An underground storage tank (UST) is a tank for flammable, combustible or other hazardous liquids that is buried in the ground, outside or beneath a building. Under US federal law, as described in the Fire Protection Handbook (2008), it is a tank system, including its piping, with at least 10 % of its volume underground.[1] Typical tanks hold from about 1,100 L to 38,000 L of liquid, most often motor and other fuels.[2][1] Such tanks are generally considered the safest form of storage, but leaks contaminate soil and groundwater, and the vapours can collect in sewers and basements and ignite.[2][1] The main concerns are therefore corrosion, leaks, correct burial and anchoring, and venting during filling. The requirements described here are those of US codes, such as NFPA 30 and NFPA 31, and of US federal rules as summarised in the 2008 handbook, so they show US practice around 2007–2008.

Definition and typical sizes

In the federal definition under Subtitle I of the Resource Conservation and Recovery Act (RCRA), a tank counts as a UST when at least a tenth of the tank system's volume, piping included, lies underground. The substances regulated are petroleum products and the hazardous substances defined under the US Superfund law (CERCLA).[1][3] Ordile notes that tanks can be installed aboveground, underground or, under certain conditions, inside buildings.[4] In the service station chapter of the handbook, Rivkin separates underground tanks from tanks in vaults. A vault is a protective enclosure that keeps the tank out of contact with the ground even when it is installed below grade.[5] In the handbook, tanks in vaults are treated as aboveground tanks, the type described in the article Atmospheric storage tank.[6]

Table 7.2.4 of the handbook lists typical sizes of underground flammable liquid tanks. They range from 1,136 L (300 gal), 0.91 m in diameter and 1.83 m long, to 37,854 L (10,000 gal). Four shapes are listed for 37,854 L, from 2.44 m by 8.23 m to 3.20 m by 4.75 m.[2] The diameters run from 0.91 m to 3.20 m and the lengths from 1.83 m to 8.84 m.[2]

Scatter chart of tank length against diameter for typical underground tanks from 1,136 to 37,854 litres
Typical sizes of underground flammable liquid tanks: length against diameter, labelled by capacity.

Fire safety and environmental trade-off

Burying a tank removes it from most fire exposures. Ordile states that underground tanks are generally considered the safest form of storage.[2] Underground piping is not subject to fire exposure, and pumping liquid from underground tanks through protected piping to the dispensers is one of the safest ways of handling flammable liquids.[7][8] The ground also damps temperature swings, so underground tanks lose less liquid by evaporation than aboveground ones.[4]

The price is the environmental risk. Rivkin writes that underground tanks present less fire hazard but have a greater potential to affect the environment, and that environmental rules are stricter for them than for aboveground tanks.[5] Concern about groundwater contamination has made users more wary of underground tanks.[2] The US federal rules on underground tanks have helped make aboveground secondary containment tanks popular.[9] At service stations, vaulted tanks are one answer to these conflicting concerns. They allow an above-grade installation with extra fire protection.[5]

The stable ground temperature also matters for filling containers. Gasoline expands by about 0.69 % per 10 °F (5.6 °C) rise, so cool liquid drawn from an underground tank into a container on a warm day will expand.[4][10] For a rise of 20 °F (11 °C), this is about 1.4 %, or about 14 L for every 1,000 L of cool fuel drawn into containers. Containers and tanks should therefore not be filled completely.[4]

Construction

According to Ordile, underground tanks are made of coated steel, fibreglass-reinforced plastic (FRP) or plastic-clad steel, in single-wall and double-wall forms. Almost all are listed by UL or other testing agencies, and most follow industry standards.[2] Unlined concrete may be used for liquids with a gravity of 40 degrees API or heavier. Lined concrete may serve lighter liquids if the lining suits the liquid and adheres well to the concrete.[2] Underground tanks must withstand the pressure of the earth, of concrete and of any vehicle traffic above them.[2]

FRP tanks avoid the corrosion problem of steel tanks. Their makers' installation instructions must be followed closely, because poor installation can cause major failure, and the stored liquid must not attack the plastic.[11] A properly installed underground steel tank with either a fibreglass outer wall or cathodic protection has a normal life expectancy of 25 to 30 years.[11] Rivkin describes the double-walled, cathodically protected steel tanks of a typical service station. Their pressure relief devices, cathodic protection and concrete foundation are code requirements.[12]

