The expansion tank takes up the expansion and contraction of the fluid as the system heats and cools. It usually sits at the highest point near the heater and provides a constant hydraulic head.<ref name="LB-8-67" /> In systems operating above the fluid's boiling point the tank is normally pressurised with an inert gas blanket. Below the boiling point it may be vented to atmosphere. The tank is the point of lowest pressure, so light hydrocarbons from fluid degradation collect there.<ref name="LB-8-67" /><ref name="LB-8-68" /> Breather vents must discharge to a safe place outside the building. Emergency overflow lines should ideally return to the system's storage tank.<ref name="LB-8-68" />
The expansion tank takes up the expansion and contraction of the fluid as the system heats and cools. It usually sits at the highest point near the heater and provides a constant hydraulic head.<ref name="LB-8-67" /> In systems operating above the fluid's boiling point the tank is normally pressurised with an inert gas blanket. Below the boiling point it may be vented to atmosphere. The tank is the point of lowest pressure, so light hydrocarbons from fluid degradation collect there.<ref name="LB-8-67" /><ref name="LB-8-68" /> Breather vents must discharge to a safe place outside the building. Emergency overflow lines should ideally return to the system's storage tank.<ref name="LB-8-68" />
[[File:fse-heat-transfer-fluid-system-v5.jpg|thumb|upright=1.5|alt=Packaged fuel-fired thermal oil heater with burner, insulated piping and expansion tank above|Fuel-fired heater of a heat transfer fluid system. Based on LeBlanc (2008), pp. 8-67–8-68.]]


== Fire and explosion hazards ==
== Fire and explosion hazards ==

Revision as of 08:18, 8 November 2026

A heat transfer fluid system is a closed, recirculating system in which a liquid or vapour carries heat at a controlled rate from a heater to process equipment and back.[1][2] The term heat transfer fluid covers a broad range of media, from water and steam to molten salts.[3] The handbook chapter on heat transfer systems deals mainly with organic and synthetic fluids, which in the forest products industry are called thermal oil.[3][4] These fluids have high flash points and are hard to ignite at room temperature. In service, however, they are pumped through the plant well above their flash points and sometimes above their boiling points.[2] A leak can therefore produce a pool fire, a spray fire or, from a fluid above its boiling point, a flammable vapour or mist that can explode in an enclosed space.[2] Single losses have been very large: a 1995 fire at a sprinklered carpet mill in Georgia, United States, caused a gross loss of $400 million.[2] The Fire Protection Handbook (2008) bases its safeguards partly on NFPA 30. They cover location, interlocks, piping and sprinklers.[5]

Definition and uses

The handbook chapter on heat transfer systems defines the heat transfer fluid broadly. It is any of "a broad spectrum of liquid and vapor media used to transfer heat at a controlled rate from one place to another". The chapter then concentrates on the organic and synthetic fluids and on the safeguards they need.[3] Such systems were first associated with the chemical and petroleum industries. By 2008 they were also used in industries ranging from food, plastics and paper to commercial laundries.[3]

In the forest products industry the heat transfer fluid (HTF) is usually called thermal oil. It carries heat from the point of generation to the point of use, such as the hot presses of panel plants.[6][4] In Plastics processing, rolls and kneaders for compounding are heated with high-pressure steam or heat transfer fluids.[7] Barrel heating for moulding and extrusion is different. It runs at 149 to 343 °C (300 to 650 °F), and the upper part of that range is beyond what is practical for heat transfer fluids, so electric resistance heating is almost universally used.[8] An Industrial oven and furnace can also be heated by a thermal heat transfer fluid system. Its heat exchanger should then be kept free of combustibles such as lint.[9][10]

Types of system and fluid

There are two general types of system: liquid phase and vapour phase. In a liquid-phase system the fluid's temperature changes as it gives up heat, so temperatures are not uniform even at high circulation rates. In a vapour-phase system heat is transferred at the saturation temperature of the vapour, which gives controlled temperatures. Combinations of the two are also used.[3]

Water, as liquid or steam, is the most common heat transfer fluid. Between its freezing point and about 177 °C (350 °F) the choice is usually between water and steam. Above that temperature the vapour pressure of water rises rapidly and requires expensive high-pressure equipment.[3] A fluid with a high boiling point is then more practical. It should have a high flash point, be thermally stable and be noncorrosive.[11] Such fluids fall into three groups: molten salts, heat transfer oils, and specially formulated synthetic media.[11]

