New FSE wiki article: Natural gas (written by Claude Opus 5.5) |
Add SVG figures fse-natural-gas-v1.svg, fse-natural-gas-v2.svg, fse-natural-gas-v3.svg, fse-natural-gas-v4.svg, fse-natural-gas-v5.svg (list-2 visual plan) |
||
| Line 20: | Line 20: | ||
For the high-methane type, the same table gives an ignition temperature of 482–632 °C (900–1170 °F).<ref name="Lemoff-6-174" /> The SFPE Handbook lists pure methane with a lower limit of 5.0 percent, an upper limit of 15.0 percent and a minimum autoignition temperature of 540 °C at atmospheric pressure.<ref name="Beyler-2-176">Beyler (2002b), p. 2-176.</ref> Ethane, the second component, has limits of 3.0 and 12.4 percent and an autoignition temperature of 515 °C.<ref name="Beyler-2-175">Beyler (2002b), p. 2-175.</ref> The net heat of combustion of methane is given as 50,030 kJ/kg in a US nuclear regulatory guide and as about 50 MJ/kg in the ''International Fire Engineering Guidelines''.<ref name="IS-15-10">Iqbal and Salley (2004), p. 15-10.</ref><ref name="NRCC-3.3-5">National Research Council of Canada et al. (2005), p. 3.3-5.</ref> | For the high-methane type, the same table gives an ignition temperature of 482–632 °C (900–1170 °F).<ref name="Lemoff-6-174" /> The SFPE Handbook lists pure methane with a lower limit of 5.0 percent, an upper limit of 15.0 percent and a minimum autoignition temperature of 540 °C at atmospheric pressure.<ref name="Beyler-2-176">Beyler (2002b), p. 2-176.</ref> Ethane, the second component, has limits of 3.0 and 12.4 percent and an autoignition temperature of 515 °C.<ref name="Beyler-2-175">Beyler (2002b), p. 2-175.</ref> The net heat of combustion of methane is given as 50,030 kJ/kg in a US nuclear regulatory guide and as about 50 MJ/kg in the ''International Fire Engineering Guidelines''.<ref name="IS-15-10">Iqbal and Salley (2004), p. 15-10.</ref><ref name="NRCC-3.3-5">National Research Council of Canada et al. (2005), p. 3.3-5.</ref> | ||
[[File:fse-natural-gas-v1.svg|thumb|upright=1.5|alt=Horizontal bars showing the flammable range in air of three natural gas types, methane and ethane|Flammable ranges in air at atmospheric pressure of three types of natural gas, pure methane and pure ethane.]] | |||
Utility natural gas has a density of about two-thirds that of air.<ref name="Lemoff-6-186" /> A chapter on gaseous vehicle fuels gives methane a vapour density of 0.6 and notes that natural gas rises at ambient conditions.<ref name="Rivkin-21-58">Rivkin (2008b), p. 21-58.</ref> The heaviness of a leak can change with temperature, however. Gas that boils off from [[Cryogenic fluid|cryogenic]] liquefied natural gas is denser than air until it warms above about −118 °C (−180 °F).<ref name="Rivkin-21-58" /> Natural gas is nontoxic but is a simple asphyxiant.<ref name="Lemoff-6-186" /> This is in marked contrast to the manufactured gas formerly distributed as utility gas, which contained poisonous carbon monoxide.<ref name="Lemoff-6-186" /> | Utility natural gas has a density of about two-thirds that of air.<ref name="Lemoff-6-186" /> A chapter on gaseous vehicle fuels gives methane a vapour density of 0.6 and notes that natural gas rises at ambient conditions.<ref name="Rivkin-21-58">Rivkin (2008b), p. 21-58.</ref> The heaviness of a leak can change with temperature, however. Gas that boils off from [[Cryogenic fluid|cryogenic]] liquefied natural gas is denser than air until it warms above about −118 °C (−180 °F).<ref name="Rivkin-21-58" /> Natural gas is nontoxic but is a simple asphyxiant.<ref name="Lemoff-6-186" /> This is in marked contrast to the manufactured gas formerly distributed as utility gas, which contained poisonous carbon monoxide.<ref name="Lemoff-6-186" /> | ||
| Line 27: | Line 28: | ||
The 2008 handbook describes the US supply chain as follows. Gas travels from the wells in large-diameter transmission pipelines at pressures up to about 6895 kPa (1000 psi). Utility companies tap these lines and reduce the pressure for distribution, generally to about 1.72–414 kPa (0.25–60 psi), using regulators and safety relief devices.<ref name="Lemoff-6-186" /> The underground network then measured about 1.5 million miles (2.4 million km). Steel and cast-iron pipe are used extensively, and plastic pipe has been used in distribution at pressures up to about 689.5 kPa (100 psi).<ref name="Lemoff-6-186" /> Except as liquefied natural gas, the gas is distributed in piping as a compressed gas, and it is stored in cylinders at pressures up to 24.8 MPa (3600 psi).<ref name="Lemoff-6-186" /> | The 2008 handbook describes the US supply chain as follows. Gas travels from the wells in large-diameter transmission pipelines at pressures up to about 6895 kPa (1000 psi). Utility companies tap these lines and reduce the pressure for distribution, generally to about 1.72–414 kPa (0.25–60 psi), using regulators and safety relief devices.<ref name="Lemoff-6-186" /> The underground network then measured about 1.5 million miles (2.4 million km). Steel and cast-iron pipe are used extensively, and plastic pipe has been used in distribution at pressures up to about 689.5 kPa (100 psi).<ref name="Lemoff-6-186" /> Except as liquefied natural gas, the gas is distributed in piping as a compressed gas, and it is stored in cylinders at pressures up to 24.8 MPa (3600 psi).<ref name="Lemoff-6-186" /> | ||