Installation

Underground tanks may be buried outside or under buildings. Tanks under buildings should have their fill and vent connections outside the building walls.[2][11] Tanks are set on firm foundations and surrounded with well-tamped sand or gravel, and the excavation must not undermine existing foundations.[11] Normally no special protection is needed if the tank is well supported and buried deep enough. Where higher loads can occur, concrete, paving or extra earth cover may be necessary. Sleeves, casings or flexible connectors protect piping against damaging loads and vibration.[11]

In the United States, the service station rules described by Rivkin in the 2008 handbook set two clearances. Tanks must be at least 0.3 m (1 ft) from any basement or pit wall and 0.91 m (3 ft) from any property line that can be built on. Tanks are buried deep enough, or protected at the surface, against vehicle damage.[13] For fuel oil, NFPA 31 and NFPA 30 both deal with location relative to building foundations and property lines, with traffic, and with tanks dislodged by groundwater or flooding.[14]

Section through a buried horizontal tank in sand backfill with fill pipe, vent pipe, anchoring and clearances to a basement wall and property line
Buried tank installation with clearances described for US service stations.

The Building Code of the City of New York, whose fuel oil provisions were unchanged from 1987 to 1999 according to NIST, gives another example.[15] It required the top of a buried fuel oil tank at least 0.61 m (2 ft) below ground. Stones in the surrounding sand or earth had to pass a 25 mm (1 in.) mesh.[16] No tank could be buried within 0.91 m (3 ft) of a foundation wall or footing, and pipes needed double swing joints at the tank.[17]

Where groundwater is high or can rise in a flood, tanks should be anchored or weighted so that they cannot float.[11] The reason is Archimedes' principle. A submerged body experiences an upward lift equal to the weight of the fluid it displaces, and it floats if this lift exceeds its own weight.[18] For a fully submerged cylindrical tank, the lift is:

Fb=ρwgπD24L

The net upward force on a tank holding liquid follows by subtracting the weight of the contents, and of the tank itself where that is known:

Fnet=Fb(1−Sϕ)−Wtank

Symbol Description Unit
Fb Buoyant force on the fully submerged tank N
Fnet Net upward force to be resisted by anchoring or weight N
ρw Density of groundwater (taken as water) kg/m³
g Acceleration due to gravity, 9.81 m/s²
D, L Tank diameter and length m
S Specific gravity of the stored liquid –
ϕ Fraction of the tank volume filled with liquid (0 for an empty tank) –
Wtank Weight of the empty tank N

Worked example. Take the 37,854 L (10,000 gal) tank of Table 7.2.4 that is 2.44 m in diameter and 8.23 m long.[2] Its outer cylinder volume is π/4 × 2.44² × 8.23 = 38.4 m³. With water at 10 °C, 62.4 lb/ft³ (999.6 kg/m³), the lift on the empty, fully submerged tank is 999.6 × 9.81 × 38.4 = 377 kN, rounded up to 380 kN.[19] Full of gasoline with a specific gravity of 0.72, the 37.85 m³ of contents weigh 0.72 × 999.6 × 9.81 × 37.85 = 267 kN. The net lift is then 377 − 267 = 110 kN before the tank's own weight is deducted.[20] In the formula this corresponds to φ ≈ 0.98, because the capacity is slightly smaller than the outer volume. An empty tank is therefore the critical case; the tank weight is not given in the sources and is left out.

Free-body diagram of a submerged tank with upward buoyant force and downward weight of contents
Forces on a 2.44 m by 8.23 m tank fully submerged in groundwater: lift 377 kN; net lift 110 kN when full of gasoline, before the tank weight.

Venting, filling and gauging

Rivkin describes the vent rules for US service station tanks as they stood in 2008. Vent pipes must be wide enough to prevent blowback of vapour or liquid at the fill opening while the tank is filled, and they must not be obstructed. An undersized vent also slows refilling, because the air in the tank is harder to displace.[5] The vent should discharge at least 3.7 m (12 ft) above ground for Class I liquids such as gasoline, and above the expected snow level for Class II liquids such as diesel fuel. It must be away from building openings and ventilation air intakes, and higher than the fill pipe.[5][13] These liquid classes are those of NFPA 30, which groups liquids by flash point and, for Class I, boiling point.[21]

For fuel oil tanks, NFPA 31 as described in the 2008 handbook requires fill and vent pipes that end outside the building, including for tanks buried beneath buildings. Vents must prevent abnormal pressure during filling and be at least 1¼ in. (30 mm) nominal pipe size for tanks up to 2,500 L (660 gal).[14] Openings for measuring the liquid level can release vapour during gauging. They are particularly undesirable in tanks buried under basements, and the handbook says that NFPA standards prohibit them unless protected by a spring-loaded check valve or other approved device.[6] The handbook covers fuel dispensing from underground tanks in the chapter on service stations, the subject of the article Motor fuel dispensing facility.[5] At such sites, breakaway and shear valves limit the release of fuel if a hose or the piping breaks.[12]

