In the ''Fire Protection Handbook'', creosote in chimney systems means the tarry brown or hard black internal deposits produced by burning wood.<ref name="GW-10-52" /> Burning wood releases complex hydrocarbons that can condense and accumulate on the inside of the connector and the chimney.<ref name="GW-10-52" /> The same chapter describes creosote as a collection of tars and other hydrocarbons produced by the pyrolytic distillation of wood.<ref name="GW-10-24" /> Cholin (2008c) adds that wood burned with little or no air produces charcoal, carbon monoxide and condensable yet combustible vapours, which are called creosote in the aggregate.<ref name="CH-6-69">Cholin (2008c), p. 6-69.</ref> The word also names an oily wood preservative made from coal tar, which is a different product.<ref name="CH-6-66">Cholin (2008c), p. 6-66.</ref>
In the ''Fire Protection Handbook'', creosote in chimney systems means the tarry brown or hard black internal deposits produced by burning wood.<ref name="GW-10-52" /> Burning wood releases complex hydrocarbons that can condense and accumulate on the inside of the connector and the chimney.<ref name="GW-10-52" /> The same chapter describes creosote as a collection of tars and other hydrocarbons produced by the pyrolytic distillation of wood.<ref name="GW-10-24" /> Cholin (2008c) adds that wood burned with little or no air produces charcoal, carbon monoxide and condensable yet combustible vapours, which are called creosote in the aggregate.<ref name="CH-6-69">Cholin (2008c), p. 6-69.</ref> The word also names an oily wood preservative made from coal tar, which is a different product.<ref name="CH-6-66">Cholin (2008c), p. 6-66.</ref>


Wood burns in three stages: moisture is driven off, combustible gases are distilled out and leave charcoal, and the gases then burn above the glowing charcoal.<ref name="GW-10-11">Gore Willse (2008a), p. 10-11.</ref> Pyrolysis is the decomposition of a material by heating, in which large molecules break down into smaller ones and release pyrolysis gases.<ref name="VR-3.1">Van Rossum (2027), §3.1.</ref> Pyrolysis needs no oxygen, but combustion does, so the gases do not necessarily burn as soon as they are formed.<ref name="VR-3.1" /> Cellulosic materials such as wood decompose into small volatile compounds, char and high-molecular-weight semi-liquid materials known as tars.<ref name="BH-1-115">Beyler and Hirschler (2002), p. 1-115.</ref> Under ideal conditions these products burn in the flames. In a stove with limited air, part of them escapes and deposits on the stove, the connector and the chimney.<ref name="GW-10-24" />
Wood burns in three stages: moisture is driven off, combustible gases are distilled out and leave charcoal, and both the gases and charcoal then burn.<ref name="GW-10-11">Gore Willse (2008a), p. 10-11.</ref> Pyrolysis is the decomposition of a material by heating, in which large molecules break down into smaller ones and release pyrolysis gases.<ref name="VR-3.1">Van Rossum (2027), §3.1.</ref> Pyrolysis needs no oxygen, but combustion does, so the gases do not necessarily burn as soon as they are formed.<ref name="VR-3.1" /> Cellulosic materials such as wood decompose into small volatile compounds, char and high-molecular-weight semi-liquid materials known as tars.<ref name="BH-1-115">Beyler and Hirschler (2002), p. 1-115.</ref> Under ideal conditions these products burn in the flames. In a stove with limited air, part of them escapes and deposits on the stove, the connector and the chimney.<ref name="GW-10-24" />


