The curve behind the equation covers sea-level equivalent oxygen concentrations from about 9.6 down to 3.9 percent.<ref name="Purser-2-107" /> For changing concentrations, Purser sums the fractional doses of each time step, and loss of consciousness is predicted when the sum reaches 1.<ref name="Purser-2-107" /> The data are for people at rest, and the time also depends on activity, which affects oxygen demand, and on the breathing rate.<ref name="Purser-2-107" /> | The curve behind the equation covers sea-level equivalent oxygen concentrations from about 9.6 down to 3.9 percent.<ref name="Purser-2-107" /> For changing concentrations, Purser sums the fractional doses of each time step, and loss of consciousness is predicted when the sum reaches 1.<ref name="Purser-2-107" /> The data are for people at rest, and the time also depends on activity, which affects oxygen demand, and on the breathing rate.<ref name="Purser-2-107" /> | ||
[[File:fse-medical-gas-system-v3.svg|thumb|upright=1.5|alt=Curve of time to loss of consciousness rising steeply as oxygen concentration increases from 4 to 10 percent|Predicted time to loss of consciousness for a person at rest against oxygen concentration, from Purser's hypoxia equation.]] | |||
'''Worked example.''' A nitrogen leak in a manifold room lowers the oxygen concentration to 10 percent. The vitiation is 20.9 − 10 = 10.9 percent, and <math>t_{IO}</math> = exp(8.13 − 0.54 × 10.9) = 9.4 min, the value Purser also gives.<ref name="Purser-2-107" /> At 8 percent oxygen the vitiation is 12.9 percent and <math>t_{IO}</math> = 3.2 min. | '''Worked example.''' A nitrogen leak in a manifold room lowers the oxygen concentration to 10 percent. The vitiation is 20.9 − 10 = 10.9 percent, and <math>t_{IO}</math> = exp(8.13 − 0.54 × 10.9) = 9.4 min, the value Purser also gives.<ref name="Purser-2-107" /> At 8 percent oxygen the vitiation is 12.9 percent and <math>t_{IO}</math> = 3.2 min. | ||
| Line 42: | Line 43: | ||
== System components == | == System components == | ||
The first way to reduce the hazards is to remove cylinders and containers from occupied spaces by locating all sources remotely and piping the gases and vacuum to the bedside.<ref name="Allen-6-188" /> Centrally piped systems are found in most hospitals and larger medical facilities. Bedside cylinders remain mainly in small facilities, such as nursing homes, and specialised gases still arrive in cylinders in laboratories.<ref name="Allen-6-188" /> Oxygen usually comes from a bulk oxygen system or a manifold of cylinders. Nitrous oxide, carbon dioxide and nitrogen usually come from manifolds, and medical air from a compressor.<ref name="Allen-6-189" /> Because of economies of scale, almost all medium to large hospitals store oxygen in bulk on site.<ref name="Allen-6-190" /> | The first way to reduce the hazards is to remove cylinders and containers from occupied spaces by locating all sources remotely and piping the gases and vacuum to the bedside.<ref name="Allen-6-188" /> Centrally piped systems are found in most hospitals and larger medical facilities. Bedside cylinders remain mainly in small facilities, such as nursing homes, and specialised gases still arrive in cylinders in laboratories.<ref name="Allen-6-188" /> Oxygen usually comes from a bulk oxygen system or a manifold of cylinders. Nitrous oxide, carbon dioxide and nitrogen usually come from manifolds, and medical air from a compressor.<ref name="Allen-6-189" /> Because of economies of scale, almost all medium to large hospitals store oxygen in bulk on site.<ref name="Allen-6-190" /> | ||
[[File:fse-medical-gas-system-v1.svg|thumb|upright=1.5|alt=Schematic of bulk oxygen, cylinder manifold, air compressor and vacuum pump feeding pipes, zone valves and bedside outlets|Main parts of a centrally piped medical gas and vacuum system: remote supply sources, dedicated piping with zone valves and alarms, and keyed outlets in patient care areas.]] | |||