[[File:fse-natural-gas-v2.svg|thumb|upright=1.5|alt=Flow diagram from gas well through transmission pipeline and regulator station to distribution mains and a building|Natural gas supply chain in the United States around 2007 with typical pressures.]] | |||
Natural gas is also used as a vehicle fuel. Compressed natural gas (CNG) is gas from the distribution system compressed to 16.5–24.8 MPa (2400–3600 psi), stored at a fuelling station and dispensed into vehicle containers at that pressure.<ref name="Lemoff-6-186" /> Liquefied natural gas (LNG) is stored at about −162 °C (−260 °F).<ref name="Rivkin-21-58" /> The two forms share the same flammability limits and autoignition temperature, because these properties do not depend on the storage state.<ref name="Rivkin-21-58" /> In wastewater treatment plants, natural gas heats treatment processes, while anaerobic digesters produce their own off-gas of about 65 percent methane and 5 percent hydrogen.<ref name="Wheeler-9-147">Wheeler (2008), p. 9-147.</ref> Even sewer gas, never used as fuel, can contain up to 5 percent methane and reach explosive limits in poorly ventilated spaces.<ref name="Wheeler-9-151">Wheeler (2008), p. 9-151.</ref> | Natural gas is also used as a vehicle fuel. Compressed natural gas (CNG) is gas from the distribution system compressed to 16.5–24.8 MPa (2400–3600 psi), stored at a fuelling station and dispensed into vehicle containers at that pressure.<ref name="Lemoff-6-186" /> Liquefied natural gas (LNG) is stored at about −162 °C (−260 °F).<ref name="Rivkin-21-58" /> The two forms share the same flammability limits and autoignition temperature, because these properties do not depend on the storage state.<ref name="Rivkin-21-58" /> In wastewater treatment plants, natural gas heats treatment processes, while anaerobic digesters produce their own off-gas of about 65 percent methane and 5 percent hydrogen.<ref name="Wheeler-9-147">Wheeler (2008), p. 9-147.</ref> Even sewer gas, never used as fuel, can contain up to 5 percent methane and reach explosive limits in poorly ventilated spaces.<ref name="Wheeler-9-151">Wheeler (2008), p. 9-151.</ref> | ||
| Line 36: | Line 38: | ||
The strength of ordinary buildings explains why such explosions are so destructive. An enclosure completely full of a flammable gas-air mixture at atmospheric pressure would have to withstand about 400–750 kPa (60–110 psi) to stay intact. Conventional structures can withstand only about 3.5–7.0 kPa (0.5–1.0 psi).<ref name="Lemoff-6-175">Lemoff (2008), p. 6-175.</ref> Most combustion explosions of conventional structures therefore occur with less than 25 percent of the enclosure occupied by the flammable mixture. A room does not have to be filled with gas before it can explode.<ref name="Lemoff-6-175" /> | The strength of ordinary buildings explains why such explosions are so destructive. An enclosure completely full of a flammable gas-air mixture at atmospheric pressure would have to withstand about 400–750 kPa (60–110 psi) to stay intact. Conventional structures can withstand only about 3.5–7.0 kPa (0.5–1.0 psi).<ref name="Lemoff-6-175">Lemoff (2008), p. 6-175.</ref> Most combustion explosions of conventional structures therefore occur with less than 25 percent of the enclosure occupied by the flammable mixture. A room does not have to be filled with gas before it can explode.<ref name="Lemoff-6-175" /> | ||
[[File:fse-natural-gas-v3.svg|thumb|upright=1.5|alt=Room cross-section with a gas layer under the ceiling and a bar comparing explosion pressure with wall strength|Pressure potential of a gas-air mixture compared with the strength of a conventional structure.]] | |||