This air-limited burning is a small-scale form of a [[ventilation-controlled fire]], in which the supply of oxygen, not the amount of fuel, governs combustion and unburned pyrolysis gases leave the fire.<ref name="VR-4.8">Van Rossum (2027), §4.8.</ref> Soot follows the same logic. It consists of tiny carbon particles that often form in diffusion flames.<ref name="IS-F-55">Iqbal and Salley (2004), p. F-55.</ref> Its production depends on the fuel and on the combustion conditions, such as temperature and oxygen supply, and better combustion gives less soot.<ref name="VR-6.2">Van Rossum (2027), §6.2.</ref> For well-ventilated burning of wood, Karlsson and Quintiere (2000), as cited in Van Rossum (2027, §6.2), give a soot yield of 0.015 kg/kg. Smothered fires give much higher yields.<ref name="VR-6.2" />
The oxygen limit has a parallel in a [[ventilation-controlled fire]] in a compartment: there, limited air supply governs combustion and can leave unburned pyrolysis gases.<ref name="VR-4.8">Van Rossum (2027), §4.8.</ref> Soot follows the same logic. It consists of tiny carbon particles that often form in diffusion flames.<ref name="IS-F-55">Iqbal and Salley (2004), p. F-55.</ref> Its production depends on the fuel and on the combustion conditions, such as temperature and oxygen supply, and better combustion gives less soot.<ref name="VR-6.2">Van Rossum (2027), §6.2.</ref> For well-ventilated burning of wood, Karlsson and Quintiere (2000), as cited in Van Rossum (2027, §6.2), give a soot yield of 0.015 kg/kg. Smothered fires give much higher yields.<ref name="VR-6.2" />


Operating habits matter more than the fuel itself. Airtight wood stoves operated with the draft controls restricted, or loaded with large amounts of fuel, can build up a significant layer of creosote in a short time.<ref name="GW-10-25" /> According to Gore Willse (2008a), the species and moisture content of the wood are not major determinants of the rate of build-up, but habits of stove operation are.<ref name="GW-10-25" /> A stove that is too large for the heating need tends to run as an air-limited, low-temperature fire, so correct sizing helps to limit creosote production.<ref name="GW-10-25" /> In solid-fuel add-on furnaces, the thermostat keeps a large charge of wood low and smouldering when the heating need is small, which produces a large amount of creosote.<ref name="GW-10-27">Gore Willse (2008a), p. 10-27.</ref> Open-front fireplaces without doors may not accumulate creosote rapidly.<ref name="GW-10-53" />
Wood-stove operating habits strongly affect creosote build-up. Airtight wood stoves operated with the draft controls restricted, or loaded with large amounts of fuel, can build up a significant layer of creosote in a short time.<ref name="GW-10-25" /> According to Gore Willse (2008a), the species and moisture content of the wood are not major determinants of the rate of build-up, but habits of stove operation are.<ref name="GW-10-25" /> A stove that is too large for the heating need tends to run as an air-limited, low-temperature fire, so correct sizing helps to limit creosote production.<ref name="GW-10-25" /> In solid-fuel add-on furnaces, the thermostat keeps a large charge of wood low and smouldering when the heating need is small, which produces a large amount of creosote.<ref name="GW-10-27">Gore Willse (2008a), p. 10-27.</ref> Open-front fireplaces without doors may not accumulate creosote rapidly.<ref name="GW-10-53" />


== Ignition and burning ==
== Ignition and burning ==
Line 31: Line 31:
For the handbook example, ''E'' = 128 MJ and ''t'' = 15 min = 900 s. This gives <math>\dot{Q}</math> = 128,000,000 J / 900 s ≈ 142,000 W, or about 140 kW, which matches the handbook value.<ref name="GW-10-55" /> The same layer burning off in 5 minutes would give about 430 kW, and in 30 minutes about 71 kW. A shorter burn gives a more intense fire, while a longer burn heats the chimney walls for longer and raises the chance of spread to the structure.<ref name="GW-10-52" />
For the handbook example, ''E'' = 128 MJ and ''t'' = 15 min = 900 s. This gives <math>\dot{Q}</math> = 128,000,000 J / 900 s ≈ 142,000 W, or about 140 kW, which matches the handbook value.<ref name="GW-10-55" /> The same layer burning off in 5 minutes would give about 430 kW, and in 30 minutes about 71 kW. A shorter burn gives a more intense fire, while a longer burn heats the chimney walls for longer and raises the chance of spread to the structure.<ref name="GW-10-52" />


The handbook rule of thumb for cleaning is a build-up of 6.4 mm (¼ in.), four times the thickness in the example.<ref name="GW-10-53" /> If the density of the deposit stayed the same, such a layer would hold about 510 MJ and release about 570 kW over 15 minutes. These rates are small compared with a burning sofa of about 2.5 MW.<ref name="VR-4.5" /> The heat is, however, released inside a narrow flue, and even a correctly assembled and installed chimney lacks the capability of repeatedly acting as a combustion chamber.<ref name="GW-10-52" />
The handbook rule of thumb for cleaning is a build-up of 6.4 mm (¼ in.), four times the thickness in the example.<ref name="GW-10-53" /> If the deposit had the same composition and density, and energy were approximated as proportional to layer thickness, it would hold about 510 MJ and release about 570 kW over 15 minutes. These rates are small compared with a burning sofa of about 2.5 MW.<ref name="VR-4.5" /> The heat is, however, released inside a narrow flue, and even a correctly assembled and installed chimney lacks the capability of repeatedly acting as a combustion chamber.<ref name="GW-10-52" />


