New FSE wiki article: Industrial exhaust system (written by Claude Opus 5.5) |
Add SVG figures fse-industrial-exhaust-system-v1.svg, fse-industrial-exhaust-system-v2.svg, fse-industrial-exhaust-system-v3.svg, fse-industrial-exhaust-system-v4.svg (list-2 visual plan) |
||
| (One intermediate revision by one other user not shown) | |||
| Line 16: | Line 16: | ||
US fire statistics in the same chapter illustrate the scale. For 1999–2003, US municipal fire departments attended an estimated 1,130 fires per year that started in a duct in structures other than homes.<ref name="Lataille-8-4" /> Dust, fibre or lint was the item first ignited in 280 of them (25 %), and electrical wire or cable insulation in 140 (13 %).<ref name="Lataille-8-4" /> The handbook stresses that many duct fires start not in the conveyed material but in items installed in or near the duct, such as insulation, wiring and structural members.<ref name="Lataille-8-4" /> | US fire statistics in the same chapter illustrate the scale. For 1999–2003, US municipal fire departments attended an estimated 1,130 fires per year that started in a duct in structures other than homes.<ref name="Lataille-8-4" /> Dust, fibre or lint was the item first ignited in 280 of them (25 %), and electrical wire or cable insulation in 140 (13 %).<ref name="Lataille-8-4" /> The handbook stresses that many duct fires start not in the conveyed material but in items installed in or near the duct, such as insulation, wiring and structural members.<ref name="Lataille-8-4" /> | ||
[[File:fse-industrial-exhaust-system-v4.svg|thumb|upright=1.5|alt=Bar chart of US non-home duct fires 1999 to 2003 by item first ignited, led by dust, fibre or lint at 280 fires per year|US structure fires other than homes that began in a duct, by item first ignited, annual average 1999–2003.]] | |||
== Components and arrangement == | == Components and arrangement == | ||
| Line 27: | Line 28: | ||
Ducts that carry flammable vapours need to withstand some fire exposure. Where vapours can condense, continuously welded joints prevent leakage.<ref name="Lataille-8-7" /> Because flash fires and explosions can occur inside ducts, the handbook advises routing them away from combustibles but within easy reach, and never concealing them in a wall or ceiling.<ref name="Lataille-8-7" /> Plastic ducts are accepted only for nonflammable corrosive vapours. The plastic must then have a flame-spread rating of 25 or less and a smoke-developed rating of 50 or less in the NFPA 255 test.<ref name="Lataille-8-7" /> A typical industrial arrangement for fume hoods in the handbook shows a centrifugal exhaust fan, horizontal duct sections, elbows, balancing dampers, flexible connections, a fume scrubber and a fan discharge stack.<ref name="Lataille-8-9" /> | Ducts that carry flammable vapours need to withstand some fire exposure. Where vapours can condense, continuously welded joints prevent leakage.<ref name="Lataille-8-7" /> Because flash fires and explosions can occur inside ducts, the handbook advises routing them away from combustibles but within easy reach, and never concealing them in a wall or ceiling.<ref name="Lataille-8-7" /> Plastic ducts are accepted only for nonflammable corrosive vapours. The plastic must then have a flame-spread rating of 25 or less and a smoke-developed rating of 50 or less in the NFPA 255 test.<ref name="Lataille-8-7" /> A typical industrial arrangement for fume hoods in the handbook shows a centrifugal exhaust fan, horizontal duct sections, elbows, balancing dampers, flexible connections, a fume scrubber and a fan discharge stack.<ref name="Lataille-8-9" /> | ||
[[File:fse-industrial-exhaust-system-v1.svg|thumb|upright=1.5|alt=Schematic of an industrial exhaust system from process hood through duct, collector and fan to a roof stack, with makeup air entering the room|Main components of an industrial exhaust system.]] | |||
=== Replacement air === | === Replacement air === | ||
| Line 39: | Line 41: | ||