Molten salts are mostly used as heat absorbers to control exothermic reactions in chemical manufacture. The usual salt is a sodium and potassium mixture with a relatively low melting point. Because it is solid at room temperature, it must be kept above its melting point so that it does not plug the system, and it must be melted slowly at start-up. Many molten salts are strong oxidisers.[11] A sodium nitrate and sodium nitrite mixture used in indirect fired heaters can support the combustion of steel if the temperature is high enough and ignition occurs.[12]

Heat transfer oils are specially refined petroleum oils for use up to about 315 °C (600 °F). Above that temperature they crack excessively and form light hydrocarbons; some fluids do so even at normal operating temperature. The light ends collect in the expansion tank, and the tank's breather and emergency vents must be designed for them.[11] Petroleum oils also oxidise above 200 °C (392 °F) in contact with air. Synthetic fluids crack and oxidise as well, but they are noncorrosive and generally thermally stable when used as their makers recommend.[11] Some newer fluids have limited flammability or will not burn, but they are used mainly in refrigeration.[11][1]

Components

A recirculating system has a heater or vaporiser, a piping system and, in liquid-phase systems, an expansion tank. The heater or vaporiser supplies the heat that the fluid carries to the user equipment. The unit is called a heater when the fluid stays liquid and a vaporiser when it is used as vapour.[1] Fuel-fired units are generally built for heat duties above about 1 million Btu/h, which the handbook converts as 290 kW. Electric heaters usually serve smaller duties. Capacities range from less than 1 kW to more than 175 million Btu/h, given as 50,000 kW.[1]

The piping can form a single loop between heater and users, or primary and secondary loops. Control valves and emergency shutoff valves must be arranged so that the fluid can be isolated during a fire.[1]

The expansion tank takes up the expansion and contraction of the fluid as the system heats and cools. It usually sits at the highest point near the heater and provides a constant hydraulic head.[1] In systems operating above the fluid's boiling point the tank is normally pressurised with an inert gas blanket. Below the boiling point it may be vented to atmosphere. The tank is the point of lowest pressure, so light hydrocarbons from fluid degradation collect there.[1][2] Breather vents must discharge to a safe place outside the building. Emergency overflow lines should ideally return to the system's storage tank.[2]

Packaged fuel-fired thermal oil heater with burner, insulated piping and expansion tank above
Fuel-fired heater of a heat transfer fluid system. Based on LeBlanc (2008), pp. 8-67–8-68.

Fire and explosion hazards

The basic hazard follows from the operating conditions. Organic heat transfer fluids are high flash point liquids, circulated in closed piping while heated above their Flash point and sometimes above their boiling point.[2] At room temperature they are difficult to ignite. Like any combustible liquid heated to or above its flash point, they ignite and burn easily once released.[2] Because most systems run above the flash point, a loss of containment can quickly produce a pool or spray fire. Typical leak points are pumps and valves in the heater room, rotary joints at user equipment, and exposed piping anywhere in the plant.[2]

In the woodworking industry, a leak from a press system can release combustible liquid above its flash point as an atomised spray or as a rapidly expanding pool over large parts of the facility.[6] A spray of this kind can burn as a Jet fire. NUREG/CR-6850 (2005) is a fire risk methodology for US nuclear power plants. It characterises spray fires from a leak in a pressurised flammable liquid line by the leak rate and the length of the fuel jet, with the total inventory as a possible limit.[13] Burning oil can also flow horizontally across floors and equipment. The handbook notes that this makes a fire spread fast beyond its point of origin in a wood-processing plant.[14]

Fluids heated above their boiling points add an explosion hazard. A loss of containment can quickly release large quantities of flammable vapour or mist, which can produce a deflagration if ignited in an enclosed space. Depending on the amount released, the vapour or mist may spread well beyond the release area.[2] A release inside the heater creates an uncontrolled fire in the unit and can damage the heater or overheat the fluid. If the liquid level in a heater or vaporiser falls below the tops of the tubes, burner flames in direct-fired units can impinge on empty tubes. The local overheating causes deposits and finally tube failure.[2]

Leaks, insulation fires and self-heating

Heat transfer fluids generally have very low surface tension and low viscosity. They can therefore escape through small openings at pipe joints, even in a well-engineered system at high temperature and pressure.[2] Leaking oil soaks into common pipe insulation. The handbook warns that oil-soaked insulation can autoignite and carry fire along the piping.[2]