A gas fire can be seen as an aborted explosion: the gas ignites too soon, or no confining structure is present, so an explosive quantity of mixture never accumulates.<ref name="Lemoff-6-175" /> Outdoors, fires are more likely than explosions. A massive release can still produce an open-air explosion, if the surrounding air or buildings provide enough confinement.<ref name="Lemoff-6-175" /> Such an event is a [[Vapour cloud explosion|vapour cloud explosion]]. The handbook's list of noteworthy incidents includes a release of 500 kg of methane at Raunheim, Germany, on 16 January 1966, which killed one person and injured five.<ref name="Zalosh-2-104">Zalosh (2008), p. 2-104.</ref> | A gas fire can be seen as an aborted explosion: the gas ignites too soon, or no confining structure is present, so an explosive quantity of mixture never accumulates.<ref name="Lemoff-6-175" /> Outdoors, fires are more likely than explosions. A massive release can still produce an open-air explosion, if the surrounding air or buildings provide enough confinement.<ref name="Lemoff-6-175" /> Such an event is a [[Vapour cloud explosion|vapour cloud explosion]]. The handbook's list of noteworthy incidents includes a release of 500 kg of methane at Raunheim, Germany, on 16 January 1966, which killed one person and injured five.<ref name="Zalosh-2-104">Zalosh (2008), p. 2-104.</ref> | ||
| Line 61: | Line 64: | ||
The rule is empirical and applies to mixtures of flammable gases in air.<ref name="Beyler-2-174" /> The lower limit hardly changes with pressure, except well below atmospheric. The upper limit, however, rises with pressure above atmospheric. For natural gas in air at 28 °C, it approaches 60 percent at an initial pressure of about 200 atm.<ref name="Beyler-2-174" /> | The rule is empirical and applies to mixtures of flammable gases in air.<ref name="Beyler-2-174" /> The lower limit hardly changes with pressure, except well below atmospheric. The upper limit, however, rises with pressure above atmospheric. For natural gas in air at 28 °C, it approaches 60 percent at an initial pressure of about 200 atm.<ref name="Beyler-2-174" /> | ||
[[File:fse-natural-gas-v4.svg|thumb|upright=1.5|alt=Line chart of lower flammable limit against methane share in a methane-ethane gas, falling from 5.0 to 3.95 percent|Lower flammable limit of methane-ethane mixtures in air calculated with Le Chatelier's rule.]] | |||
'''Worked example.''' Take a gas of 90 percent methane and 10 percent ethane, within the range the handbook gives for commercial gas.<ref name="Lemoff-6-186" /> With lower limits of 5.0 percent for methane and 3.0 percent for ethane,<ref name="Beyler-2-176" /><ref name="Beyler-2-175" /> the mixture limit is 100 / (90/5.0 + 10/3.0) = 100 / 21.3 = 4.69 percent. A gas with 70 percent methane and 30 percent ethane gives 4.17 percent. Both values lie close to the 4.5–4.7 percent the handbook lists for commercial natural gas.<ref name="Lemoff-6-174" /> If the gas is odorised to be smelled at one-fifth of its lower limit, a person should notice the 90/10 gas at about 0.94 percent by volume, or about 9,400 ppm.<ref name="Lemoff-6-175" /> | '''Worked example.''' Take a gas of 90 percent methane and 10 percent ethane, within the range the handbook gives for commercial gas.<ref name="Lemoff-6-186" /> With lower limits of 5.0 percent for methane and 3.0 percent for ethane,<ref name="Beyler-2-176" /><ref name="Beyler-2-175" /> the mixture limit is 100 / (90/5.0 + 10/3.0) = 100 / 21.3 = 4.69 percent. A gas with 70 percent methane and 30 percent ethane gives 4.17 percent. Both values lie close to the 4.5–4.7 percent the handbook lists for commercial natural gas.<ref name="Lemoff-6-174" /> If the gas is odorised to be smelled at one-fifth of its lower limit, a person should notice the 90/10 gas at about 0.94 percent by volume, or about 9,400 ppm.<ref name="Lemoff-6-175" /> | ||
| Line 98: | Line 102: | ||
A [[Gas detection system|gas detection system]] places its sensors where gas will collect after a leak. For methane, natural gas and other lighter-than-air gases, sensors are generally located above the gas-containing equipment; for propane and butane they are placed low.<ref name="Cholin-14-107">Cholin (2008a), p. 14-107.</ref> Catalytic combustible-gas sensors tend to read higher than the actual concentration of natural gas, and the error grows with concentration. Specific calibration corrects this.<ref name="Cholin-14-103">Cholin (2008a), p. 14-103.</ref> For indoor CNG dispensing, the handbook describes detection that starts mechanical ventilation and sounds an alarm at no more than 20 percent of the lower flammable limit. It also shuts down compression and dispensing automatically.<ref name="Rivkin-21-62" /> | A [[Gas detection system|gas detection system]] places its sensors where gas will collect after a leak. For methane, natural gas and other lighter-than-air gases, sensors are generally located above the gas-containing equipment; for propane and butane they are placed low.<ref name="Cholin-14-107">Cholin (2008a), p. 14-107.</ref> Catalytic combustible-gas sensors tend to read higher than the actual concentration of natural gas, and the error grows with concentration. Specific calibration corrects this.<ref name="Cholin-14-103">Cholin (2008a), p. 14-103.</ref> For indoor CNG dispensing, the handbook describes detection that starts mechanical ventilation and sounds an alarm at no more than 20 percent of the lower flammable limit. It also shuts down compression and dispensing automatically.<ref name="Rivkin-21-62" /> | ||