Corrosion and leaks

Poor workmanship is one of the largest causes of failures and leaks, and poorly installed piping often shows leakage within the first year.[11] Soil matters as much. Some soils, such as red clay, are highly corrosive because of their chemistry or moisture, as are backfills mixed with construction debris, cinders or shale. Clean, homogeneous backfill and protective coatings extend the life of steel tanks and piping, and cathodic protection is often necessary.[11] As described in the 2008 handbook, NFPA 30 requires either corrosion-resistant materials, such as special alloys and fibreglass, or an engineered cathodic protection system. Rivkin adds that the choice must be made location by location.[11][13]

Corrosion can also be electrical. Galvanic corrosion occurs where dissimilar metals, such as steel and brass, are joined, so such connections should be avoided. Stray electrical currents can start corrosion that is hard to detect until damage is done.[11] Environmental rules or a hazard analysis may require a double-walled tank, groundwater monitoring, or both.[11]

A leak need not appear near the tank. Leaking liquid can travel substantial distances underground or penetrate 610 mm (24 in.) of waterproofed concrete before it appears in a building.[11] Severson notes that leaks readily reach groundwater and that the vapours can collect in septic tanks, sewers and building basements, where they are a health hazard and can cause a fire or explosion.[1] A tank suspected of leaking should be tested hydrostatically with the same liquid it stores. The handbook shows a simple set-up: a gauge glass of 305 to 457 mm on a pipe about 1.5 m long above the fill box. Air tests, or tests with other liquids, can be dangerous and inconclusive.[11]

Federal regulation in the United States

Before stricter rules took effect, the US Environmental Protection Agency (EPA) estimated more than two million UST systems at more than 700,000 facilities. That number has since been greatly reduced by tank removal, and many tanks are retired in place.[1] RCRA Subtitle I, as described by Severson, requires USTs installed after 1988 to meet construction specifications. They must be certified, have overfill protection and detection systems, and be protected against corrosion if made of steel. By 1998, all existing USTs needed corrosion protection for steel tanks and piping and devices to prevent overfilling.[1]

Existing tanks must be tested for leaks on a schedule set by their age. Each UST needs at least one leak monitoring method: automatic tank gauging, soil vapour monitoring, interstitial monitoring between the walls of a double-wall tank, or groundwater monitoring.[22] Hildebrand and Noll describe the aim of Subtitle I as preventing leakage to groundwater and cleaning up past releases. It covers performance standards for new tanks and leak detection, prevention, closure, financial responsibility and corrective action at all underground tank sites.[23] The UST programme is one of four RCRA programmes, next to solid waste, medical waste and hazardous waste.[23]

Section through a buried tank showing automatic tank gauge, soil vapour monitor, interstitial monitor and groundwater monitoring well
Leak monitoring options for underground storage tanks under US federal rules, as described in 2008.

Case: the WTC 7 emergency fuel tanks

The NIST investigation of World Trade Center Building 7 (WTC 7), which collapsed on 11 September 2001, documents two underground tanks in a burning building. The Salomon Brothers fuel system, installed in 1990, drew fuel oil from two 22,700 L (6,000 gal) tanks under the loading dock.[24] It supplied nine 1,750 kW generators on the 5th floor.[24] These tanks were always kept full for emergencies and were full on 11 September 2001.[25]

Both tanks were found damaged and empty in the rubble several months after the collapse. NIST noted that the fuel may have fed a fire on Floor 5, but could not tell this apart from the fuel burning or dispersing in the rubble fire after the collapse.[25] Fire fighters reported no sign of burning liquid fuel before the collapse.[25] NIST concluded that the hypothetical fuel oil fires on the 5th and 6th floors did not contribute to the collapse of WTC 7.[26] An environmental contractor's report on the removal of the tanks, reviewed by NIST, found no residual product in the tanks or their piping.[27] The tanks had stood on a concrete slab over silty sand with a gravel bedding, and the gravel and sand showed some fuel contamination.[27] The soil below also ran under the adjacent base-system tanks, which held 90,850 L (24,000 gal) in total, so NIST judged that a leak from any of the tanks would likely contaminate it.[27]