{| class="wikitable"
{| class="wikitable"
Line 61: Line 61:
In 1999–2002, United States fire departments attended an estimated 10,600 confined chimney or flue fires in homes each year, 3 % of all home structure fires. They caused an estimated 10 civilian injuries and 7 million dollars of direct damage per year, about 600 dollars per fire. The estimated civilian deaths rounded to zero.<ref name="AE-3-74" /> The same table counts 53,700 home fires per year caused by heating equipment, so confined chimney fires made up about one fifth of the [[heating equipment fire]] total.<ref name="AE-3-74" /> One- and two-family dwellings accounted for an estimated 10,400 confined chimney or flue fires per year, 4 % of their structure fires.<ref name="LA-20-57">Lathrop (2008b), p. 20-57.</ref>
In 1999–2002, United States fire departments attended an estimated 10,600 confined chimney or flue fires in homes each year, 3 % of all home structure fires. They caused an estimated 10 civilian injuries and 7 million dollars of direct damage per year, about 600 dollars per fire. The estimated civilian deaths rounded to zero.<ref name="AE-3-74" /> The same table counts 53,700 home fires per year caused by heating equipment, so confined chimney fires made up about one fifth of the [[heating equipment fire]] total.<ref name="AE-3-74" /> One- and two-family dwellings accounted for an estimated 10,400 confined chimney or flue fires per year, 4 % of their structure fires.<ref name="LA-20-57">Lathrop (2008b), p. 20-57.</ref>


These numbers rest on inference as much as on observation. Abbreviated reports of confined fires capture little more than dispatch information. NFPA analysts therefore infer that some type of chimney was involved and that these fires started with creosote.<ref name="AE-3-66" /><ref name="AE-3-72">Ahrens et al. (2008), pp. 3-72–3-73.</ref> Hall and Ahrens (2002) note that in NFIRS up to version 4.1, the categories for chimneys and chimney connectors were not linked to the devices they served. Linking chimney fires to wood stoves or to fireplaces typically needed one-time special data collection.<ref name="HA-5-72">Hall and Ahrens (2002), pp. 5-72–5-73.</ref>
Some details in these data are inferred rather than directly recorded. Abbreviated reports of confined fires capture little more than dispatch information. The handbook's classification infers that a chimney was involved from the incident code and suggests creosote as a possible item first ignited; it does not establish creosote as the cause of every coded fire.<ref name="AE-3-66" /><ref name="AE-3-72">Ahrens et al. (2008), pp. 3-72–3-73.</ref> Hall and Ahrens (2002) note that in NFIRS up to version 4.1, the categories for chimneys and chimney connectors were not linked to the devices they served. Linking chimney fires to wood stoves or to fireplaces typically needed one-time special data collection.<ref name="HA-5-72">Hall and Ahrens (2002), pp. 5-72–5-73.</ref>


The raw count of fires coded as confined chimney or flue fires in NFIRS rose from 467 in 1999 to 12,006 in 2003.<ref name="AE-3-77">Ahrens et al. (2008), p. 3-77.</ref> Older NFIRS versions have no codes for confined fires, and some states still accepted them. The ease of abbreviated reporting may also have caused an artificial increase. Part of the rise may therefore reflect the new reporting system rather than a real increase in fires.<ref name="AE-3-66" />
The raw count of fires coded as confined chimney or flue fires in NFIRS rose from 467 in 1999 to 12,006 in 2003.<ref name="AE-3-77">Ahrens et al. (2008), p. 3-77.</ref> Older NFIRS versions have no codes for confined fires, and some states still accepted them. The ease of abbreviated reporting may also have caused an artificial increase. Part of the rise may therefore reflect the new reporting system rather than a real increase in fires.<ref name="AE-3-66" />