In US practice as described by Allen (2008), each gas and vacuum system has its own dedicated network of copper pipe. All joints, except those at the source, must be brazed or otherwise joined to withstand a fire exposure of 1000 °F (538 °C) or more (the handbook prints 588 °C, a conversion error).<ref name="Allen-6-188" /> Before service, the piping is pressure tested for leaks and then tested for purity, cleanliness and the absence of cross connections to other systems.<ref name="Allen-6-188" /> Station outlets have noninterchangeable fittings keyed to the specific gas and carry a label with the gas name.<ref name="Allen-6-189" /> Colour codes identify each gas from the source to the outlets, and may even carry through to the equipment plugged into them.<ref name="Allen-6-189" /> | In US practice as described by Allen (2008), each gas and vacuum system has its own dedicated network of copper pipe. All joints, except those at the source, must be brazed or otherwise joined to withstand a fire exposure of 1000 °F (538 °C) or more (the handbook prints 588 °C, a conversion error).<ref name="Allen-6-188" /> Before service, the piping is pressure tested for leaks and then tested for purity, cleanliness and the absence of cross connections to other systems.<ref name="Allen-6-188" /> Station outlets have noninterchangeable fittings keyed to the specific gas and carry a label with the gas name.<ref name="Allen-6-189" /> Colour codes identify each gas from the source to the outlets, and may even carry through to the equipment plugged into them.<ref name="Allen-6-189" /> | ||
[[File:fse-medical-gas-system-v5.jpg|thumb|upright=1.5|alt=Wall-mounted medical gas outlets for oxygen, medical air and vacuum above a hospital bed, each with its own label|Station outlets for oxygen, medical air and vacuum above a patient bed, each with a gas-specific fitting and label | [[File:fse-medical-gas-system-v5.jpg|thumb|upright=1.5|alt=Wall-mounted medical gas outlets for oxygen, medical air and vacuum above a hospital bed, each with its own label|Station outlets for oxygen, medical air and vacuum above a patient bed, each with a gas-specific fitting and label.]] | ||
Table 6.11.1 of the handbook reproduces the colours and operating pressures of NFPA 99 (2005 edition), Table 5.1.11.<ref name="Allen-6-189" /> Medical air, carbon dioxide, helium, nitrous oxide and oxygen are piped at a gauge pressure of 345–380 kPa (50–55 psi). Nitrogen and instrument air are piped at 1100–1275 kPa (160–185 psi).<ref name="Allen-6-189" /> Medical-surgical vacuum operates at 380 to 760 mm (15 to 30 in.) of mercury vacuum.<ref name="Allen-6-189" /> Oxygen is green with white text or the reverse, medical air yellow with black text, nitrous oxide blue with white text and nitrogen black with white text.<ref name="Allen-6-189" /> | Table 6.11.1 of the handbook reproduces the colours and operating pressures of NFPA 99 (2005 edition), Table 5.1.11.<ref name="Allen-6-189" /> Medical air, carbon dioxide, helium, nitrous oxide and oxygen are piped at a gauge pressure of 345–380 kPa (50–55 psi). Nitrogen and instrument air are piped at 1100–1275 kPa (160–185 psi).<ref name="Allen-6-189" /> Medical-surgical vacuum operates at 380 to 760 mm (15 to 30 in.) of mercury vacuum.<ref name="Allen-6-189" /> Oxygen is green with white text or the reverse, medical air yellow with black text, nitrous oxide blue with white text and nitrogen black with white text.<ref name="Allen-6-189" /> | ||
All piping systems are divided into zones so that the supply to any specific area can be shut off.<ref name="Allen-6-188" /> Medical gases can then be isolated from the piping in a fire area, allowing a "defend in place" fire attack while patients in other areas keep their gases and vacuum.<ref name="Allen-6-188" /> Allen (2008) stresses that extreme care is needed before any valve is closed. Valves should be closed only after it has been verified that all patients are stable, and many valves are poorly labelled, so closing one can affect areas not named on the label.<ref name="Allen-6-188" /> Apart from zone valves, no valve should be closed by anyone other than facility staff.<ref name="Allen-6-188" /> | All piping systems are divided into zones so that the supply to any specific area can be shut off.<ref name="Allen-6-188" /> Medical gases can then be isolated from the piping in a fire area, allowing a "defend in place" fire attack while patients in other areas keep their gases and vacuum.<ref name="Allen-6-188" /> Allen (2008) stresses that extreme care is needed before any valve is closed. Valves should be closed only after it has been verified that all patients are stable, and many valves are poorly labelled, so closing one can affect areas not named on the label.<ref name="Allen-6-188" /> Apart from zone valves, no valve should be closed by anyone other than facility staff.<ref name="Allen-6-188" /> | ||