The SFPE Handbook describes a comparable mechanism under Self-heating. Liquids with very high flash points can ignite spontaneously at temperatures more than a hundred degrees below their flash points or their Autoignition temperature.[15] Its examples include hydraulic fluids with very high flash points that leak onto thermal lagging such as mineral wool or fibreglass, which has a particularly high surface area.[15] The handbook's safeguard is closed-cell, nonabsorbent insulation on heat transfer piping.[5] A related point applies to hot process piping in general: where it is insulated, flanges may have to be left bare.[16]

Typical fluid properties and a worked example

The handbook gives physical properties of common heat transfer fluids. The table below lists three of them, checked against the printed table.[1]

Fluid Boiling point Flash point Fire point
Diphenyl ether–diphenyl eutectic 257 °C (495 °F) 124 °C (255 °F) 135 °C (275 °F)
Partially hydrogenated terphenyl 366 °C (690 °F) 168 °C (335 °F) 191 °C (375 °F)
Aliphatic oil 382–510 °C (720–950 °F) 218 °C (425 °F) 246 °C (475 °F)

Two simple checks show how the hazard is judged. The first is the margin between the operating temperature and the flash point of the fluid: ΔTfp=Top−Tfp The second is the handbook's trigger for damage-limiting construction of the heater room. It applies when the fluid's flash point is below about 220 °C (425 °F) and the fluid is heated to or above its atmospheric boiling point:[5] Tfp<220 ∘CandTop≥Tb

Symbol Description Unit
Top maximum operating temperature of the fluid °C
Tfp flash point of the fluid, from the handbook table or the fluid data sheet °C
Tb atmospheric boiling point of the fluid °C
ΔTfp margin of the operating temperature above the flash point K

As a worked example, take the aliphatic oil at an assumed operating temperature of 315 °C, the approximate upper limit the handbook gives for heat transfer oils. It is then 97 K above its flash point and 69 K above its fire point, so any leak is readily ignitable.[11][1] Its boiling range starts at 382 °C, so it stays liquid and the damage-limiting construction trigger is not met. Now take the diphenyl eutectic in vapour-phase service at an assumed 260 °C. It is 136 K above its flash point and above its boiling point of 257 °C. Both conditions of the trigger are met, so the heater room would need damage-limiting construction.[5] The flash point margin itself has no limit in the source; it only shows that any release must be treated as ignitable.

Loss experience

The handbook gives three sets of loss data, all from United States sources. An industrial property insurer recorded 54 fire and explosion losses with organic or synthetic heat transfer fluids from 1981 to 1990. The gross total was $150,800,000, the average about $3 million and the median below $300,000.[2] Because the average is more than ten times the median, a few large losses evidently dominate the total. Smaller leaks also cause fires, but in a well-designed plant those losses stay well below a catastrophic level.[2]

A three-year study by one fluid manufacturer found 23 fires among its users and established the cause of 22. Operation or misoperation was the primary cause in 5 (23 percent), design in 5 (23 percent) and maintenance in 12 (54 percent).[2] One of the most common preventable causes was poor siting of breather vent and relief valve outlets, which discharged directly into plant areas.[2] In the 1995 Georgia carpet mill fire, a rotary coupling failed and released the fluid. The system was not shut down, and all of the heat transfer fluid was pumped into the fire.[2]

The handbook lists the unfavourable factors behind such losses. The fluid is virtually always well above its flash point. Systems often have large liquid holdups and high flow rates. Piping and user equipment run throughout the plant, often next to other important equipment or combustibles.[2] Many occupancies that now use these systems are low hazard and are not protected against a combustible liquid pool fire.[2]

Safeguards

The safeguards in the handbook are based in part on Section 7.4, "Recirculating Heat Transfer Systems", of NFPA 30, the US Flammable and Combustible Liquids Code. The handbook does not state the edition.[5] Ideally the heater or vaporiser stands away from important buildings. Inside such a building it should be cut off by a fire barrier wall of at least 2 hours, or 1 hour if sprinklers are provided.[5] Curbs, dikes, sloped floors and drainage limit the spread of a release around the heater, the expansion tank and the user equipment.[5]

The design recommendations aim to stop the flow of fuel quickly. They include an emergency drain line from the low points to a storage tank and interlocks that stop circulation in a fire. A clearly marked manual emergency shutoff switch should shut down the whole system. Breather vents should end in a safe place, and the fluid should not be used to heat buildings directly.[5] Oil-fired and gas-fired heaters follow NFPA 31, NFPA 54 or NFPA 85. Interlocks should sound an alarm and shut off the fuel on any of six conditions. These are low flow through the tubes, high outlet temperature or pressure, low system pressure, low expansion tank level, low vaporiser level, or sprinkler flow.[5]