Revision as of 01:05, 8 November 2026

A chimney fire, also called a flue fire, is the burning of combustible deposits that have built up on the inner surfaces of a chimney flue or chimney connector.[1][2] The deposits are creosote, the tarry brown or hard black residue left by burning wood, and soot.[1][3] They form when wood burns with too little air, so that tars and other products of pyrolysis condense on the flue walls instead of burning in the flame.[4] Once ignited, the deposits burn at about 650 to 1100 °C (1200 to 2000 °F), and the fire can crack clay liners and brickwork, overheat the surrounding framing and carry sparks onto the roof.[1] In the United States in 1999–2002, fire departments attended an estimated 10,600 confined home chimney or flue fires per year, with estimated civilian deaths that rounded to zero.[2] Deposits build up quickly when airtight wood stoves and other solid-fuel heating appliances run with restricted air, so correct operation and regular chimney cleaning are the main defences.[5][6]

Creosote and soot deposits

In the Fire Protection Handbook, creosote in chimney systems means the tarry brown or hard black internal deposits produced by burning wood.[1] Burning wood releases complex hydrocarbons that can condense and accumulate on the inside of the connector and the chimney.[1] The same chapter describes creosote as a collection of tars and other hydrocarbons produced by the pyrolytic distillation of wood.[4] Cholin (2008c) adds that wood burned with little or no air produces charcoal, carbon monoxide and condensable yet combustible vapours, which are called creosote in the aggregate.[7] The word also names an oily wood preservative made from coal tar, which is a different product.[8]

Wood burns in three stages: moisture is driven off, combustible gases are distilled out and leave charcoal, and both the gases and charcoal then burn.[9] Pyrolysis is the decomposition of a material by heating, in which large molecules break down into smaller ones and release pyrolysis gases.[10] Pyrolysis needs no oxygen, but combustion does, so the gases do not necessarily burn as soon as they are formed.[10] Cellulosic materials such as wood decompose into small volatile compounds, char and high-molecular-weight semi-liquid materials known as tars.[11] Under ideal conditions these products burn in the flames. In a stove with limited air, part of them escapes and deposits on the stove, the connector and the chimney.[4]

The oxygen limit has a parallel in a ventilation-controlled fire in a compartment: there, limited air supply governs combustion and can leave unburned pyrolysis gases.[12] Soot follows the same logic. It consists of tiny carbon particles that often form in diffusion flames.[13] Its production depends on the fuel and on the combustion conditions, such as temperature and oxygen supply, and better combustion gives less soot.[14] For well-ventilated burning of wood, Karlsson and Quintiere (2000), as cited in Van Rossum (2027, §6.2), give a soot yield of 0.015 kg/kg. Smothered fires give much higher yields.[14]

Wood-stove operating habits strongly affect creosote build-up. Airtight wood stoves operated with the draft controls restricted, or loaded with large amounts of fuel, can build up a significant layer of creosote in a short time.[5] According to Gore Willse (2008a), the species and moisture content of the wood are not major determinants of the rate of build-up, but habits of stove operation are.[5] A stove that is too large for the heating need tends to run as an air-limited, low-temperature fire, so correct sizing helps to limit creosote production.[5] In solid-fuel add-on furnaces, the thermostat keeps a large charge of wood low and smouldering when the heating need is small, which produces a large amount of creosote.[15] Open-front fireplaces without doors may not accumulate creosote rapidly.[6]

Ignition and burning

The deposits ignite when the temperature in the flue becomes high enough.[1] The temperature and duration of the fire depend on the thickness and composition of the deposit, the oxygen supply, the type of appliance and the type of chimney.[1] One trigger named in the handbook is the burning of highly combustible solid material in a fireplace, such as a dried Christmas tree and its wrappings. The resulting high gas temperatures may ignite creosote deposits or damage the masonry.[16]

A chimney is built to create draft, a negative pressure that draws combustion air to the fuel and removes the products of combustion from the appliance and the building.[17] Draft is a form of the stack effect. Hot gas rises because it is less dense than the surrounding air, and a chimney strengthens the effect because the rising gas cannot mix sideways.[18] The same air supply governs a chimney fire. Once the doors and air dampers of a stove are closed, the burning rate in the chimney depends on the air that still reaches it.[1]

The energy stored in the deposits sets the size of the fire. The handbook gives the example of a creosote layer 1.6 mm (1/16 in.) thick in a 200 mm (8 in.) chimney 4.6 m (15 ft) high. This layer contains as much as 128 MJ (122,000 Btu) of fuel. If it burns off in 15 minutes, the gas temperature could reach 930 °C (1700 °F) at a heat release rate as high as 140 kW (488,000 Btu/h).[16] The average heat release rate during such a burn-off equals the energy released divided by the time over which it is released.[19] The relation assumes that the whole deposit burns, and it gives the average over the burning period, not the peak.