[[File:fse-medical-gas-system-v4.svg|thumb|upright=1.5|alt=Floor plan of three hospital zones with the zone valve closed for the zone on fire and open for the others|Zoning of medical gas piping: the zone valve of the fire area is closed while the other zones stay supplied.]] | |||
== Cylinders and supply storage == | == Cylinders and supply storage == | ||
| Line 57: | Line 60: | ||
These values show how much gas a single cylinder can release. Dividing the gas volume by the cylinder volume gives a factor of 6900/43.6 = 158 for oxygen at 2200 psig and 15,800/43.6 = 362 for nitrous oxide at only 745 psig.<ref name="Allen-6-190" /> Manifold rooms and cylinder stores should therefore be identified and labelled as containing medical gases, and care is needed when entering a room that holds large quantities.<ref name="Allen-6-189" /> Transfilling gas from one cylinder to another is hazardous and, as described in the 2008 handbook, NFPA 99 does not permit it in patient care areas.<ref name="Allen-6-192">Allen (2008), p. 6-192.</ref><ref name="Allen-6-193">Allen (2008), p. 6-193.</ref> | These values show how much gas a single cylinder can release. Dividing the gas volume by the cylinder volume gives a factor of 6900/43.6 = 158 for oxygen at 2200 psig and 15,800/43.6 = 362 for nitrous oxide at only 745 psig.<ref name="Allen-6-190" /> Manifold rooms and cylinder stores should therefore be identified and labelled as containing medical gases, and care is needed when entering a room that holds large quantities.<ref name="Allen-6-189" /> Transfilling gas from one cylinder to another is hazardous and, as described in the 2008 handbook, NFPA 99 does not permit it in patient care areas.<ref name="Allen-6-192">Allen (2008), p. 6-192.</ref><ref name="Allen-6-193">Allen (2008), p. 6-193.</ref> | ||
[[File:fse-medical-gas-system-v2.svg|thumb|upright=1.5|alt=Bar chart of gas volume in one H or K cylinder for oxygen, nitrogen, helium, air and nitrous oxide|Gas volume at 21.1 °C in one H or K cylinder (nominal volume 43.6 L) for five medical gases.]] | |||
== Medical air and vacuum systems == | == Medical air and vacuum systems == | ||
Latest revision as of 08:51, 9 November 2026
A medical gas system is the installation that supplies gases for life support, therapy, medical analysis and mechanical power in a health care facility. It usually includes vacuum systems for fluids and waste anaesthetic gases.[1] A centrally piped system consists of supply sources with their controls, a piping network with control valves and alarms, and terminal units or outlets in patient care areas and laboratories.[2] Typical gases are oxygen, medical air, nitrous oxide, nitrogen, carbon dioxide, helium and their mixtures.[1] Allen (2008) explains that medical gases matter for fire safety less because of what they are than because of where they are used: in areas with patients who often cannot be moved.[1]
The gases bring three kinds of hazard. Patients may depend on an uninterrupted supply, some gases are oxidisers or asphyxiants, and the cylinders that store them can vent or burst in a fire.[2] Fires caused directly by medical gases are rare. The larger concern is the effect of the gases near a fire that started for other reasons.[1] In the United States the design, installation and testing of these systems are covered by NFPA 99, Standard for Health Care Facilities, as described in the NFPA Fire Protection Handbook (2008).[3]
Purpose and scope
In a typical medical facility gases are used for life support, therapy, medical analysis and mechanical power. Besides oxygen, medical air, nitrous oxide, nitrogen, carbon dioxide and helium, they include blood gas mixtures.[1] Two vacuum systems are usually present as well: medical vacuum and waste anaesthetic gas disposal (WAGD).[1] The safe practices described by Allen (2008) apply to all health care facilities that use medical gases, such as hospitals, ambulatory health care centres, nursing homes and dental offices. They are also relevant to home health care.[1]