[[File:fse-natural-gas-v5.svg|thumb|upright=1.5|alt=Two room sections: natural gas rising to a sensor above the equipment and propane sinking to a sensor near the floor|Sensor placement for lighter-than-air and heavier-than-air flammable gases.]] | |||
== Safeguards and emergency control == | == Safeguards and emergency control == | ||
Latest revision as of 08:59, 9 November 2026
Natural gas is a flammable fuel gas, consisting mainly of methane, that forms underground from decomposing organic material and is distributed by gas utilities through pipelines for heating, cooking, power and industrial processes.[1] After treatment, commercial natural gas contains about 70 to 90 percent methane, with most of the rest being ethane.[1] It is lighter than air, has no smell of its own and is not toxic, but it can displace breathing air and burns or explodes when it mixes with air in the right proportions.[1] Its flammable range in air runs from about 4.5–4.7 percent to 14–15 percent by volume, depending on the type of gas.[2] For fire safety, a leak indoors can build up a flammable mixture that ignites as a combustion explosion, while a leak that ignites at once burns as a gas fire or jet flame. Most safeguards therefore aim to keep gas inside pipes and appliances, to make leaks noticeable by adding an odorant, and to detect and remove gas before it reaches an ignition source.
Composition and properties
Natural gas is created by the decomposition of organic material under heat, pressure and bacterial action, in the absence of air and usually below ground.[1] As it comes out of the ground, it contains flammable gases, mainly methane and ethane with some propane, butane and pentane, and nonflammable gases, mainly nitrogen and carbon dioxide. Most of the nonflammable part is removed before distribution.[1] A US handbook chapter on heating appliances gives the same picture: principally methane, with some ethane, propane and butane and small amounts of carbon dioxide and nitrogen.[3]
Natural gas is a flammable gas in the sense of NFPA 55, the US standard for compressed gases and cryogenic fluids.[1] As quoted in the 2008 handbook, NFPA 55 defines a flammable gas as a material that is a gas at 20 °C or less at an absolute pressure of 101.325 kPa. It must also ignite in air at 13 percent or less by volume, or have a flammable range of at least 12 percentage points.[4] The flashpoint, so useful for liquids, has no practical meaning for such a gas. A flammable gas is always above its boiling point, so it can always form an ignitable mixture with air.[5]
The handbook distinguishes three commercial types of natural gas by composition. They differ mainly in their methane and nitrogen content. The values in the table below are copied from its Table 6.10.3; the heating values are gross values.[2]
| Type | Typical composition | Gross heating value (MJ/m³) | Lower limit (vol %) | Upper limit (vol %) | Specific gravity (air = 1.0) | Air to burn 1 m³ of gas (m³) |
|---|---|---|---|---|---|---|
| High inert | CH4 71.9–83.2 %; N2 6.3–16.2 % | 35.7–39.2 | 4.5 | 14.0 | 0.660–0.708 | 9.2 |
| High methane | CH4 87.6–95.7 %; N2 0.1–2.39 % | 37.6–39.9 | 4.7 | 15.0 | 0.590–0.614 | 10.2 |
| High Btu | CH4 85.0–90.1 %; N2 1.2–7.5 % | 39.9–41.9 | 4.7 | 14.5 | 0.620–0.719 | 9.4 |
For the high-methane type, the same table gives an ignition temperature of 482–632 °C (900–1170 °F).[2] The SFPE Handbook lists pure methane with a lower limit of 5.0 percent, an upper limit of 15.0 percent and a minimum autoignition temperature of 540 °C at atmospheric pressure.[6] Ethane, the second component, has limits of 3.0 and 12.4 percent and an autoignition temperature of 515 °C.[7] The net heat of combustion of methane is given as 50,030 kJ/kg in a US nuclear regulatory guide and as about 50 MJ/kg in the International Fire Engineering Guidelines.[8][9]
Utility natural gas has a density of about two-thirds that of air.[1] A chapter on gaseous vehicle fuels gives methane a vapour density of 0.6 and notes that natural gas rises at ambient conditions.[10] The heaviness of a leak can change with temperature, however. Gas that boils off from cryogenic liquefied natural gas is denser than air until it warms above about −118 °C (−180 °F).[10] Natural gas is nontoxic but is a simple asphyxiant.[1] This is in marked contrast to the manufactured gas formerly distributed as utility gas, which contained poisonous carbon monoxide.[1]
Supply, distribution and use