Q˙=Et

Symbol Description Unit
Q˙ Average heat release rate of the burning deposit W (kW)
E Energy stored in the deposit and released by burning J (MJ)
t Time in which the deposit burns off s

For the handbook example, E = 128 MJ and t = 15 min = 900 s. This gives Q˙ = 128,000,000 J / 900 s ≈ 142,000 W, or about 140 kW, which matches the handbook value.[16] The same layer burning off in 5 minutes would give about 430 kW, and in 30 minutes about 71 kW. A shorter burn gives a more intense fire, while a longer burn heats the chimney walls for longer and raises the chance of spread to the structure.[1]

The handbook rule of thumb for cleaning is a build-up of 6.4 mm (¼ in.), four times the thickness in the example.[6] If the deposit had the same composition and density, and energy were approximated as proportional to layer thickness, it would hold about 510 MJ and release about 570 kW over 15 minutes. These rates are small compared with a burning sofa of about 2.5 MW.[19] The heat is, however, released inside a narrow flue, and even a correctly assembled and installed chimney lacks the capability of repeatedly acting as a combustion chamber.[1]

Deposit (example chimney) Energy E Burn-off time t Average Q˙
1.6 mm layer 128 MJ 5 min 430 kW
1.6 mm layer 128 MJ 15 min 140 kW
1.6 mm layer 128 MJ 30 min 71 kW
6.4 mm layer (same density assumed) 510 MJ 15 min 570 kW

Effects on the chimney and the building

Brick chimneys with clay flue liners are a special case of masonry in fire, because the fire burns inside the flue and heats the masonry from within. Clay flue liners resist high temperatures quite well when these are applied gradually. A chimney fire, however, typically causes a very sudden temperature rise, so the hot inner surface of the liner expands against its cooler, inflexible outer part.[1] Longitudinal cracks in one or more liner sections are a frequent result. Such cracks can look closed when the chimney is cool and open up to measurable widths when later use heats the chimney again.[1] Intense fires can also crack the brickwork and transfer excessive heat through the walls to their outer surfaces.[1]

Whether the fire spreads to the building depends largely on its duration. Masonry chimneys have a large mass and therefore significant thermal inertia, so a short, intense chimney fire is less likely to overheat the structure than a longer one.[1] Thick or heavy deposits can burn long enough to raise the outer chimney surface to temperatures that ignite the surrounding structure.[1] Missing firestopping around chimneys does not start a fire, but a chase that encloses several chimneys without floors or internal framing provides an ideal passage for rapid vertical flame spread.[16]

The heat that reaches the framing also depends on the air space around the chimney. The 2008 handbook gives a minimum air space of 51 mm (2 in.) between combustibles and a residential or low-heat chimney inside a building, and 25 mm (1 in.) for one entirely outside.[20] These clearances must remain open air. A fill of insulation, even noncombustible insulation, hinders the dissipation of heat and can expose the framing to ignition.[20][21] At 260 °C (500 °F) on the outer brick surface, a 51 mm clearance is of little protective value, particularly with little ventilation airflow.[21]

A chimney fire also threatens the roof. The upward gas velocity can be high enough to carry sparks from the burning creosote and drop them on the roof.[1] Untreated wood shingles may be readily ignited by such small sparks.[22] A restrictive chimney cap combined with cracks or failed mortar can cause excessive leakage of hot gas at roof level, which endangers the rafters and roofing.[21] Spark arresters with square mesh openings of about 13 mm (½ in.) are desirable on chimneys for all solid fuels, because smaller openings clog quickly and larger ones let sparks through.[3]