Piping should run underground, outside or in floor trenches where practical, with welded joints throughout. Above 15 psig (1 bar gauge) it should meet ANSI/ASME B31, and copper, cast iron and plastic pipe should be avoided.[5] Areas with a heater or vaporiser should have automatic sprinklers designed to NFPA 13 for an Extra Hazard Group 1 occupancy. Sprinklers are also advisable wherever the system's equipment or piping runs. Where steam or inert gas is available, a manual smothering system for the firebox is advisable.[5] Leaks should be corrected promptly, interlocks inspected and tested every year, and operators trained to recognise upset conditions.[5]

For wood products plants in the United States, the handbook (2008) describes NFPA 664, without stating its edition, as giving detailed criteria for thermal oil systems. It allows a prescriptive or a performance-based design. The performance-based route assesses the "largest credible spill" from the oil quantity, maximum flow, instrumentation, shutdown interlocks, trained staff and plant layout. The result sets the spill area and the suppression capacity needed.[4] In risk indexing, the Dow Fire and Explosion Index lists a "hot oil heat exchange system" among its special process hazards. Its penalty factor ranges from 0.15 to 1.15 on a base factor of 1.00.[17]

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 LeBlanc (2008), p. 8-67.
  2. ↑ 2.00 2.01 2.02 2.03 2.04 2.05 2.06 2.07 2.08 2.09 2.10 2.11 2.12 2.13 2.14 2.15 2.16 2.17 2.18 2.19 LeBlanc (2008), p. 8-68.
  3. ↑ 3.0 3.1 3.2 3.3 3.4 3.5 LeBlanc (2008), p. 8-65.
  4. ↑ 4.0 4.1 4.2 Cholin (2008d), p. 9-15.
  5. ↑ 5.00 5.01 5.02 5.03 5.04 5.05 5.06 5.07 5.08 5.09 5.10 5.11 LeBlanc (2008), p. 8-69.
  6. ↑ 6.0 6.1 Cholin (2008d), p. 9-9.
  7. ↑ Ouellette (2008), p. 9-58.
  8. ↑ Ouellette (2008), p. 9-62.
  9. ↑ Ostrowski (2008a), p. 8-74.
  10. ↑ Ostrowski (2008a), p. 8-76.
  11. ↑ 11.0 11.1 11.2 11.3 11.4 11.5 11.6 LeBlanc (2008), p. 8-66.
  12. ↑ Schwab (2008a), p. 8-24.
  13. ↑ Nowlen et al. (2005b), p. 11-19.
  14. ↑ Cholin (2008d), p. 9-18.
  15. ↑ 15.0 15.1 Gray (2002), p. 2-224.
  16. ↑ Schwab (2008a), p. 8-22.
  17. ↑ Watts (2002), p. 5-130.

References

  • Cholin, J. M. (2008d). Woodworking facilities and processes. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-3–9-25). National Fire Protection Association.
  • Gray, B. (2002). Spontaneous combustion and self-heating. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-211–2-228). National Fire Protection Association; Society of Fire Protection Engineers.
  • LeBlanc, J. A. (2008). Heat transfer systems and fluids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-65–8-70). National Fire Protection Association.
  • Nowlen, S. P., Najafi, B., Wyant, F. J., Forester, J., Kazarians, M., Kolaczkowski, A., Joglar, F., Funk, D., Hannaman, G., & Anoba, R. (2005b). EPRI/NRC-RES fire PRA methodology for nuclear power facilities: Vol. 2. Detailed methodology (NUREG/CR-6850; EPRI 1011989). Electric Power Research Institute; U.S. Nuclear Regulatory Commission, Office of Nuclear Regulatory Research.
  • Ostrowski, R. (2008a). Industrial and commercial heat utilization equipment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-71–8-92). National Fire Protection Association.
  • Ouellette, G. (2008). Plastics industry and related process hazards. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-53–9-65). National Fire Protection Association.
  • Schwab, R. F. (2008a). Chemical processing equipment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-17–8-29). National Fire Protection Association.
  • Watts, J. M., Jr. (2002). Fire risk indexing. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 5-125–5-142). National Fire Protection Association; Society of Fire Protection Engineers.