Because flammable vapours are typically denser than air, low peripheral exhaust slots are usually preferred over overhead hoods. The canopy hood is the least efficient, because vapours can migrate to other areas.<ref name="Katunar-9-44" /> Exhaust rates for such tanks typically range from 15 to 60 m³/min per square metre of wetted surface (50 to 200 ft³/min per ft²).<ref name="Katunar-9-45">Katunar (2008), p. 9-45.</ref> | Because flammable vapours are typically denser than air, low peripheral exhaust slots are usually preferred over overhead hoods. The canopy hood is the least efficient, because vapours can migrate to other areas.<ref name="Katunar-9-44" /> Exhaust rates for such tanks typically range from 15 to 60 m³/min per square metre of wetted surface (50 to 200 ft³/min per ft²).<ref name="Katunar-9-45">Katunar (2008), p. 9-45.</ref> | ||
[[File:fse-industrial-exhaust-system-v3.svg|thumb|upright=1.5|alt=Two open tanks compared: canopy hood letting dense vapour spill sideways, and rim slot exhaust capturing vapour at the tank edge|Canopy hood (left) and rim or push-pull slot exhaust (right) on an open process tank.]] | |||
The same chapter lists design points that apply to exhaust systems for dipping and coating in general. Ventilation should run during the process and long enough afterwards to clear the vapours, and automatic processes should shut down if the ventilation fails.<ref name="Katunar-9-45" /> Each exhaust system should ideally discharge directly outdoors, because manifolded systems increase the hazard.<ref name="Katunar-9-45" /> Exhaust air should not be recirculated to occupied spaces. Discharges should be at least 1.8 m (6 ft) from any exterior wall or roof and not within 7.6 m (25 ft) of combustible construction.<ref name="Katunar-9-45" /> | The same chapter lists design points that apply to exhaust systems for dipping and coating in general. Ventilation should run during the process and long enough afterwards to clear the vapours, and automatic processes should shut down if the ventilation fails.<ref name="Katunar-9-45" /> Each exhaust system should ideally discharge directly outdoors, because manifolded systems increase the hazard.<ref name="Katunar-9-45" /> Exhaust air should not be recirculated to occupied spaces. Discharges should be at least 1.8 m (6 ft) from any exterior wall or roof and not within 7.6 m (25 ft) of combustible construction.<ref name="Katunar-9-45" /> | ||
| Line 70: | Line 73: | ||
! Symbol !! Description !! Unit | ! Symbol !! Description !! Unit | ||
|- | |- | ||
| <math>V_\mathrm{v}</math> || Volume of vapour produced by 1 L of liquid | | <math>V_\mathrm{v}</math> || Volume of vapour produced by 1 L of liquid || m³/L | ||
|- | |- | ||
| SG || Specific gravity of the liquid (water = 1) || – | | SG || Specific gravity of the liquid (water = 1) || – | ||
| Line 93: | Line 96: | ||
|} | |} | ||
Slye (2008) bases the vapour-volume equation on the weight of 1 US gallon of water (8.33 lb) and of 1 ft³ of air (0.075 lb), and gives no correction for other temperatures or pressures.<ref name="Slye-6-202" /> The LFL itself changes with temperature, so an oven or dryer design needs LFL data at the elevated temperature.<ref name="Slye-6-203">Slye (2008), p. 6-203.</ref> Le Chatelier's rule is empirical. For example, a mixture of 50 % methane, 25 % carbon monoxide and 25 % hydrogen has an estimated LFL of 5.48 %.<ref name="Beyler-2-174" /> | |||
=== Worked example === | === Worked example === | ||
| Line 102: | Line 105: | ||
* Air needed to stay just below the LFL: 1 × 0.33 × 37 = 12.2 m³/min. The handbook gives the same 12.2 m³ of air per litre of acetone.<ref name="Slye-6-202" /> | * Air needed to stay just below the LFL: 1 × 0.33 × 37 = 12.2 m³/min. The handbook gives the same 12.2 m³ of air per litre of acetone.<ref name="Slye-6-202" /> | ||
* Design flow with the factor of four: 4 × 12.2 = 48.8 m³/min, rounded up to 49 m³/min (0.82 m³/s) at 21 °C. | * Design flow with the factor of four: 4 × 12.2 = 48.8 m³/min, rounded up to 49 m³/min (0.82 m³/s) at 21 °C. | ||
* Exhaust volume at 149 °C (422 K) from fresh air at 21 °C (294 K): 48.8 × 422/294 = 70. | * Exhaust volume at 149 °C (422 K) from fresh air at 21 °C (294 K): 48.8 × 422/294 = 70.0 m³/min, rounded up to 71 m³/min (1.2 m³/s). | ||