Factory-built chimneys are tested with repeated flue gas temperatures up to 1149 °C (2100 °F) for up to 30 minutes, so they can be expected to survive a chimney fire in usable condition.[1] Gore Willse (2008a) warns that this should never simply be assumed. Chimney fires can exceed the test temperatures, and uneven heating can create unmanageable stresses in the metal.[1] Buckling of the liner after a fire is not uncommon. Minor buckling that still contains the flue gases allows further use, while more significant buckling requires replacement of at least the affected section.[1] A shiny, undiscoloured outer chimney generally indicates that structural damage to the building is unlikely, provided the chimney was installed at the correct clearance.[1]

Statistics and fire data

In the United States, a chimney fire that stays in the flue can be recorded as a confined fire in the National Fire Incident Reporting System (NFIRS). Version 5.0 of NFIRS expanded the incident type to three digits, which allowed a specific code for confined chimney fires.[23] Confined structure fires are small fires that are generally confined to a noncombustible container, with no flame damage beyond it. Fire departments may report them in abbreviated form, and losses, deaths and injuries rarely occur.[24]

In 1999–2002, United States fire departments attended an estimated 10,600 confined chimney or flue fires in homes each year, 3 % of all home structure fires. They caused an estimated 10 civilian injuries and 7 million dollars of direct damage per year, about 600 dollars per fire. The estimated civilian deaths rounded to zero.[2] The same table counts 53,700 home fires per year caused by heating equipment, so confined chimney fires made up about one fifth of the heating equipment fire total.[2] One- and two-family dwellings accounted for an estimated 10,400 confined chimney or flue fires per year, 4 % of their structure fires.[25]

Some details in these data are inferred rather than directly recorded. Abbreviated reports of confined fires capture little more than dispatch information. The handbook's classification infers that a chimney was involved from the incident code and suggests creosote as a possible item first ignited; it does not establish creosote as the cause of every coded fire.[24][26] Hall and Ahrens (2002) note that in NFIRS up to version 4.1, the categories for chimneys and chimney connectors were not linked to the devices they served. Linking chimney fires to wood stoves or to fireplaces typically needed one-time special data collection.[27]

The raw count of fires coded as confined chimney or flue fires in NFIRS rose from 467 in 1999 to 12,006 in 2003.[28] Older NFIRS versions have no codes for confined fires, and some states still accepted them. The ease of abbreviated reporting may also have caused an artificial increase. Part of the rise may therefore reflect the new reporting system rather than a real increase in fires.[24]

The long-term trend follows the use of wood heat. According to Gore Willse (2008a), residential cordwood stoves, furnaces and fireplaces have been the most prevalent form of solid-fuel use since the mid-1970s. Their rise was accompanied by a dramatic increase in heating-related home fires in the early 1980s.[9] Fires involving coal and wood stoves have dropped dramatically since then, and much of the improvement is attributed to more careful installation and operation.[29]

The problem is old. A fourteenth-century London ordinance required chimneys of tile, stone or plaster instead of wood.[30] In colonial Boston, householders who had a chimney fire paid a fine of 10 shillings, about 100 dollars in 2007, which encouraged them to keep their chimneys free from soot and creosote.[31]

Control and inspection after a fire

For wood-burning stoves and heaters with air dampers and doors, closing them to reduce the air supply is the best option to control a chimney fire.[1] Other appliances connected to the same chimney, or a barometric damper used for draft control, can still supply air and must also be closed.[1] Flare-type extinguishers, similar to road safety flares, release a cloud of extinguishing agent into the chimney, and the stove must stay closed so that the agent remains there.[6] In open-front fireplaces and fireplace stoves without doors, air control is difficult under fire conditions.[6] Because the fire may spread to the structure, the handbook advises that occupants be gathered and prepared to leave. The fire department is called at once to make sure the fire is completely extinguished.[6]

Gore Willse (2008a) recommends a thorough inspection of both masonry and factory-built chimneys after a suspected chimney fire. The flue surface is examined for cracks, holes, missing sections and distortion, using closed-circuit video equipment unless the chimney is very short.[1] The outer surface is checked for cracks, smoke leaks and major discolouration, and the surrounding combustibles for charring.[1] The chimney returns to service only after the necessary repairs.[1] A smoke test, as defined by Nolan (2000), checks the tightness of the flue. Smoke is generated in the fireplace or appliance with the chimney outlet covered, and leakage through the walls is then looked for.[32]