The handbook groups natural gas with the liquefied petroleum gases as the principal fuel gases. Fuel gases are those burned with air in appliances to produce heat, power or light, a usage class reflected in NFPA 54, the National Fuel Gas Code.[11] In the United States around 2000, utility natural gas supplied about one-fifth to one-fourth of the total fuel energy for domestic, commercial and industrial heating and power.[1] It was the most commonly used gas fuel there, because transmission pipelines reach most areas of the country.[3]
The 2008 handbook describes the US supply chain as follows. Gas travels from the wells in large-diameter transmission pipelines at pressures up to about 6895 kPa (1000 psi). Utility companies tap these lines and reduce the pressure for distribution, generally to about 1.72–414 kPa (0.25–60 psi), using regulators and safety relief devices.[1] The underground network then measured about 1.5 million miles (2.4 million km). Steel and cast-iron pipe are used extensively, and plastic pipe has been used in distribution at pressures up to about 689.5 kPa (100 psi).[1] Except as liquefied natural gas, the gas is distributed in piping as a compressed gas, and it is stored in cylinders at pressures up to 24.8 MPa (3600 psi).[1]
Natural gas is also used as a vehicle fuel. Compressed natural gas (CNG) is gas from the distribution system compressed to 16.5–24.8 MPa (2400–3600 psi), stored at a fuelling station and dispensed into vehicle containers at that pressure.[1] Liquefied natural gas (LNG) is stored at about −162 °C (−260 °F).[10] The two forms share the same flammability limits and autoignition temperature, because these properties do not depend on the storage state.[10] In wastewater treatment plants, natural gas heats treatment processes, while anaerobic digesters produce their own off-gas of about 65 percent methane and 5 percent hydrogen.[12] Even sewer gas, never used as fuel, can contain up to 5 percent methane and reach explosive limits in poorly ventilated spaces.[13]
In buildings, natural gas feeds appliances through injection (Bunsen) burners, yellow-flame burners, catalytic burners and power burners.[3][14] Appliances are certified for one or more marked gases, and converting an appliance from one gas to another requires parts to be interchanged by qualified personnel.[14] The products of combustion leave the appliance through a flue, a chimney or a gas vent. The handbook's table of clearances for connectors, for example, treats listed gas appliances with draft hoods and Category I appliances listed for Type B vents separately from oil and solid-fuel appliances.[15] This topic is covered under Gas appliance venting. In large boilers, natural gas is described as the ideal fuel, because it needs no preparation and little postcombustion pollution control.[16]
Fire and explosion behaviour
Released natural gas presents two basic hazards: a combustion explosion and a fire.[2] The handbook describes the explosion as a sequence of events. Gas escapes from its container, piping or equipment and mixes with air. If the proportion lies within the flammable range, the mixture can be ignited and burns rapidly. The heat expands the air most of all, and if the air is confined in a room, the pressure rises. When the room structure is not strong enough, part of it moves suddenly and a bang is heard.[2]
The strength of ordinary buildings explains why such explosions are so destructive. An enclosure completely full of a flammable gas-air mixture at atmospheric pressure would have to withstand about 400–750 kPa (60–110 psi) to stay intact. Conventional structures can withstand only about 3.5–7.0 kPa (0.5–1.0 psi).[17] Most combustion explosions of conventional structures therefore occur with less than 25 percent of the enclosure occupied by the flammable mixture. A room does not have to be filled with gas before it can explode.[17]
A gas fire can be seen as an aborted explosion: the gas ignites too soon, or no confining structure is present, so an explosive quantity of mixture never accumulates.[17] Outdoors, fires are more likely than explosions. A massive release can still produce an open-air explosion, if the surrounding air or buildings provide enough confinement.[17] Such an event is a vapour cloud explosion. The handbook's list of noteworthy incidents includes a release of 500 kg of methane at Raunheim, Germany, on 16 January 1966, which killed one person and injured five.[18]
Ignition of a high-pressure leak usually produces a jet flame. For compressed natural gas, the handbook states that such a jet fire can be 3–9 m (10–30 ft) long, depending on the size of the leak and the pressure.[19] Large-scale tests reported in the SFPE Handbook measured heat fluxes of up to 300 kW/m² from sonic natural gas jets. Averaged over the impingement area on a cylindrical target, the flux was 200 kW/m².[20] Compressed methane releases are of relatively short duration, and the fire usually involves only the combustibles on a vehicle, because the gas is consumed quickly in the jet.[10]
