A heating equipment fire is a fire started by heat from equipment that heats a building or water, such as a space heater, furnace, boiler, fireplace, chimney or water heater.[1][2] In United States fire statistics the category combines fires coded by the equipment that supplied the heat with small fires confined to a chimney, flue or fuel burner.[3] In 1999–2002 it was the second leading cause of reported structure fires in the United States, with an annual average of 65,000 fires, 340 civilian deaths and 867 million US dollars of direct damage.[3][4] Most of these fires involved portable or other space heaters, and the problem had peaked in the early 1980s after a rapid growth in the use of space heaters and wood stoves.[4][5] Heating equipment starts fires mainly because it runs hotter than the ignition temperature of many common materials, so furniture, bedding, clothing or structural wood that is too close can ignite.[6][1] Fuel handling, venting and chimney cleaning add hazards that differ by fuel, and total deaths and rates per household give different rankings of equipment types.[1][7]

Scope and classification

Heating equipment includes fixed or portable space heaters, chimneys, central heating units, fireplaces and water heaters, and each type has its own rules for installation, maintenance and use.[1] The handbook chapter on heating systems divides the appliances into central heating appliances, room heating appliances and miscellaneous heat-producing devices.[8] A room heater differs from a central furnace because it heats the space around it directly, without pipes or ducts.[9] A second grouping follows the fuel or power: gas, liquid fuel such as fuel oil or kerosene, solid fuel such as wood or coal, and electricity.[10]

In the United States the fire cause is recorded through the National Fire Incident Reporting System (NFIRS). Its field "equipment involved in ignition" names the equipment that provided the heat, whether or not it malfunctioned, and even when it was misused.[2] An upholstered chair that ignites because it stands too close to a space heater is therefore recorded with the heater as the equipment.[2] Version 5.0 of NFIRS records portability in a separate field, so a portable space heater is coded as a heater (code 141) with the box "portable" ticked.[11] Older versions used the categories central heating unit, fixed-area space heater, portable space heater, fireplace, chimney, chimney connector, heat-transfer system and other.[12]

Version 5.0 also allows an abbreviated report for confined fires, such as incident type 114 (chimney or flue fire, confined to the chimney or flue) and type 116 (fuel burner or boiler malfunction, fire confined).[13] A confined structure fire stays within a noncombustible container without flame damage beyond it, and deaths are not an expected result.[14] The NFPA leading-cause tables therefore build the heating category from identified heating equipment, taken from the equipment field, and confined heating fires, taken from the incident type.[3] The same fire can be listed under more than one cause.[3] Analysts infer that confined chimney fires started with creosote, the tarry residue of wood burned with too little air.[15][16]

Tree diagram: heating equipment fires in US homes split into identified heating equipment and two confined fire incident types, with annual fires and deaths
How the heating equipment cause category is built from NFIRS data, with United States home fires, 1999–2002 annual averages.

Size of the problem in the United States

The national fire statistics in the 20th edition of the Fire Protection Handbook (2008) are estimates of fires reported to municipal fire departments.[3] In 1999–2002 heating equipment caused an annual average of 65,000 structure fires (13 % of the total), 340 civilian deaths (11 %), 1,470 injuries and 867 million US dollars of direct damage. The estimates exclude the events of 11 September 2001.[3] Homes accounted for 53,700 of these fires and 320 of the deaths, about 83 % of the fires and 94 % of the deaths.[4] Outside homes, heating equipment caused 10,900 fires a year (8 %) and about 10 deaths.[17] Heating ranked second among the causes of structure fires, behind cooking.[4]

Leading causes of home structure fires in the United States, 1999–2002 annual averages (selected rows; deaths per 1,000 fires calculated)[4]
Cause Fires Civilian deaths Deaths per 1,000 fires
Cooking equipment 105,400 270 2.6
Heating equipment (total) 53,700 320 6.0
– identified heating equipment 40,300 320 7.9
– confined chimney or flue fire 10,600 0 0
– confined fuel burner or boiler fire 2,900 0 0
Intentional 34,400 550 16
Electrical distribution or lighting equipment 32,400 220 6.8
Smoking materials 24,800 850 34
Candle 18,200 160 8.8