With the design flow, the vapour concentration is 0.33/(0.33 + 48.8) = 0.67 % by volume. That is about | With the design flow, the vapour concentration is 0.33/(0.33 + 48.8) = 0.67 % by volume. That is about 26 % of the acetone LFL, close to but slightly above the 25 % criterion used in NFPA practice.<ref name="Lataille-8-6" /> The same handbook gives a simpler US rule for continuous ovens: 283 m³ (10,000 ft³) of fresh air at 21 °C for each 3.79 L (1 gal) of solvent evaporated.<ref name="Ostrowski-8-80" /> This rule assumes that 3.79 L of common solvent forms about 71 m³ (2,500 ft³) of the leanest explosive mixture, and multiplies by four.<ref name="Ostrowski-8-80" /> Per litre, the rule gives 74.7 m³, against 48.8 m³ from the acetone calculation, so for acetone it is conservative. For some solvents the barely explosive volume exceeds the assumed value, and the margin of the rule shrinks accordingly.<ref name="Ostrowski-8-80" /> | ||
[[File:fse-industrial-exhaust-system-v2.svg|thumb|upright=1.5|alt=Bar chart of fresh air per litre of solvent: 12.2 cubic metres to reach the LFL, 48.8 with factor four, 74.7 by the oven rule|Fresh air per litre of evaporated solvent for acetone, with and without the factor of four, against the US oven rule of thumb.]] | |||
== Dust, refuse and particulate systems == | == Dust, refuse and particulate systems == | ||
| Line 123: | Line 127: | ||
== Limits and uncertainty == | == Limits and uncertainty == | ||
The dilution method assumes that the exhaust air mixes evenly with the vapour. Real enclosures are never uniform, and Slye (2008) states that a substantial excess of air is applied in practice for that reason.<ref name="Slye-6-203" /> The factor of four in US oven practice serves the same purpose.<ref name="Ostrowski-8-80" /> Vapour release rates vary widely between processes, and Katunar (2008) concludes that no standard exhaust design can serve all operations.<ref name="Katunar-9-44" /> The extent of a vapour area | The dilution method assumes that the exhaust air mixes evenly with the vapour. Real enclosures are never uniform, and Slye (2008) states that a substantial excess of air is applied in practice for that reason.<ref name="Slye-6-203" /> The factor of four in US oven practice serves the same purpose.<ref name="Ostrowski-8-80" /> Vapour release rates vary widely between processes, and Katunar (2008) concludes that no standard exhaust design can serve all operations.<ref name="Katunar-9-44" /> The extent of a vapour area can be determined with a combustible gas analyser.<ref name="Katunar-9-44" /> | ||
The 25 % LFL limit, the discharge distances, the hood face velocities and the oven rule are US practice as summarised in the 2008 handbook. Later editions of NFPA 91, NFPA 86 and the other standards may differ, and other countries regulate industrial exhaust under their own rules. The duct fire statistics describe US municipal fire department responses in 1999–2003 and exclude fires handled only by industrial fire brigades.<ref name="Lataille-8-4" /> | The 25 % LFL limit, the discharge distances, the hood face velocities and the oven rule are US practice as summarised in the 2008 handbook. Later editions of NFPA 91, NFPA 86 and the other standards may differ, and other countries regulate industrial exhaust under their own rules. The duct fire statistics describe US municipal fire department responses in 1999–2003 and exclude fires handled only by industrial fire brigades.<ref name="Lataille-8-4" /> | ||
Latest revision as of 09:13, 9 November 2026
An industrial exhaust system is a mechanical air-moving system that captures vapours, gases, mists or dusts where a process releases them. Ducts and a fan carry them to the outside or to a collector. In the Fire Protection Handbook (2008), such air-moving equipment covers all mechanical-draft duct systems, of both the pressure and the exhaust type, used to remove dusts, vapours and waste material or to convey materials.[1] These systems are separate from the normal heating, ventilating and air-conditioning plant of a building.[2]
Their fire safety task is to keep flammable vapours and combustible residues from building up inside rooms and equipment. In US practice described in the handbook, the usual design target is a vapour concentration below 25 % of the lower flammable limit.[3] The same system can also become a hazard: fans, ducts and collectors can ignite the material they carry and spread fire through a building.[1]
Definition and scope