In the classification of gases by use, Lemoff (2008) calls medical gases the most specialised group. They serve purposes such as anaesthesia and respiratory therapy, and oxygen and nitrous oxide are the most common.[4] The setting makes the fire problem different from other buildings. Many patients cannot be readily moved, either because they depend on life-support equipment or because they are not mobile, so a fire becomes a more lethal threat.[1] The International Fire Engineering Guidelines (2005) make the same point for evacuation. In a hospital the patients, rather than the staff, determine the movement time, and that time depends on the type of patient, such as intensive care or surgery.[5]
Recorded incidents fall into a few groups. The fires most directly linked to medical gases involved lasers near endotracheal tubing that carried medical gas, and oxygen catheters ignited when a patient tried to smoke.[1] Some fires are thought to have started when waste anaesthetic gases passed through oil-lubricated pumps. Other incidents, injuries and deaths resulted from construction faults such as untested cross connections, from cylinder misuse, wrong gases and mislabelling, and from inadequate training of maintenance staff.[1]
Gases and their hazards
The first and most significant hazard is that the supply of one or more gases may be the only thing keeping a patient alive.[2] The second is chemical. Oxygen is the most important oxidiser: a little pure oxygen increases the intensity of any fire and makes items normally considered noncombustible in air burn very well.[2] Where the oxygen concentration exceeds 21 percent by volume, the result is an oxygen-enriched atmosphere, in which most materials ignite at considerably lower temperatures and burn faster.[6][7] Nitrous oxide behaves similarly when heated to dissociation, because the breakdown of the molecule releases oxygen and heat.[2]
Other medical gases work the opposite way. Nitrogen, helium and carbon dioxide slow or stop a fire, but they create an anoxic environment in which there is not enough oxygen for breathing, and anyone nearby risks asphyxiation.[2] Nitrous oxide also acts as an asphyxiant when it is not dissociated.[2] Normal air contains 21 percent oxygen by volume.[8] A leak of nitrogen, helium or carbon dioxide can therefore cause oxygen depletion without any fire.[2] In the practice described by Allen (2008), the label on a manifold or storage room must indicate whether the room contains oxygen or only asphyxiants.[9]
Purser (2002) gives an equation, derived from human high-altitude data, for the time to loss of consciousness of a person at rest in a reduced-oxygen atmosphere.[10] Loss of consciousness occurs when the oxygen partial pressure in the venous blood of the brain falls below a critical value of 20 mmHg.[11] The equation uses the oxygen vitiation, which is the drop in oxygen concentration below the normal 20.9 percent.[10]
| Symbol | Description | Unit |
|---|---|---|
| time to loss of consciousness at a constant oxygen concentration | min | |
| oxygen concentration of the inhaled atmosphere | % by volume | |
| oxygen vitiation | % by volume | |
| fraction of an incapacitating dose of hypoxia; loss of consciousness is predicted when it reaches 1 | – | |
| duration of exposure step at a constant concentration | min |
The curve behind the equation covers sea-level equivalent oxygen concentrations from about 9.6 down to 3.9 percent.[10] For changing concentrations, Purser sums the fractional doses of each time step, and loss of consciousness is predicted when the sum reaches 1.[10] The data are for people at rest, and the time also depends on activity, which affects oxygen demand, and on the breathing rate.[10]
Worked example. A nitrogen leak in a manifold room lowers the oxygen concentration to 10 percent. The vitiation is 20.9 − 10 = 10.9 percent, and = exp(8.13 − 0.54 × 10.9) = 9.4 min, the value Purser also gives.[10] At 8 percent oxygen the vitiation is 12.9 percent and = 3.2 min.