In one- and two-family dwellings heating equipment caused 48,900 fires a year (17 %) and 300 deaths (12 %).[18] This made it the second leading cause of fires and the third leading cause of fire deaths in these homes.[1] In apartments heating equipment caused only 5 % of fires.[19] Bush links such differences to the centralised design and installation of building systems and closer equipment supervision in apartment buildings.[19]

The heating fire problem peaked shortly after the rapid growth in the use of portable and other space heaters in the 1970s and early 1980s.[4] Concern about the price and availability of conventional energy drove a surge in wood stoves, furnaces and fireplaces from the mid-1970s, and heating-related home fires rose sharply.[5] Estimates of home fires involving space heaters show wood or coal stove fires and other space heater fires both peaking in 1983 and falling by more than three-quarters by 1998.[16] The decline is attributed to less use of the installed appliances and to better installation, use and maintenance.[5] In 1980 smoking and heating were the two leading causes of home fire deaths, and arson moved past heating into second place in the late 1980s.[20]

Heating fires follow the weather. In 2000–2004, 19 % of home heating equipment fires occurred in January, 17 % in December and 15 % in February, against 2 % in each of June, July and August.[21] December to February together account for 51 % of the year's heating fires. Hall recommends plotting these fires by week, or against daily temperatures, to time public awareness campaigns.[22]

Bar chart of the share of US home heating equipment fires per month, high in December to February and about 2 percent in summer
Share of United States home heating equipment fires by month, 2000–2004 annual averages.

Some groups carry a larger share of the risk. For older adults heating equipment is the second cause of fire deaths after smoking.[23] For people aged 85 and over it is a close second, with nearly 21 % of deaths against 25 % for smoking materials.[23] In the rural South, with its milder winters, people may try to heat whole homes with space heaters designed only for small spaces, and heating fires cause a larger share of deaths there.[24]

How heating equipment starts fires

Combustion needs fuel, oxygen and enough heat, and the ignition temperature is the lowest temperature at which a substance ignites.[25] Heat-producing appliances are among the most frequent causes of fire because they operate above the ignition temperature of many common materials.[6] Their heat reaches nearby objects by conduction, convection and radiation.[26] A heater is therefore an ignition source whose danger depends on its surface temperature, its distance from fuel and the time of exposure.[27]

The most common sequence is simple: a combustible item stands too close to an operating heater. Across all home structure fires in 1999–2002, "heat source too close to combustibles" was the factor contributing to ignition in 12 % of fires.[28] Radiated or conducted heat from operating equipment was the heat source in 27 %, although both shares cover all equipment, not only heaters.[28] Maintaining clearance to combustibles, whether walls and structural members or furniture, bedding and clothing, is a common problem for all portable and area heating equipment.[1] Radiated heat from nearby equipment such as space heaters is one of the dominant ignition sources of upholstered furniture and mattress fires.[29] In 1999–2002 portable heaters were involved in about 300 home upholstered furniture fires a year, which killed 28 people a year.[30]

A slower route is the long-term heating of wood at moderate temperatures. Wood can ignite far below its usual ignition temperature when it is exposed to moderate heat over long periods.[27] The ignition temperature of wood is generally quoted as about 200 °C (392 °F).[31] Documented fires near low-pressure steam pipes suggest that the limit for long-term, low-level heating is not much higher than 100 °C (212 °F).[31] The handbook therefore states that exposed combustibles should not exceed 82 °C (180 °F) under any conditions of operation.[31] Van Rossum gives an approximate ignition-temperature range of 200–500 °C for most materials.[32]