The handbook chapter on air-moving equipment starts from a practical need. Many industrial and commercial operations generate airborne materials during normal work, such as vapours, gases and particulate solids, and these must be removed.[2] An industrial exhaust system does this with a chain of components: an inlet or hood at the source, ducts, an air-moving device such as a fan, and often separating or cleaning equipment before discharge.[4] The system is in addition to the building's own heating, ventilating and air-conditioning, which in the United States falls under NFPA 90A.[2]
The handbook distinguishes several families of air-moving systems by the material handled. In the United States, NFPA 91, Standard for Exhaust Systems for Air Conveying of Vapors, Gases, Mists, and Noncombustible Particulate Solids, covers systems for vapours, gases, mists and noncombustible particles. NFPA 654 covers combustible particulate solids, and it absorbed the material of the withdrawn NFPA 650.[2] Smoke control and heat venting are covered by other standards and are not part of the process exhaust function.[1] Further standards apply to particular processes, for example NFPA 33 for spray application, NFPA 34 for dipping and coating, NFPA 45 for laboratories, NFPA 86 for ovens and furnaces and NFPA 96 for commercial cooking.[1]
As summarised in the 2008 handbook, NFPA 91 limits the concentration of combustible vapours to 25 % of the lower explosive limit. It also contains rules for duct construction and clearances, identifies where fire dampers are needed, describes special extinguishing systems with drainage for their discharge, and requires inspection, testing and maintenance.[2] The handbook does not name the edition of NFPA 91 it summarises.
Why exhaust systems matter for fire safety
Exhaust systems protect against fire by removing fuel from the air of a workroom. If the removed materials were left to accumulate, the handbook names three results: an explosion of a vapour-air mixture, a flash fire in accumulated lint or other combustibles, and generally poor housekeeping that favours fires.[2] The concept rests on the flammability limits of a vapour. The lower flammable limit (LFL) is the lowest vapour concentration in air at which a flame can propagate when an ignition source is present; it is the same quantity as the lower explosive limit (LEL).[5] For methane in air at normal temperature and pressure the LFL is 5 % by volume and the upper limit 15 %.[6] For most simple hydrocarbons the LFL corresponds to roughly 48 g of fuel per cubic metre of mixture.[6]
The duct network is also a fire path in its own right. The handbook names sparks from fans or from foreign material such as tramp metal, and overheated fan bearings, as ignition sources inside such systems. It adds that the systems can spread fire through the building.[1]
US fire statistics in the same chapter illustrate the scale. For 1999–2003, US municipal fire departments attended an estimated 1,130 fires per year that started in a duct in structures other than homes.[1] Dust, fibre or lint was the item first ignited in 280 of them (25 %), and electrical wire or cable insulation in 140 (13 %).[1] The handbook stresses that many duct fires start not in the conveyed material but in items installed in or near the duct, such as insulation, wiring and structural members.[1]
Components and arrangement
Fans
Air-moving systems usually contain axial-flow fans or centrifugal blowers. A straight-blade centrifugal fan suits air carrying large particles, because it resists clogging and its blades withstand abrasion.[1] Propeller fans move large volumes against little resistance, so they are unsuitable for ducts of any appreciable length.[7]
To reduce the fire hazard, fans should be of noncombustible construction, capable of remote shutdown in a fire, accessible for maintenance and structurally sound against wear and misalignment.[7] A blade striking a distorted housing can produce a friction spark, so nonsparking materials are used where the exhaust contains flammable solids or vapours.[7] For vapours that may condense on the blades, the handbook recommends backward-curved blades and a nonferrous fan and housing.[8] Fans are selected to move the required air quantity against all calculated friction losses of the duct system.[9]
Hoods, inlets and ducts