A worker who spends 2 minutes at 10 percent receives a dose fraction of 2/9.43 = 0.21.[10] If the concentration then falls to 8 percent, the remaining fraction of 0.79 is reached after 0.79 × 3.20 = 2.5 min. Loss of consciousness is therefore predicted after about 4.5 minutes in total, rounded down to the safe side.
System components
The first way to reduce the hazards is to remove cylinders and containers from occupied spaces by locating all sources remotely and piping the gases and vacuum to the bedside.[2] Centrally piped systems are found in most hospitals and larger medical facilities. Bedside cylinders remain mainly in small facilities, such as nursing homes, and specialised gases still arrive in cylinders in laboratories.[2] Oxygen usually comes from a bulk oxygen system or a manifold of cylinders. Nitrous oxide, carbon dioxide and nitrogen usually come from manifolds, and medical air from a compressor.[9] Because of economies of scale, almost all medium to large hospitals store oxygen in bulk on site.[3]
In US practice as described by Allen (2008), each gas and vacuum system has its own dedicated network of copper pipe. All joints, except those at the source, must be brazed or otherwise joined to withstand a fire exposure of 1000 °F (538 °C) or more (the handbook prints 588 °C, a conversion error).[2] Before service, the piping is pressure tested for leaks and then tested for purity, cleanliness and the absence of cross connections to other systems.[2] Station outlets have noninterchangeable fittings keyed to the specific gas and carry a label with the gas name.[9] Colour codes identify each gas from the source to the outlets, and may even carry through to the equipment plugged into them.[9]

Table 6.11.1 of the handbook reproduces the colours and operating pressures of NFPA 99 (2005 edition), Table 5.1.11.[9] Medical air, carbon dioxide, helium, nitrous oxide and oxygen are piped at a gauge pressure of 345–380 kPa (50–55 psi). Nitrogen and instrument air are piped at 1100–1275 kPa (160–185 psi).[9] Medical-surgical vacuum operates at 380 to 760 mm (15 to 30 in.) of mercury vacuum.[9] Oxygen is green with white text or the reverse, medical air yellow with black text, nitrous oxide blue with white text and nitrogen black with white text.[9]
All piping systems are divided into zones so that the supply to any specific area can be shut off.[2] Medical gases can then be isolated from the piping in a fire area, allowing a "defend in place" fire attack while patients in other areas keep their gases and vacuum.[2] Allen (2008) stresses that extreme care is needed before any valve is closed. Valves should be closed only after it has been verified that all patients are stable, and many valves are poorly labelled, so closing one can affect areas not named on the label.[2] Apart from zone valves, no valve should be closed by anyone other than facility staff.[2]
Cylinders and supply storage
Medical gases are stored in compressed gas cylinders and containers. If they overheat in a fire they vent their contents and, in extreme circumstances, may explode.[2] A falling cylinder can also block an evacuation route or break off its valve and become a high-speed "torpedo".[2] Compressed-oxygen cylinders are protected against overpressure by bursting discs, or by bursting discs combined with fusible plugs, while insulated cryogenic containers have pressure-relief valves.[12] Combustion inside a container is a further hazard. Gas-oxygen mixtures can form inadvertently in industrial and medical gas applications where oxygen or compressed air is used with flammable gases.[13]
Table 6.11.2 of the handbook gives typical cylinder contents, with gas volumes at 70 °F (21.1 °C).[3] An E cylinder of 10.8 × 66 cm with a nominal volume of 4.80 L holds 660 L of oxygen at 1900 psig (13.1 MPa gauge). An H or K cylinder of 23.5 × 130 cm and 43.6 L holds 6900 L of oxygen at 2200 psig (15.2 MPa gauge).[3] The same H cylinder holds 6400 L of nitrogen. Filled with nitrous oxide at 745 psig, it holds 15,800 L of gas weighing 29.1 kg.[3]