Prevention: inspection, cleaning and installation

In the United States, NFPA 211, as summarised in the 20th edition of the Fire Protection Handbook (2008), requires every chimney to be inspected at least once a year, whatever fuel the connected appliances burn.[6] The inspection covers the inner flue surface, for combustible deposits, cracks, gaps and softening, and the outer wall, for missing bricks or mortar and signs of leakage. It also confirms that no insulation or loose combustible material has fallen into the required air space.[6]

For chimneys that serve solid-fuel equipment, removing creosote is the most frequent maintenance task. A common rule of thumb treats a build-up of 6.4 mm (¼ in.) as the point at which cleaning is needed.[6] The rule fits soft, powdery or crusty deposits best. Smooth, gummy or hard tar-glaze may contain much more energy, so any thickness of tarry deposit calls for immediate cleaning.[6]

Loose deposits are removed with a stiff wire brush on rods, and harder ones with flat brushes, scrapers, rotating chains or, in extreme cases, chemicals. The handbook reserves mechanical and chemical cleaning for trained professional chimney service specialists.[6] NFPA 211 also requires repair, replacement or relining when the liner has softened, cracked or otherwise deteriorated so that it can no longer contain heat, moisture and flue gases.[6]

The handbook advises users of wood stoves to avoid long, extended burn cycles and large fuel loads, and it notes that add-on furnaces and their venting systems need frequent inspection and cleaning.[5][15] NFPA 211 prohibits the use of one chimney flue for both a solid-fuel appliance and an appliance burning another fuel.[15] In the 2000 edition of NFPA 211, factory-built chimneys for wood-burning appliances in one- and two-family dwellings had to meet the Type HT requirements of UL 103 or the Canadian 650 °C standard CAN/ULC-S629-M87.[21] Chimneys that serve only gas appliances have a different problem. Condensed moisture from the flue gases can slowly disintegrate the mortar, and liners made for gas appliance venting are often aluminium, which is unsuitable for the temperatures of general residential appliances.[3][33]

The same advice appears in other chapters of the handbook. Wood-burning fireplaces in bed-and-breakfast properties are typically used more often than in private homes. Annual cleaning and inspection of the flue can prevent creosote build-up and reveal blockages such as a nest.[34] In historic buildings, flues are to be examined for deteriorated mortar joints that could pass sparks or heat to wood framing, and lined and repointed before use.[35] Winter preparedness guidance includes an annual chimney inspection, and fire prevention inspection forms list unsafe masonry chimneys among common hazards.[36][37]

Limitations and misconceptions

A factory-built chimney that passed its high-temperature test is not certain to survive a chimney fire. The test covers repeated exposures of up to 30 minutes, and real fires can exceed its temperatures.[1] A masonry chimney that looks sound after a fire may also be damaged, because liner cracks can close when the chimney cools.[1] The 6.4 mm cleaning rule is easily misread, because a dense tar-glaze can fuel a more intense and longer fire than less dense deposits.[6]

Fewer chimney fires in one winter do not prove that a prevention programme works. A severe winter increases stove use. A mild winter can make people reduce the air supply to the firebox, which increases creosote build-up and may lead to more house fires instead of fewer.[38] The statistics count fires reported to United States fire departments, and fires in which a fireplace or chimney was coded as the equipment involved appear in a separate category from confined chimney fires.[26] The data date from 1999–2003, and the NFPA 211 requirements are those summarised in the 2008 handbook. Later editions and the rules of other countries may differ.