Vapours should be drawn from the room or equipment where they arise and taken directly outside, or to suitably protected pollution-control equipment.[3] Suction inlets have little directional effect beyond a few inches (1 in. = 25.4 mm) from their face. They are therefore placed to produce a sweeping or purging effect that leaves no pockets where vapours collect.[3] Heavier-than-air vapours are best captured by openings near the floor, and lighter vapours by openings near the top of the room, hood or enclosure.[8]
Ducts that carry flammable vapours need to withstand some fire exposure. Where vapours can condense, continuously welded joints prevent leakage.[8] Because flash fires and explosions can occur inside ducts, the handbook advises routing them away from combustibles but within easy reach, and never concealing them in a wall or ceiling.[8] Plastic ducts are accepted only for nonflammable corrosive vapours. The plastic must then have a flame-spread rating of 25 or less and a smoke-developed rating of 50 or less in the NFPA 255 test.[8] A typical industrial arrangement for fume hoods in the handbook shows a centrifugal exhaust fan, horizontal duct sections, elbows, balancing dampers, flexible connections, a fume scrubber and a fan discharge stack.[4]
Replacement air
An exhaust system can only remove air if the same amount of air can enter the space. Iqbal and Salley (2004), writing for US nuclear plants, note that in a closed area exhaust cannot reach its design flow without an equal supply of makeup air.[10] The terms makeup air and replacement air refer to the air brought into a space to limit pressure differences, so that the exhaust can operate as designed.[11] It may enter through ducts or through openings from adjacent areas. Its flow must let the exhaust work within its design pressure difference without creating a positive pressure in the space.[11][10] A makeup air supply placed with care relative to the vapour source also helps to dilute and remove vapours.[3]
Exhaust of flammable vapours
Because flammable vapours ignite easily, ignition sources must be kept out of ducts that carry them. The handbook calls the use of one system for flammable vapours and for particles from spark-producing processes "obviously dangerous".[3] Drawing different vapours into one system is also poor practice if they form a hazardous mixture. Perchloric acid, for example, acts as an oxidising agent at elevated temperatures and can cause a fire or explosion when drawn into a system that also exhausts organic materials.[3] Processes that generate flammable vapours are best placed along an outside wall, so that vapours can be removed efficiently.[3]
The handbook gives the design target as enough air movement to keep the vapour concentration below 25 % of the LFL where vapours are released. Toxic vapours may require concentrations well below that level.[3] All electrical equipment that may be exposed to the vapours should meet NFPA 70, the US National Electrical Code, for hazardous locations.[8]
Open process tanks show how the exhaust layout affects performance. For a dip tank, the handbook defines ventilation as air movement that prevents vapour-air mixtures above 25 % of the LFL. The exhaust air stream should not exceed that level either.[12] The vapour area around a dipping process should not extend more than 1.5 m (5 ft) from the vapour source.[12]
Because flammable vapours are typically denser than air, low peripheral exhaust slots are usually preferred over overhead hoods. The canopy hood is the least efficient, because vapours can migrate to other areas.[12] Exhaust rates for such tanks typically range from 15 to 60 m³/min per square metre of wetted surface (50 to 200 ft³/min per ft²).[13]
The same chapter lists design points that apply to exhaust systems for dipping and coating in general. Ventilation should run during the process and long enough afterwards to clear the vapours, and automatic processes should shut down if the ventilation fails.[13] Each exhaust system should ideally discharge directly outdoors, because manifolded systems increase the hazard.[13] Exhaust air should not be recirculated to occupied spaces. Discharges should be at least 1.8 m (6 ft) from any exterior wall or roof and not within 7.6 m (25 ft) of combustible construction.[13]