These values show how much gas a single cylinder can release. Dividing the gas volume by the cylinder volume gives a factor of 6900/43.6 = 158 for oxygen at 2200 psig and 15,800/43.6 = 362 for nitrous oxide at only 745 psig.[3] Manifold rooms and cylinder stores should therefore be identified and labelled as containing medical gases, and care is needed when entering a room that holds large quantities.[9] Transfilling gas from one cylinder to another is hazardous and, as described in the 2008 handbook, NFPA 99 does not permit it in patient care areas.[14][15]
Medical air and vacuum systems
Medical air is purified compressed air. It supports fire as well as any air, and it is under pressure.[2] Air compressed above ambient pressure, 14.7 psi (101 kPa), is itself an oxygen-enriched atmosphere in which ignition is easier and flame spreads faster.[16] In US practice as described by Allen (2008), a compressor that supplies a piped medical air system must not add impurities such as hydrocarbons, carbonaceous particles or carbon monoxide.[16] At minimum, its intake must not draw from the building in which the compressor stands, and the air must be free of lubricants and their breakdown products.[16] Where the compressor serves operating rooms and respiratory therapy, its power must come from the critical branch of the essential electrical system set out in NFPA 99.[16]
Cylinder air is an alternative where the outdoor air is highly contaminated. Some suppliers then use so-called synthetic air, a mixture of pure oxygen and nitrogen that contains no atmospheric pollutants.[16] Because of the risks of backfeeding and overdrawing, the medical air system should not be used for any nonpatient purpose.[16] Oxygen concentrators, which separate air and deliver oxygen of a purity approaching 90 percent, are used in mobile military hospitals, remote hospitals and home care.[16]
Central vacuum systems look like the gas systems, but the flow is into the wall or ceiling.[16] Inlets are installed in emergency rooms, operating rooms, recovery rooms, intensive care units, delivery rooms, nurseries and patient rooms, with collection bottles for fluids and trap bottles that protect the suction line.[16] Vacuum is also life supporting, so it deserves the same precautions as the gas systems for valve closures and supply interruptions.[14] Flammable gases or liquids must not be drawn into the system. Laboratory vacuum is kept separate from the medical-surgical vacuum piping, although a common receiver tank is permitted.[14]
Waste anaesthetic gas disposal collects excess anaesthetic gases, transports them and exhausts them with a pump or blower.[14] The medical vacuum system may serve this purpose if its capacity exceeds the normal operating room demand. Fires appear to have resulted from waste anaesthetic gases passing through oil-lubricated pumps, and that practice should be discouraged.[14]
Fire hazards in use
Oxygen-enriched atmospheres are encountered during practically every inhalation anaesthetic and respiratory therapy procedure, and nitrous oxide is also considered one.[17] The operating room is a particularly hazardous fire location, because of the widespread use of oxygen and nitrous oxide, its "wet environment" and its many electrical ignition sources.[3] Potential ignition sources include electrosurgical units, lasers, fibreoptic light sources, adiabatic compression of gases, sparks, static electricity and defibrillators.[17] Fuels include mattresses, sheets and drapes, patient hair, oxygen tubing and masks, gauze, rubber gloves and the intestinal gases hydrogen and methane.[17]
Respiratory therapy equipment, such as ventilators connected to the compressed air and oxygen outlets, combines an enriched atmosphere with an electrical power supply and nearby fuels.[14] In such atmospheres flame spread can be extremely rapid if bedding or clothing is saturated with oxygen.[14] To prevent dangerous adiabatic compression heating, cylinder valves should be opened slowly, and brass rather than aluminium regulators should be used.[17] All components carrying compressed air, oxygen or nitrous oxide must be cleaned for this service and kept free of hydrocarbon contaminants such as solvents and lubricants.[17] In home health care, small containers or concentrators supply the oxygen, and fires from smoking near the oxygen may occur.[15]