Fuel-burning equipment adds its own hazards: an accumulated combustible mixture, the discharge of unburned fuel and the exposure of fuel to ignition sources.[6] Safe fuelling matters most for liquid-fuelled units, venting for gas-fuelled units, and regular inspection and cleaning for solid-fuelled units.[1] In a solid-fuel heating appliance burned with limited air, tars from the wood deposit as creosote on the stove, connector and chimney.[16] Ignited creosote can feed a fire in parts of the venting system not designed for it, and the fire can spread to the structure.[33]

Electric heating equipment can start fires through electrical failure. In 1994–1998 such fires involved central heating units 1,930 times a year, water heaters 1,280 times, fixed space heaters 1,110 times and portable space heaters 850 times.[34] Together these four types make up about 6 % of the 81,670 electrical-failure fires a year. Failure to turn off devices such as space heaters when they are no longer needed is a typical lapse.[34] Baseboard heaters are tested for contact with curtains and furniture, but other electric air heaters can be hazardous when they touch combustibles or are covered.[35]

Risk by type of equipment

A fair comparison of heater types needs usage data as well as fire data. Fire counts must be divided by the number of units in use, for example of portable electric heaters against wood stoves, to estimate fires per unit per year.[36] Such a comparison of the major types of home heating equipment is possible because each type can be identified in the national databases.[37] Different designs within one type, such as competing portable electric heaters, cannot be distinguished from statistics alone and need tests and models.[37]

Deaths for five leading types of space heater in United States homes (1995–1999 fires, usage in 1997)[7]
Type Fire deaths per million households Fire and unvented carbon monoxide deaths per million households Fire deaths, not adjusted for usage (nearest ten)
Portable, liquid fuel (e.g. kerosene) 9.93–12.41 12.02–15.02 40
Portable, electric 5.95–7.11 5.95–7.11 90
Fixed, gas (e.g. LP-gas) 4.49–5.35 9.70–11.56 60
Fixed, solid fuel (e.g. wood) 3.32–3.91 3.69–4.34 60
Fixed, electric 0.65–1.42 0.65–1.42 10

The three measures give different answers. By fire deaths per million households, portable liquid-fuelled heaters such as kerosene heaters rank first, but by the number of deaths, portable electric heaters come first.[7] The portable liquid-fuelled type moves from first by rate to fourth by total deaths; fixed electric remains last by both measures.[7] The fire death rate for portable liquid-fuelled heaters is roughly 7 to 19 times that for fixed electric heaters. Adding deaths from unvented carbon monoxide moves fixed gas above portable electric by rate, while fixed solid fuel remains below portable electric.[7] With 1985–1990 fire data, portable liquid-fuelled heaters would have ranked second behind fixed gas heaters.[7]

Two-panel chart comparing five space heater types by fire death rate per million households and by total fire deaths, showing different rankings
Five types of space heater in United States homes ranked by fire death rate (1995–1999 fires, 1997 usage) and by number of fire deaths.

Non-fire carbon monoxide deaths from unvented heating equipment are counted separately from fire deaths, and gas-fuelled heating equipment dominates them.[38] For the portable space heater, the choice of measure therefore changes the verdict on fuelled against electric designs.[7] Fixed electric heating ranks lowest on every measure, but it was also one of the least used of the five types.[7]

Calculating loss rates

A simple measure of how dangerous a type of fire is, once it occurs, is the number of deaths per 1,000 reported fires. The handbook uses this rate, for example to show that home fires with automatic suppression had a 77 % lower death rate per 1,000 fires.[18] The rate divides the deaths by the fires in the same population and period. The share of one cause divides its fires by the fires of all causes:

rD=1000DNs=100NcNtot

Symbol Description Unit
rD deaths per 1,000 reported fires deaths per 1,000 fires
D civilian deaths in the fires of the category, per year deaths/year
N reported fires of the category, per year fires/year
s share of one cause in all fires %
Nc fires of one cause, per year fires/year
Ntot fires of all causes, per year fires/year