For a spray booth or spray room, vapour removal works best with the exhaust intake along one wall within 300 mm (1 ft) of the floor. The makeup air then enters along the opposite wall.[14] Overspray collectors in such systems combine a fan with baffles, dry filters or water scrubbers. Residues that pass the collector can deposit on the exhaust stack, on the fan blades or on the roof.[14]
Laboratory hoods are a special case of local exhaust. According to Anderson (2008a), typical hoods operate under negative pressure with face velocities of 0.41 to 0.61 m/s (80 to 120 ft/min), with 0.5 m/s (100 ft/min) the most common value. In the United States their duct systems are to follow NFPA 91.[15] The ducts of hoods and local exhaust systems must be noncombustible and kept at negative pressure relative to the surrounding area.[15]
Calculating the dilution airflow
The required airflow follows from a mass balance between the vapour released and the air that dilutes it. Slye (2008) sets out the method in three steps. First, the volume of vapour produced by one litre of liquid is found from the specific gravity of the liquid and the vapour density relative to air.[5]
Second, the LFL in percent by volume gives the number of volumes of air per volume of vapour that make the mixture just too lean to ignite. Acetone, with an LFL of 2.6 %, needs about 37 volumes of air.[5]
Third, the airflow that keeps the mixture at the LFL is the evaporation rate times the vapour volume per litre times this ratio. Ostrowski (2008a) describes the US oven practice of adding a factor of safety of four on the calculated air volume. The reason is that part of the air may pass through the enclosure without reaching the zone where vapours are released.[16]
Gas volume varies in direct proportion to absolute temperature. The volume exhausted from a hot enclosure must therefore be corrected from the fresh-air temperature to the operating temperature. In the handbook example, fresh air at 21 °C supplied to an oven at 149 °C occupies 1.44 times its volume.[16]
Exhaust streams often carry several flammable gases at once. The LFL of such a mixture can be estimated with Le Chatelier's rule, as given by Beyler (2002b). Each gas contributes in proportion to its share of the fuel mixture and inversely to its own LFL.[17]
| Symbol | Description | Unit |
|---|---|---|
| Volume of vapour produced by 1 L of liquid | m³/L | |
| SG | Specific gravity of the liquid (water = 1) | – |
| VD | Vapour density relative to air (air = 1) | – |
| LFL | Lower flammable limit of the vapour in air | % by volume |
| Volumes of air per volume of vapour at the LFL | – | |
| Rate at which liquid evaporates into the enclosure | L/min | |
| Design fresh-air flow, including the factor of four | m³/min | |
| Exhaust flow at the operating temperature | m³/min | |
| , | Absolute operating temperature and fresh-air temperature | K |
| Lower flammable limit of a fuel-gas mixture | % by volume | |
| Volume percent of gas i in the fuel-gas mixture | % |
Slye (2008) bases the vapour-volume equation on the weight of 1 US gallon of water (8.33 lb) and of 1 ft³ of air (0.075 lb), and gives no correction for other temperatures or pressures.[5] The LFL itself changes with temperature, so an oven or dryer design needs LFL data at the elevated temperature.[18] Le Chatelier's rule is empirical. For example, a mixture of 50 % methane, 25 % carbon monoxide and 25 % hydrogen has an estimated LFL of 5.48 %.[17]
Worked example
A process releases acetone vapour into an enclosure that is exhausted at 149 °C. The evaporation rate is assumed to be 1 L/min, the SI counterpart of the 1 gal/min used in the handbook example. The acetone data are those given by Slye (2008): specific gravity 0.792, vapour density 2 and flammable range 2.6 to 12.8 % by volume.[5]
- Vapour per litre: m³/L.
- Air-to-vapour ratio at the LFL: .
- Air needed to stay just below the LFL: 1 × 0.33 × 37 = 12.2 m³/min. The handbook gives the same 12.2 m³ of air per litre of acetone.[5]
- Design flow with the factor of four: 4 × 12.2 = 48.8 m³/min, rounded up to 49 m³/min (0.82 m³/s) at 21 °C.
- Exhaust volume at 149 °C (422 K) from fresh air at 21 °C (294 K): 48.8 × 422/294 = 70.0 m³/min, rounded up to 71 m³/min (1.2 m³/s).