Two related installations are often found next to the medical gas system. A hyperbaric chamber deliberately raises the oxygen percentage, and its elevated pressure increases the oxygen partial pressure further; NFPA 99 covers its safety in the United States.[17][18] Ethylene oxide sterilisers use a highly flammable, toxic gas. Allen (2008) stresses that it is not a medical gas in the sense of oxygen or nitrous oxide, because it has no role in patient treatment. It is therefore outside the rules for medical gases and falls under NFPA 560 instead.[15]
Fire response and regulation
When bedding and clothing saturated with oxygen catch fire, flame spread is extremely rapid and large quantities of water are needed.[17] Dry chemical extinguishers and fire blankets are ineffective. Electrical equipment must be de-energised before water is applied, and halon and carbon dioxide extinguishers are also appropriate.[17]
Fire services need to know the special problems of each area. The NFPA 704 hazard identification diamond helps by showing flammability, health and instability hazards. In the United States, NFPA 99, as described in the 2008 handbook, requires it on laboratories.[17] Complete evacuation of a medical facility is rare, so zone valves are used to shut off the gases to the fire area alone.[2]
In the United States, the handbook chapter on health care occupancies states that laboratories, anaesthetising locations and medical gas systems should comply with the hazardous-area provisions of NFPA 99.[19] In ambulatory care facilities and dental offices, many requirements for the safe use of oxygen-enriched atmospheres are identical to those for hospitals.[18] Larger dental offices and ambulatory care facilities that perform surgery under general anaesthesia need central vacuum and central piping of oxygen and nitrous oxide.[18] In US code enforcement as described in the 2008 handbook, plumbing departments are responsible for medical gas and medical vacuum systems.[20] All of these requirements describe US documents and practice around 2008 and are not universal.
See also
Notes
- ↑ 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 Allen (2008), p. 6-187.
- ↑ 2.00 2.01 2.02 2.03 2.04 2.05 2.06 2.07 2.08 2.09 2.10 2.11 2.12 2.13 2.14 2.15 2.16 2.17 2.18 2.19 Allen (2008), p. 6-188.
- ↑ 3.0 3.1 3.2 3.3 3.4 3.5 3.6 Allen (2008), p. 6-190.
- ↑ Lemoff (2008), p. 6-168.
- ↑ National Research Council of Canada et al. (2005), p. 1.2-31.
- ↑ Rosales and Stoltzfus (2008), p. 9-225.
- ↑ Rosales and Stoltzfus (2008), p. 9-227.
- ↑ Van Rossum (2027), §4.2.
- ↑ 9.0 9.1 9.2 9.3 9.4 9.5 9.6 9.7 9.8 Allen (2008), p. 6-189.
- ↑ 10.0 10.1 10.2 10.3 10.4 10.5 10.6 Purser (2002), p. 2-107.
- ↑ Purser (2002), p. 2-106.
- ↑ Lemoff (2008), p. 6-185.
- ↑ Lemoff (2008), p. 6-173.
- ↑ 14.0 14.1 14.2 14.3 14.4 14.5 14.6 Allen (2008), p. 6-192.
- ↑ 15.0 15.1 15.2 Allen (2008), p. 6-193.
- ↑ 16.0 16.1 16.2 16.3 16.4 16.5 16.6 16.7 16.8 Allen (2008), p. 6-191.
- ↑ 17.0 17.1 17.2 17.3 17.4 17.5 17.6 17.7 17.8 Allen (2008), p. 6-194.
- ↑ 18.0 18.1 18.2 Allen (2008), p. 6-195.
- ↑ O'Connor (2008), p. 20-152.
- ↑ Farr and Sawyer (2008), p. 1-92.
References
- Allen, M. (2008). Medical gases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-187–6-196). National Fire Protection Association.
- Farr, R. R., & Sawyer, S. F. (2008). Fire prevention and code enforcement. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 1-81–1-93). National Fire Protection Association.
- Lemoff, T. C. (2008). Gases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-165–6-186). National Fire Protection Association.
- National Research Council of Canada, International Code Council, Department of Building and Housing, & Australian Building Codes Board. (2005). International fire engineering guidelines (2005 ed.). Australian Building Codes Board.
- O'Connor, D. J. (2008). Health care occupancies. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-139–20-155). National Fire Protection Association.
- Purser, D. A. (2002). Toxicity assessment of combustion products. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-83–2-171). National Fire Protection Association; Society of Fire Protection Engineers.
- Rosales, K., & Stoltzfus, J. M. (2008). Oxygen-Enriched atmospheres. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-225–9-243). National Fire Protection Association.
- Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.