Methane ignites easily. A mining chapter notes that as little as 0.3 mJ of electrical energy can ignite methane under proper conditions. That is about one-fiftieth of the static charge a person accumulates walking across a carpet on a dry day.[21] Natural gas, methane, ethane and propane are dielectric materials, so a fast leak can build up static charge and supply its own ignition source.[22] The fundamental burning velocity of methane is 40 cm/s, lower than that of ethane (47 cm/s) or propane (46 cm/s).[23]
Calculating flammability and explosion pressure
Natural gas is a mixture, so its flammability limits differ from those of pure methane. The SFPE Handbook gives Le Chatelier's rule for estimating the lower flammable limit of a mixture of flammable gases. The rule weights the lower limit of each component by its share in the fuel gas:[24]
| Symbol | Description | Unit |
|---|---|---|
| Lower flammable limit of the fuel gas mixture in air | vol % | |
| Volume percentage of fuel gas i in the fuel gas mixture | vol % | |
| Lower flammable limit of fuel gas i in air alone | vol % | |
| Number of flammable components | – |
The rule is empirical and applies to mixtures of flammable gases in air.[24] The lower limit hardly changes with pressure, except well below atmospheric. The upper limit, however, rises with pressure above atmospheric. For natural gas in air at 28 °C, it approaches 60 percent at an initial pressure of about 200 atm.[24]
Worked example. Take a gas of 90 percent methane and 10 percent ethane, within the range the handbook gives for commercial gas.[1] With lower limits of 5.0 percent for methane and 3.0 percent for ethane,[6][7] the mixture limit is 100 / (90/5.0 + 10/3.0) = 100 / 21.3 = 4.69 percent. A gas with 70 percent methane and 30 percent ethane gives 4.17 percent. Both values lie close to the 4.5–4.7 percent the handbook lists for commercial natural gas.[2] If the gas is odorised to be smelled at one-fifth of its lower limit, a person should notice the 90/10 gas at about 0.94 percent by volume, or about 9,400 ppm.[17]
The ideal mixture follows from the combustion reaction. One mole of methane, about 16 g, reacts with two moles of oxygen, about 64 g, to form one mole of carbon dioxide and two moles of water.[25] Burning 1 kg of methane therefore needs about 4 kg of oxygen. With air containing 21 percent oxygen, the stoichiometric methane concentration is 1/(1 + 2/0.21) = 9.5 percent, the same value the handbook gives as a volume fraction of 0.095.[26] The handbook table states that about 9.2–10.2 m³ of air is needed to burn 1 m³ of natural gas.[2]
When a flame has passed through an unvented enclosure, the final pressure follows from the ideal gas law. Both the unburned and the burned gas occupy the same volume. The ratio of final to initial pressure therefore equals the ratio of moles times temperature of the burned and unburned gas:[26]
| Symbol | Description | Unit |
|---|---|---|
| Pressure at the completion of a closed-vessel deflagration | kPa (absolute) | |
| Initial pressure in the enclosure | kPa (absolute) | |
| Number of moles of burned gas at the end of the deflagration | mol | |
| Number of moles of gas-air mixture initially in the enclosure | mol | |
| Temperature of the burned gas at the end of the deflagration | K | |
| Initial temperature of the gas-air mixture | K |
Calculations without heat loss give worst-case pressure ratios of 8 to 9.6 for methane, propane and hydrogen, at slightly richer than stoichiometric mixtures.[26] Starting from 101.3 kPa, this means about 810–970 kPa absolute, or an overpressure of roughly 710–870 kPa. That is about a hundred times the 7.0 kPa an ordinary structure can withstand.[17] Near the lower limit, at an equivalence ratio of 0.5, the theoretical pressure ratio for methane and propane is still 6 to 6.5.[27] Measured pressures agree well near stoichiometric mixtures but fall below the theory near the limits, because of incomplete flame propagation and heat losses.[26]
For the energy of a confined explosion, NUREG-1805 multiplies the mass of released fuel by its heat of combustion and by a yield, the fraction of energy that drives the blast wave. The yield ranges from about 0.01 for unconfined releases to 1.0 for confined vapour releases.[28] For the 500 kg of methane released at Raunheim,[18] and a heat of combustion of 50,030 kJ/kg,[8] this gives about 250 MJ with a yield of 0.01 and 25 GJ with a yield of 1.0. The hundredfold range shows how strongly the result depends on the assumed confinement.