With the design flow, the vapour concentration is 0.33/(0.33 + 48.8) = 0.67 % by volume. That is about 26 % of the acetone LFL, close to but slightly above the 25 % criterion used in NFPA practice.[3] The same handbook gives a simpler US rule for continuous ovens: 283 m³ (10,000 ft³) of fresh air at 21 °C for each 3.79 L (1 gal) of solvent evaporated.[16] This rule assumes that 3.79 L of common solvent forms about 71 m³ (2,500 ft³) of the leanest explosive mixture, and multiplies by four.[16] Per litre, the rule gives 74.7 m³, against 48.8 m³ from the acetone calculation, so for acetone it is conservative. For some solvents the barely explosive volume exceeds the assumed value, and the margin of the rule shrinks accordingly.[16]
Dust, refuse and particulate systems
Dust collecting and stock conveying systems consist of suction ducts and inlets, air-moving equipment, feeders, discharge ducts, collecting equipment and receptacles. When the material is a combustible dust, a fire or explosion is possible.[9] The handbook therefore places the fan on the clean-air side of the dust collector. The system then works under suction and the dust is removed before the air reaches the fan.[19] If the fan must sit between the source and the collector, its blades and housing should be of nonsparking material with ample clearance.[19]
Ducts for dusts and stock are made of metal, with long bends to limit deposits at turns.[19] The handbook recommends no more than two branches on any section of main duct, branches joined at the top or side at no more than 45° to the airflow, and short main ducts.[19] Branches should not be added without redesigning the system.[19]
Collectors are built to withstand the expected explosion pressure, with allowance for deflagration vents. They are preferably of steel and located outside the building.[19] Screw conveyors or rotary feeders create a "choke" that helps stop a flash fire from spreading through the system.[20] High-efficiency particulate air filters remove at least 99.97 % of particles of 0.3 µm diameter.[20] The handbook advises that such filters be UL 900 listed, so that they do not contribute to a duct fire.[21]
Fire and explosion protection
Because the ducts themselves or the material in them can burn, the handbook considers automatic extinguishing systems justified. For a flammable vapour or an easily ignited dust, a deluge system actuated by heat-sensitive devices may be most appropriate. Where the problem is a combustible duct, an automatic sprinkler system may be adequate.[22] For vapour exhaust systems, the agent should be water, foam, dry chemical or carbon dioxide, as suited to the hazard, with portable extinguishers as backup.[23] Ductwork can also obstruct the discharge of sprinklers in the room below, and extra sprinklers beneath the ducts may be needed.[22]
Where ignition sources are hard to control, inerting, explosion suppression or spark extinguishing may be used. Inerting is generally practical for essentially closed systems. Explosion suppression has not succeeded for some materials, such as metal dusts.[23] Spark extinguishing systems suit fibres and flyings.[23] Deflagration relief vents on ducts that carry explosible mixtures should lead by the most direct route to the outside.[21] Static charge on an insulated duct section can discharge across a joint and ignite the conveyed material, so exhaust systems for flammable vapours, dusts and gases are bonded and grounded.[21]
Where ducts pass through fire-rated walls, floors or partitions, the handbook calls for dampers with an equivalent fire resistance rating. These keep the fire compartment intact.[21] A fire damper of this kind is a different device from the backdraft dampers used in manifolded duct systems, which stop vapours or dusts being drawn back upstream.[21] For plastic ductwork, firestopping spool pieces collapse when heated and block the duct.[21] Frequent cleaning of ducts, filters and discharge enclosures limits both the intensity of a duct fire and spontaneous heating of deposits.[8] One cleaning compound in the handbook is one part calcium hydroxide to two parts calcium carbonate, which saponifies grease and oily sludge.[21]
Ventilation is also one of four ways named by Ural and Garzia (2008) to limit combustibles for explosion prevention. They refer to Appendix D of NFPA 69 for concentration-control design and to NFPA 91 for the physical installation.[24] They warn that a poorly designed ventilation system for a dusty operation can leave dust deposits in unexpected places. Such deposits can fuel devastating secondary explosions, as in the West Pharmaceutical explosion of 29 January 2003.[25]
Limits and uncertainty
The dilution method assumes that the exhaust air mixes evenly with the vapour. Real enclosures are never uniform, and Slye (2008) states that a substantial excess of air is applied in practice for that reason.[18] The factor of four in US oven practice serves the same purpose.[16] Vapour release rates vary widely between processes, and Katunar (2008) concludes that no standard exhaust design can serve all operations.[12] The extent of a vapour area can be determined with a combustible gas analyser.[12]
The 25 % LFL limit, the discharge distances, the hood face velocities and the oven rule are US practice as summarised in the 2008 handbook. Later editions of NFPA 91, NFPA 86 and the other standards may differ, and other countries regulate industrial exhaust under their own rules. The duct fire statistics describe US municipal fire department responses in 1999–2003 and exclude fires handled only by industrial fire brigades.[1]
See also
- Industrial oven and furnace
- Laboratory fume hood
- Explosion venting
- Spark detection and extinguishing system
- Hazardous area classification
Notes
- ↑ 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 Lataille (2008), p. 8-4.