Worked example: for United States home heating equipment fires in 1999–2002, D = 320 deaths and N = 53,700 fires a year.[4] The rate is 1000 × 320 / 53,700 = 5.96, or about 6.0 deaths per 1,000 fires. Excluding the 13,500 confined chimney and burner fires, which caused no deaths, gives 1000 × 320 / 40,300 = 7.9. The same calculation gives 2.6 for cooking equipment and 34 for smoking materials. A reported heating fire was thus about 2.3 times as deadly as a cooking fire, but about one-sixth as deadly as a smoking-material fire. The 637 million US dollars of damage spread over 53,700 fires gives about 11,900 US dollars per fire, not adjusted for inflation.

Horizontal bar chart of civilian deaths per 1,000 reported home fires by cause in the US, 1999–2002, heating at about 6
Civilian deaths per 1,000 reported home structure fires by cause, United States, 1999–2002 (calculated from annual averages).

Such rates hold only for the population, period and reporting system of the input data. Fires are rounded to the nearest hundred and deaths to the nearest ten, so the rates carry about two significant digits.[3] One unusually serious fire can shift the rate of a small category heavily, such as nonhome heating fires with about 10 deaths a year.[3] Rates per fire also say nothing about how often fires occur. For risk they are combined with fire frequencies, and an expected loss is summed over scenarios as probability times predicted consequence.[37]

Heating fires outside the home

In woodworking plants, fixed or portable space heaters used to supplement building heat introduce ignition sources throughout the facility.[39] The heating plant should be designed to remove any need for them.[39] Small portable space heaters present a much higher fire hazard than engineered central heating, yet employees often use them against local discomfort.[40] Cholin therefore recommends winter inspections that remove the heaters and correct the central heating instead.[40]

Data from a large insurer for 1995–2005 attributed 46 % of construction-related fires to hot work and 14 % to incendiarism or vandalism.[41] Electrical causes made up 8 %, undetermined causes 20 %, and most of the rest were smoking or heating equipment.[41] Incorrectly installed portable or temporary heating equipment is a common hazard of temporary site buildings.[42] In libraries and museums, boilers and furnaces should be isolated in a fire-resistant enclosure, and space heaters kept out of combustible collection storage areas.[43] In board and care facilities, more residents tend to be unaware of the dangers of their actions, including the use of space heaters.[44]

A case from a United States nuclear power plant shows how the power supply of a portable heater can become the ignition source. On 19 December 2001 at Fort Calhoun Station, a 2,000 W drum heater used to warm grease was left on overnight on two 15 A extension cords.[45] Its 20 A plug had been modified to fit, and the heater drew 17.39 A, about 16 % above the rating of the cords.[45] The cords overheated and ignited a plastic step-off pad and a rubber air hose. The smoke then set off a deluge system in another area, which sprayed safety-related motor control centres.[46]

Prevention and regulation

In the United States, the 20th edition of the Fire Protection Handbook (2008) summarises several installation standards. NFPA 211 covers chimneys, fireplaces, vents and solid fuel-burning appliances.[1] NFPA 54, the National Fuel Gas Code, covers gas appliances, NFPA 90B covers warm air heating in dwellings, and NFPA 70 covers electric heating.[47][48] Listed appliances are tested by laboratories, and the clearances found in these tests appear in the listing and the installation instructions.[27] Basic principles apply to all heat-producing devices: clearance to combustibles, venting, enough air for combustion, proper burner and safety controls, and safe handling of fuel.[33]

The same chapter states that fuel-burning room heaters are not to be installed in sleeping quarters for transients, as in hotels and motels, or in institutions such as homes for the aged.[9] Where heaters are permitted in sleeping quarters, direct-vent appliances are considered good practice.[9] Of the leading causes of home fire deaths, heating involves the behaviours that are easiest to change through education.[20] Hall suggests educational material at the places where space heaters are sold, serviced or maintained.[49]

