-93.
- ↑ 26.0 26.1 26.2 Stull and Chines (2008), p. 6-94.
- ↑ Madrzykowski and Stroup (2008), p. 2-35.
- ↑ 28.0 28.1 28.2 28.3 Stull and Chines (2008), p. 6-96.
- ↑ 29.0 29.1 29.2 Hirschler (2008b), p. 18-36.
- ↑ Babrauskas (2002a), p. 3-72.
- ↑ 31.0 31.1 Miller and Roether (2008), p. 20-93.
- ↑ Hirschler (2008b), p. 18-37.
- ↑ National Research Council of Canada et al. (2005), p. 0.2-10.
- ↑ Holmes (2008b), p. 20-223.
- ↑ 35.0 35.1 Ministry of Business, Innovation and Employment (2025b), p. 51.
- ↑ Ministry of Business, Innovation and Employment (2013), p. 145.
- ↑ Babrauskas (2002b), p. 3-29.
- ↑ 38.0 38.1 Rosales and Stoltzfus (2008), p. 9-230.
References
- Babrauskas, V. (2002a). The cone calorimeter. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-63–3-81). National Fire Protection Association; Society of Fire Protection Engineers.
- Babrauskas, V. (2002b). Heat release rates. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-1–3-37). National Fire Protection Association; Society of Fire Protection Engineers.
- Hirschler, M. M. (2008a). Concepts and protocols of fire testing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-35–6-60). National Fire Protection Association.
- Hirschler, M. M. (2008b). Interior finish. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 18-23–18-42). National Fire Protection Association.
- Holmes, W. D. (2008b). Occupancies in special structures. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-217–20-226). National Fire Protection Association.
- Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
- Madrzykowski, D., & Stroup, D. W. (2008). Flammability hazard of materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-31–2-48). National Fire Protection Association.
- Miller, G., & Roether, E. (2008). Assembly occupancies. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-85–20-95). National Fire Protection Association.
- Ministry of Business, Innovation and Employment. (2013). Commentary for Building Code clauses C1–C6 and Verification Method C/VM2.
- Ministry of Business, Innovation and Employment. (2025b). Verification Method C/VM2: Framework for fire safety design (2nd ed.).
- National Research Council of Canada, International Code Council, Department of Building and Housing, & Australian Building Codes Board. (2005). International fire engineering guidelines (2005 ed.). Australian Building Codes Board.
- Rosales, K., & Stoltzfus, J. M. (2008). Oxygen-Enriched atmospheres. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-225–9-243). National Fire Protection Association.
- Stull, J. O., & Chines, S. A. (2008). Fibers and textiles. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-75–6-102). National Fire Protection Association.
- Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.