Odorisation and gas detection
Natural gas has no odour of its own and is generally odorised as it is distributed.[1] As described in the 2008 handbook, codes, standards and regulations require natural gas and LP-gas to be odorised. A person with a normal sense of smell must then detect them at no more than one-fifth of the lower flammable limit, a practice described as common throughout the world.[17] The odorants are usually volatile organic liquids containing sulfur, with a characteristic "gassy" or "rotten egg" smell.[17] The vehicle-fuel chapter states that natural gas is odorised in the pipeline before general distribution, usually to be detectable at 20 to 25 percent of the lower flammable limit of methane.[29] With a limit of 5.0 percent, this means about 1.0–1.25 percent methane by volume.
Odorisation has clear limits. Nobody may be present to smell the gas, for example when a building is empty or the occupants are asleep. Any odour deadens the sense of smell if it is inhaled long enough, and some soils scrub the odorant from gas leaking out of buried pipes.[17]
Odorants can also fade in pipelines and containers through oxidation by oxygen, rust or iron oxides. The sense of smell weakens with age and allergies, and during smoking and eating.[29] Compressed natural gas taken from a distribution line keeps its odorant, but LNG has none. In the United States, NFPA 59A did not require LNG to be odorised as of 2008.[29]
A gas detection system places its sensors where gas will collect after a leak. For methane, natural gas and other lighter-than-air gases, sensors are generally located above the gas-containing equipment; for propane and butane they are placed low.[30] Catalytic combustible-gas sensors tend to read higher than the actual concentration of natural gas, and the error grows with concentration. Specific calibration corrects this.[31] For indoor CNG dispensing, the handbook describes detection that starts mechanical ventilation and sounds an alarm at no more than 20 percent of the lower flammable limit. It also shuts down compression and dispensing automatically.[19]
Safeguards and emergency control
Basic explosion safeguards limit gas accumulation through rugged containers and equipment, emergency flow-control devices, limiting orifices and flame-failure devices on burners that shut off gas when the flame goes out.[17] For appliances, the handbook refers to NFPA 54, the National Fuel Gas Code. Gas should be turned on only after the piping has been tested for leaks. All air must be purged, because a remaining slug of air extinguishes the flame and lets unburned gas escape when flow resumes.[14] Large burners need automatic devices, because pressure fluctuations can put out the flame and let unburned gas accumulate in a combustion chamber.[14] Boiler fuel systems must supply a steady flow over the whole load range, because pressure transients can make the flame unstable.[32]
Control of ignition sources is possible mainly in industry, where staff conduct can be controlled; smoking and candles cannot be prevented in homes.[17] The severity of an explosion can be reduced by deflagration venting under NFPA 68. In this design, some building elements give way at low pressure, while others stay in place. The handbook notes that such designs suit industrial structures rather than ordinary buildings.[17] For indoor CNG fuelling, the 2008 handbook describes separation by walls of at least 2-hour fire resistance, explosion venting and gas-detection-controlled ventilation.[19] Canopies over outdoor CNG equipment should not trap rising gas, because natural gas is buoyant.[19]
In emergencies, the handbook advises extinguishing a gas fire only when the leak is small. If gas keeps escaping after the flame is put out, the fire can turn into a combustion explosion.[33] The general practice is to cool exposed containers and structures with water and to stop the flow of gas where possible.[33] In a closed space, a CNG release is more dangerous than outdoors, because methane rises and pools beneath the ceiling, where light fittings and air-handling equipment can ignite it.[10]
Limits and common misconceptions
A common belief is that a lighter-than-air gas cannot cause an explosion, or that a room must be full of gas first. The handbook rejects both ideas. Most flammable mixtures are about 90 percent air, so the density of the gas itself matters less in building explosions than expected. A mixture filling less than 25 percent of a room is enough to destroy a conventional structure.[17] A second point is that natural gas is not one substance. Its limits, heating value and density vary with composition, so tabulated values for pure methane are only a first estimate.[2]
The term "explosive range" is sometimes used as a synonym for flammable range. The handbook advises against this for gases other than hydrogen, the only gas with a separately published explosive range.[5] In addition, the limits are measured values that depend on the test apparatus. Below 5 percent methane, for example, combustion occurs only in the wake of a pilot flame and does not spread away from it.[34] The data in this article come mainly from US sources of 2002–2008. The requirements they describe, such as those of NFPA 52, NFPA 54, NFPA 55 and NFPA 59A, are those summarised in the 2008 handbook, and they do not necessarily apply elsewhere or today.