The 2013 New Zealand Building Code commentary reproduces clause C2.2 as a surface temperature limit. It limits the surface temperature of combustible building materials close to fixed appliances using controlled combustion and other fixed equipment to 90 °C at the design operating level.[50] The 2013 commentary explains that wood heated for long periods can change chemically and ignite at lower temperatures, and that recommended limits for long exposure range from 66 °C to 110 °C.[51] The International Fire Engineering Guidelines (2005) list heating appliances among the ignition sources to review when the hazards of a building are identified for a fire engineering brief.[52]

Limits of the statistics

The handbook data are national estimates of fires reported to United States municipal fire departments. They exclude fires reported only to federal or state agencies or to industrial fire brigades, and the damage is not adjusted for inflation.[3] They describe one country in 1999–2002, and the handbook stresses that local differences in the fire problem need to be identified, even within the United States.[53] Rankings can also change between data periods, as the comparison of space heater types shows.[7]

Coding practice adds uncertainty. In 2002 about 20 % of confined fire reports contained more than the basic data.[14] A review by the United States Fire Administration found that fires with damage beyond their container had also been coded as confined.[14] Native NFIRS version 5.0 data made up 7 % of reports in 1999 and 82 % in 2003, and the conversion from older versions is not one-to-one.[13] Older versions did not separate natural gas from LP-gas, fuel oil from kerosene, or wood from coal, and chimney fires had to be assigned to wood stoves or fireplaces by estimation rules.[10]

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 Lathrop (2008b), p. 20-58.
  2. ↑ 2.0 2.1 2.2 Ahrens and Stewart (2008), p. 3-49.
  3. ↑ 3.0 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 Hall and Cote (2008), p. 3-14.
  4. ↑ 4.0 4.1 4.2 4.3 4.4 4.5 4.6 Hall and Cote (2008), p. 3-15.
  5. ↑ 5.0 5.1 5.2 Gore Willse (2008a), p. 10-11.
  6. ↑ 6.0 6.1 6.2 Gore Willse (2008a), p. 10-9.
  7. ↑ 7.0 7.1 7.2 7.3 7.4 7.5 7.6 7.7 7.8 Hall (2008), p. 5-106.
  8. ↑ Gore Willse (2008a), p. 10-19.
  9. ↑ 9.0 9.1 9.2 Gore Willse (2008a), p. 10-23.
  10. ↑ 10.0 10.1 Hall and Ahrens (2002), p. 5-73.
  11. ↑ Ahrens and Stewart (2008), p. 3-53.
  12. ↑ Hall and Ahrens (2002), p. 5-72.
  13. ↑ 13.0 13.1 Ahrens et al. (2008), p. 3-67.
  14. ↑ 14.0 14.1 14.2 Ahrens et al. (2008), p. 3-66.
  15. ↑ Ahrens et al. (2008), p. 3-73.
  16. ↑ 16.0 16.1 16.2 Gore Willse (2008a), p. 10-24.
  17. ↑ Hall and Cote (2008), p. 3-16.
  18. ↑ 18.0 18.1 Lathrop (2008b), p. 20-57.
  19. ↑ 19.0 19.1 Bush (2008), p. 20-38.
  20. ↑ 20.0 20.1 Hall (2008), p. 5-108.
  21. ↑ Hall (2008), p. 5-113.
  22. ↑ Hall (2008), p. 5-112.
  23. ↑ 23.0 23.1 Gamache (2008), p. 5-67.
  24. ↑ Gamache (2008), p. 5-72.
  25. ↑ Van Rossum (2027), §4.2.
  26. ↑ Van Rossum (2027), §5.1.
  27. ↑ 27.0 27.1 27.2 Gore Willse (2008a), p. 10-28.
  28. ↑ 28.0 28.1 Ahrens et al. (2008), p. 3-72.
  29. ↑ Babrauskas (2008b), p. 6-103.
  30. ↑ Babrauskas (2008b), p. 6-109.
  31. ↑ 31.0 31.1 31.2 Gore Willse (2008a), p. 10-31.
  32. ↑ Van Rossum (2027), §9.3 (Results from zone models).
  33. ↑ 33.0 33.1 Gore Willse (2008a), p. 10-25.
  34. ↑ 34.0 34.1 Milatovich (2008), p. 8-136.
  35. ↑ Milatovich (2008), p. 8-153.
  36. ↑ Hall and Ahrens (2002), p. 5-65.
  37. ↑ 37.0 37.1 37.2 Hall (2002b), p. 5-146.
  38. ↑ Hall and Twomey (2008), p. 1-23.
  39. ↑ 39.0 39.1 Cholin (2008d), p. 9-15.
  40. ↑ 40.0 40.1 Cholin (2008d), p. 9-17.
  41. ↑ 41.0 41.1 Davis (2008a), p. 11-47.
  42. ↑ Davis (2008a), p. 11-48.
  43. ↑ McDaniel (2008), p. 20-185.
  44. ↑ Jose (2008), p. 20-19.
  45. ↑ 45.0 45.1 Iqbal and Salley (2004), p. H-32.
  46. ↑ Iqbal and Salley (2004), p. H-33.
  47. ↑ Gore Willse (2008a), p. 10-17.
  48. ↑ Gore Willse (2008a), p. 10-21.
  49. ↑ Hall (2008), p. 5-114.
  50. ↑ Ministry of Business, Innovation and Employment (2013), p. 14.
  51. ↑ Ministry of Business, Innovation and Employment (2013), p. 15.
  52. ↑ National Research Council of Canada et al. (2005), p. 1.2-9.
  53. ↑ Hall (2008), p. 5-107.

