An oxygen reduction system is a fire-prevention system that maintains a lower oxygen concentration in a protected enclosure. Introducing a gas such as nitrogen dilutes the oxygen available for combustion. The purpose is to make sustained burning of the materials of concern less likely. The oxygen concentration of the air and the fire behaviour of the fuel are separate parts of the assessment.[1][2][3]

This approach changes conditions before ignition. A gaseous extinguishing system normally discharges an agent in response to a fire and seeks to extinguish it. Although both approaches may use inert gases, they have different operating sequences. Maintaining an atmosphere also raises a separate question about the air available to people entering the enclosure.[3][4][5]

A nitrogen-rich air supply feeds an enclosed space where oxygen concentration is measured.
Dilution changes the atmosphere in the enclosure. Oxygen measurement provides evidence of the conditions at the sensor. Based on Ural and Garzia (2008), §17.8, pp. 17-148–17-150.

Why the fuel matters

For a gas or vapour mixed with air, the limiting oxygen concentration is the oxygen concentration below which a flame cannot propagate under the stated test conditions. Fuel identity and the gas used for dilution affect the result. Values measured for one gas mixture apply to the conditions and endpoint of that test.[2][3]

A list of limits for flammable vapours cannot establish a design concentration for a room containing packaged solid goods. The materials, their arrangement and the fire behaviour being assessed must correspond to the evidence. In particular, preventing sustained flame spread and demonstrating flame extinction in an established fire are different test questions. Smouldering can occur at a solid surface without a flame, so it requires its own evidence.[2][4][6]

Three panels identify the fuel, diluting gas and test endpoint needed to interpret an oxygen limit.
A limiting oxygen concentration has meaning for the fuel, diluent and combustion endpoint used in the test. Based on Zalosh (2002), ch. 3-16, pp. 3-402–3-403.

The role of the enclosure

Inerting uses dilution to bring the oxidant concentration below a level that supports propagation in the mixture being considered. The atmosphere can change if outside air enters. Gas distribution, leakage and the location and response of oxygen instruments therefore matter when judging whether a measurement represents the protected space.[2][3]

A sensor measures the mixture at its own location. A reading in well-mixed air may differ from the concentration near an opening admitting fresh air. This distinction matters when considering protection for stored goods in a warehouse fire scenario. The reading and the fuel-specific evidence answer different parts of the engineering question.[2][3]

Outside air enters through an opening, apart from an oxygen sensor within the enclosure.
A reading at one location may miss differences close to an opening where fresh air enters. Based on Zalosh (2002), ch. 3-16, pp. 3-402–3-403.

Oxygen availability for people

Oxygen depletion can impair the ability to work and, with increasing severity, to function or escape. The physiological response depends on the oxygen available for breathing and on factors including physical exertion. A fuel test measures combustion behaviour. It cannot establish safe conditions of occupancy or entry for an individual.[5][2]

What an assessment documents

An assessment identifies the protected volume, the fuels represented by the evidence, the gas used for dilution and where the oxygen concentration is measured. It also distinguishes the prevention objective from the response if a fire nevertheless occurs. For people who enter the space, the exposure assessment has its own purpose and evidence.[2][3][4][5]

See also

Notes

  1. ↑ Van Rossum (2027), §§4.1–4.2.
  2. ↑ 2.0 2.1 2.2 2.3 2.4 2.5 2.6 Zalosh (2002), ch. 3-16, pp. 3-402–3-403.
  3. ↑ 3.0 3.1 3.2 3.3 3.4 3.5 Ural and Garzia (2008), §17.8, pp. 17-148–17-150.
  4. ↑ 4.0 4.1 4.2 DiNenno (2002), ch. 4-7, pp. 4-173–4-175, 4-184.
  5. ↑ 5.0 5.1 5.2 Purser (2002), ch. 2-6, pp. 2-106–2-107.
  6. ↑ Ohlemiller (2002), ch. 2-9, pp. 2-200–2-201.

References

  • DiNenno, P. J. (2002). Halon replacement clean agent total flooding systems. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed.). National Fire Protection Association.
  • Ohlemiller, T. J. (2002). Smoldering combustion. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed.). National Fire Protection Association.
  • Purser, D. A. (2002). Toxicity assessment of combustion products. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed.). National Fire Protection Association.
  • Ural, E. A., & Garzia, H. W. (2008). Explosion prevention and protection. In A. E. Cote (Ed.), Fire protection handbook (20th ed.). National Fire Protection Association.
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.
  • Zalosh, R. (2002). Explosion protection. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed.). National Fire Protection Association.