See also
- Compressed natural gas
- Liquefied natural gas
- Fuel cell
- Stationary combustion engine
- Wastewater treatment plant
Notes
- ↑ 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 1.10 1.11 1.12 1.13 1.14 1.15 Lemoff (2008), p. 6-186.
- ↑ 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 Lemoff (2008), p. 6-174.
- ↑ 3.0 3.1 3.2 Gore Willse (2008a), p. 10-16.
- ↑ Lemoff (2008), p. 6-165.
- ↑ 5.0 5.1 Lemoff (2008), p. 6-166.
- ↑ 6.0 6.1 Beyler (2002b), p. 2-176.
- ↑ 7.0 7.1 Beyler (2002b), p. 2-175.
- ↑ 8.0 8.1 Iqbal and Salley (2004), p. 15-10.
- ↑ National Research Council of Canada et al. (2005), p. 3.3-5.
- ↑ 10.0 10.1 10.2 10.3 10.4 10.5 Rivkin (2008b), p. 21-58.
- ↑ Lemoff (2008), p. 6-168.
- ↑ Wheeler (2008), p. 9-147.
- ↑ Wheeler (2008), p. 9-151.
- ↑ 14.0 14.1 14.2 14.3 Gore Willse (2008a), p. 10-17.
- ↑ Gore Willse (2008a), p. 10-38.
- ↑ Mattern et al. (2008), p. 10-95.
- ↑ 17.00 17.01 17.02 17.03 17.04 17.05 17.06 17.07 17.08 17.09 17.10 17.11 17.12 Lemoff (2008), p. 6-175.
- ↑ 18.0 18.1 Zalosh (2008), p. 2-104.
- ↑ 19.0 19.1 19.2 19.3 Rivkin (2008b), p. 21-62.
- ↑ Beyler (2002a), p. 3-302.
- ↑ L. J. Moore (2008), p. 9-214.
- ↑ Cholin (2008a), p. 14-109.
- ↑ Schwab (2008b), p. 18-82.
- ↑ 24.0 24.1 24.2 Beyler (2002b), p. 2-174.
- ↑ Van Rossum (2027), §3.3.
- ↑ 26.0 26.1 26.2 26.3 Zalosh (2008), p. 2-98.
- ↑ Zalosh (2002), p. 3-406.
- ↑ Iqbal and Salley (2004), p. 15-9.
- ↑ 29.0 29.1 29.2 Rivkin (2008b), p. 21-60.
- ↑ Cholin (2008a), p. 14-107.
- ↑ Cholin (2008a), p. 14-103.
- ↑ Mattern et al. (2008), p. 10-96.
- ↑ 33.0 33.1 Lemoff (2008), p. 6-176.
- ↑ Beyler (2002b), p. 2-173.
References
- Beyler, C. L. (2002a). Fire hazard calculations for large, open hydrocarbon fires. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-268–3-314). National Fire Protection Association; Society of Fire Protection Engineers.
- Beyler, C. L. (2002b). Flammability limits of premixed and diffusion flames. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-172–2-187). National Fire Protection Association; Society of Fire Protection Engineers.
- Cholin, J. M. (2008a). Gas and vapor detection systems and monitors. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 14-99–14-112). National Fire Protection Association.
- Gore Willse, P. J. (2008a). Heating systems and appliances. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 10-9–10-56). National Fire Protection Association.
- Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
- Lemoff, T. C. (2008). Gases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-165–6-186). National Fire Protection Association.
- Mattern, L. J., Catania, E., & Ehrlich, S. (2008). Boiler furnaces. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 10-91–10-104). National Fire Protection Association.
- Moore, L. J. (2008). Mining and mineral processing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-203–9-223). National Fire Protection Association.
- National Research Council of Canada, International Code Council, Department of Building and Housing, & Australian Building Codes Board. (2005). International fire engineering guidelines (2005 ed.). Australian Building Codes Board.
- Rivkin, C. H. (2008b). Vehicle fueling using gaseous fuels. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-41–21-76). National Fire Protection Association.
- Schwab, R. F. (2008b). Deflagration (explosion) venting. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 18-79–18-88). National Fire Protection Association.
- Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.
- Wheeler, J. F. (2008). Protection of wastewater treatment plants. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-141–9-155). National Fire Protection Association.
- Zalosh, R. (2002). Explosion protection. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-402–3-421). National Fire Protection Association; Society of Fire Protection Engineers.
- Zalosh, R. (2008). Explosions. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-93–2-106). National Fire Protection Association.