References

  • Ahrens, M., Frazier, P., & Kelch, G. (2008). Use of fire incident data and statistics. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-61–3-92). National Fire Protection Association.
  • Ahrens, M., & Stewart, S. (2008). Fire data collection and databases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-43–3-59). National Fire Protection Association.
  • Babrauskas, V. (2008b). Upholstered furniture and mattresses. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-103–6-128). National Fire Protection Association.
  • Bush, K. (2008). Apartment buildings. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-37–20-47). National Fire Protection Association.
  • Cholin, J. M. (2008d). Woodworking facilities and processes. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-3–9-25). National Fire Protection Association.
  • Davis, R. J. (2008a). Fire hazards of construction, alteration, and demolition of buildings. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-47–11-58). National Fire Protection Association.
  • Gamache, S. (2008). Reaching high-risk groups. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 5-63–5-85). National Fire Protection Association.
  • Gore Willse, P. J. (2008a). Heating systems and appliances. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 10-9–10-56). National Fire Protection Association.
  • Hall, J. R., Jr. (2002b). Product fire risk. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 5-143–5-152). National Fire Protection Association; Society of Fire Protection Engineers.
  • Hall, J. R., Jr. (2008). Using data for public education planning and decision making. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 5-103–5-118). National Fire Protection Association.
  • Hall, J. R., Jr., & Ahrens, M. J. (2002). Data for engineering analysis. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 5-65–5-78). National Fire Protection Association; Society of Fire Protection Engineers.
  • Hall, J. R., Jr., & Cote, A. E. (2008). An overview of the fire problem and fire protection. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-3–3-30). National Fire Protection Association.
  • Hall, J. R., Jr., & Twomey, E. R. (2008). Challenges to safety in the built environment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 1-3–1-29). National Fire Protection Association.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Jose, P. R. (2008). Board and care facilities. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-15–20-21). National Fire Protection Association.
  • Lathrop, J. K. (2008b). One- and two-family dwellings. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-55–20-61). National Fire Protection Association.
  • McDaniel, D. L. (2008). Library and museum collections. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 20-179–20-202). National Fire Protection Association.
  • Milatovich, R. M. (2008). Electrical systems and appliances. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-127–8-173). National Fire Protection Association.