See also

Notes

  1. ↑ 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 1.10 1.11 1.12 1.13 1.14 1.15 1.16 1.17 1.18 1.19 1.20 1.21 1.22 1.23 1.24 1.25 1.26 Gore Willse (2008a), p. 10-52.
  2. ↑ 2.0 2.1 2.2 2.3 Ahrens et al. (2008), p. 3-74.
  3. ↑ 3.0 3.1 3.2 Gore Willse (2008a), p. 10-50.
  4. ↑ 4.0 4.1 4.2 Gore Willse (2008a), p. 10-24.
  5. ↑ 5.0 5.1 5.2 5.3 5.4 Gore Willse (2008a), p. 10-25.
  6. ↑ 6.00 6.01 6.02 6.03 6.04 6.05 6.06 6.07 6.08 6.09 6.10 6.11 6.12 Gore Willse (2008a), p. 10-53.
  7. ↑ Cholin (2008c), p. 6-69.
  8. ↑ Cholin (2008c), p. 6-66.
  9. ↑ 9.0 9.1 Gore Willse (2008a), p. 10-11.
  10. ↑ 10.0 10.1 Van Rossum (2027), §3.1.
  11. ↑ Beyler and Hirschler (2002), p. 1-115.
  12. ↑ Van Rossum (2027), §4.8.
  13. ↑ Iqbal and Salley (2004), p. F-55.
  14. ↑ 14.0 14.1 Van Rossum (2027), §6.2.
  15. ↑ 15.0 15.1 15.2 Gore Willse (2008a), p. 10-27.
  16. ↑ 16.0 16.1 16.2 16.3 Gore Willse (2008a), p. 10-55.
  17. ↑ Gore Willse (2008a), p. 10-49.
  18. ↑ Van Rossum (2027), §6.6.
  19. ↑ 19.0 19.1 Van Rossum (2027), §4.5.
  20. ↑ 20.0 20.1 Gore Willse (2008a), p. 10-47.
  21. ↑ 21.0 21.1 21.2 21.3 Gore Willse (2008a), p. 10-51.
  22. ↑ Gore Willse (2008b), p. 19-23.
  23. ↑ Ahrens and Stewart (2008), p. 3-50.
  24. ↑ 24.0 24.1 24.2 Ahrens et al. (2008), p. 3-66.
  25. ↑ Lathrop (2008b), p. 20-57.
  26. ↑ 26.0 26.1 Ahrens et al. (2008), pp. 3-72–3-73.
  27. ↑ Hall and Ahrens (2002), pp. 5-72–5-73.
  28. ↑ Ahrens et al. (2008), p. 3-77.
  29. ↑ Gore Willse (2008a), p. 10-23.
  30. ↑ Cote and Grant (2008), p. 1-52.
  31. ↑ Cote and Grant (2008), p. 1-54.
  32. ↑ Nolan (2000), as cited in Iqbal and Salley (2004), p. F-55.
  33. ↑ Gore Willse (2008a), p. 10-48.
  34. ↑ Anderson (2008b), p. 20-51.
  35. ↑ McDaniel (2008), p. 20-200.
  36. ↑ Penney (2008), p. 5-39.
  37. ↑ Farr and Sawyer (2008), p. 1-87.
  38. ↑ Hall and Weller (2008), pp. 5-133–5-134.

References

  • Ahrens, M., Frazier, P., & Kelch, G. (2008). Use of fire incident data and statistics. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-61–3-92). National Fire Protection Association.
  • Ahrens, M., & Stewart, S. (2008). Fire data collection and databases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-43–3-59). National Fire Protection Association.
  • Anderson, R. R. (2008b). Lodging or rooming houses. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-49–20-54). National Fire Protection Association.
  • Beyler, C. L., & Hirschler, M. M. (2002). Thermal decomposition of polymers. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 1-110–1-131). National Fire Protection Association; Society of Fire Protection Engineers.
  • Cholin, J. M. (2008c). Wood and wood-based products. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-61–6-74). National Fire Protection Association.
  • Cote, A. E., & Grant, C. C. (2008). Codes and standards for the built environment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 1-51–1-71). National Fire Protection Association.
  • Farr, R. R., & Sawyer, S. F. (2008). Fire prevention and code enforcement. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 1-81–1-93). National Fire Protection Association.
  • Gore Willse, P. J. (2008a). Heating systems and appliances. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 10-9–10-56). National Fire Protection Association.
  • Gore Willse, P. J. (2008b). Types of building construction. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 19-3–19-27). National Fire Protection Association.
  • Hall, J. R., Jr., & Ahrens, M. J. (2002). Data for engineering analysis. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 5-65–5-78). National Fire Protection Association; Society of Fire Protection Engineers.
  • Hall, J. R., Jr., & Weller, M. W. (2008). Evaluation techniques for fire and life safety education. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 5-119–5-137). National Fire Protection Association.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Lathrop, J. K. (2008b). One- and two-family dwellings. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-55–20-61). National Fire Protection Association.
  • McDaniel, D. L. (2008). Library and museum collections. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-179–20-202). National Fire Protection Association.
  • Penney, G. (2008). Disaster preparedness education. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 5-29–5-43). National Fire Protection Association.
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.