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 1.4 1.5 1.6 Severson (2008), p. 7-67.
  2. ↑ 2.00 2.01 2.02 2.03 2.04 2.05 2.06 2.07 2.08 2.09 2.10 Ordile (2008), p. 7-23.
  3. ↑ Severson (2008), p. 7-59.
  4. ↑ 4.0 4.1 4.2 4.3 Ordile (2008), p. 7-15.
  5. ↑ 5.0 5.1 5.2 5.3 5.4 5.5 Rivkin (2008a), p. 21-33.
  6. ↑ 6.0 6.1 Ordile (2008), p. 7-25.
  7. ↑ Ordile (2008), p. 7-22.
  8. ↑ Ordile (2008), p. 7-30.
  9. ↑ Ordile (2008), p. 7-16.
  10. ↑ Butcher (2006), p. 2: the widely accepted coefficient of expansion for gasoline is 0.00069 per °F. The 2008 Fire Protection Handbook prints 0.07 percent per 10 °F (Ordile, 2008, p. 7-15), about ten times too low.
  11. ↑ 11.00 11.01 11.02 11.03 11.04 11.05 11.06 11.07 11.08 11.09 11.10 11.11 11.12 Ordile (2008), p. 7-24.
  12. ↑ 12.0 12.1 Rivkin (2008a), p. 21-30.
  13. ↑ 13.0 13.1 13.2 Rivkin (2008a), p. 21-34.
  14. ↑ 14.0 14.1 Gore Willse (2008a), p. 10-16.
  15. ↑ Grill and Johnson (2005a), p. 3.
  16. ↑ Grill and Johnson (2005a), p. 5.
  17. ↑ Grill and Johnson (2005a), p. 6.
  18. ↑ Kandola (2002), pp. 1-4–1-5.
  19. ↑ Titus (2002), p. 4-64.
  20. ↑ Scheffey and Hickey (2002), p. 4-130.
  21. ↑ Ordile (2008), p. 7-18.
  22. ↑ Severson (2008), p. 7-68.
  23. ↑ 23.0 23.1 Hildebrand and Noll (2008), p. 13-83.
  24. ↑ 24.0 24.1 Grill and Johnson (2005a), p. xxxii.
  25. ↑ 25.0 25.1 25.2 McAllister et al. (2008), p. 614.
  26. ↑ McAllister et al. (2008), p. 613.
  27. ↑ 27.0 27.1 27.2 Lew et al. (2005), p. 181.

References

  • Butcher, T. (2006, March). Meter testing and corrections: Corrections during liquid meter testing. National Institute of Standards and Technology. https://www.nist.gov/document/b-015pdf
  • Gore Willse, P. J. (2008a). Heating systems and appliances. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 10-9–10-56). National Fire Protection Association.
  • Grill, R. A., & Johnson, D. A. (2005a). Documentation of the fuel system for emergency power in World Trade Center 7 (NIST NCSTAR 1-1J). National Institute of Standards and Technology.
  • Hildebrand, M. S., & Noll, G. G. (2008). Public fire protection and hazmat management. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 13-81–13-98). National Fire Protection Association.
  • Kandola, B. S. (2002). Introduction to mechanics of fluids. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 1-1–1-26). National Fire Protection Association; Society of Fire Protection Engineers.
  • Lew, H. S., Bukowski, R. W., & Carino, N. J. (2005). Design, construction, and maintenance of structural and life safety systems (NIST NCSTAR 1-1). National Institute of Standards and Technology.
  • McAllister, T. P., Gann, R. G., Averill, J. D., Gross, J. L., Grosshandler, W. L., Lawson, J. R., McGrattan, K. B., Pitts, W. M., Prasad, K. R., Sadek, F. H., & Nelson, H. E. (2008). Structural fire response and probable collapse sequence of World Trade Center Building 7 (NIST NCSTAR 1-9, Vols. 1–2). National Institute of Standards and Technology.
  • Ordile, A. M. (2008). Storage of flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-15–7-33). National Fire Protection Association.
  • Rivkin, C. H. (2008a). Automotive and marine service station operations. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-29–21-40). National Fire Protection Association.
  • Scheffey, J. L., & Hickey, H. E. (2002). Foam system calculations. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 4-123–4-148). National Fire Protection Association; Society of Fire Protection Engineers.
  • Severson, P. R. (2008). Hazardous waste control. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-57–7-69). National Fire Protection Association.
  • Titus, J. J. (2002). Hydraulics. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 4-44–4-71). National Fire Protection Association; Society of Fire Protection Engineers.