- ↑ 2.0 2.1 2.2 2.3 2.4 2.5 Lataille (2008), p. 8-3.
- ↑ 3.0 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 Lataille (2008), p. 8-6.
- ↑ 4.0 4.1 Lataille (2008), p. 8-9.
- ↑ 5.0 5.1 5.2 5.3 5.4 5.5 Slye (2008), p. 6-202.
- ↑ 6.0 6.1 Beyler (2002b), p. 2-172.
- ↑ 7.0 7.1 7.2 Lataille (2008), p. 8-5.
- ↑ 8.0 8.1 8.2 8.3 8.4 8.5 8.6 Lataille (2008), p. 8-7.
- ↑ 9.0 9.1 Lataille (2008), p. 8-8.
- ↑ 10.0 10.1 Iqbal and Salley (2004), p. 2-4.
- ↑ 11.0 11.1 Demers (2008b), p. 10-78.
- ↑ 12.0 12.1 12.2 12.3 12.4 Katunar (2008), p. 9-44.
- ↑ 13.0 13.1 13.2 13.3 Katunar (2008), p. 9-45.
- ↑ 14.0 14.1 Scarbrough (2008b), p. 9-30.
- ↑ 15.0 15.1 Anderson (2008a), p. 9-162.
- ↑ 16.0 16.1 16.2 16.3 16.4 16.5 Ostrowski (2008a), p. 8-80.
- ↑ 17.0 17.1 Beyler (2002b), p. 2-174.
- ↑ 18.0 18.1 Slye (2008), p. 6-203.
- ↑ 19.0 19.1 19.2 19.3 19.4 19.5 Lataille (2008), p. 8-10.
- ↑ 20.0 20.1 Lataille (2008), p. 8-11.
- ↑ 21.0 21.1 21.2 21.3 21.4 21.5 21.6 Lataille (2008), p. 8-14.
- ↑ 22.0 22.1 Lataille (2008), p. 8-12.
- ↑ 23.0 23.1 23.2 Lataille (2008), p. 8-13.
- ↑ Ural and Garzia (2008), p. 17-149.
- ↑ Ural and Garzia (2008), p. 17-150.
References
- Anderson, R. R. (2008a). Fire protection of laboratories using chemicals. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-157–9-166). National Fire Protection Association.
- Beyler, C. L. (2002b). Flammability limits of premixed and diffusion flames. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-172–2-187). National Fire Protection Association; Society of Fire Protection Engineers.
- Demers, D. P. (2008b). Ventilation of commercial cooking operations. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 10-77–10-89). National Fire Protection Association.
- Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
- Katunar, J., III (2008). Dipping and coating processes. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-39–9-51). National Fire Protection Association.
- Lataille, J. I. (2008). Air-Moving equipment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-3–8-15). National Fire Protection Association.
- Ostrowski, R. (2008a). Industrial and commercial heat utilization equipment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-71–8-92). National Fire Protection Association.
- Scarbrough, D. R. (2008b). Spray finishing and powder coating. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-27–9-37). National Fire Protection Association.
- Slye, O. M., Jr. (2008). Flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-197–6-208). National Fire Protection Association.
- Ural, E. A., & Garzia, H. W. (2008). Explosion prevention and protection. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-141–17-165). National Fire Protection Association.