A compressed gas cylinder is a portable pressure vessel, built to transport regulations, in which a gas is shipped, stored and used under pressure. In North America, cylinders are made to the specifications of the US Department of Transportation (DOT) or Transport Canada (TC), and their water capacity is limited to 454 kg (1000 lb).[1][2] A cylinder may hold a compressed gas, which stays entirely gaseous, a liquefied gas under its own vapour pressure, or a gas dissolved in a liquid, as with acetylene.[3][4] The upper charging pressure of compressed gas cylinders is usually in the range of 12.4–24.8 MPa (1800–3600 psi).[3] When a cylinder fails, the cylinder or its pieces can fly as missiles, and the handbook notes that this missile hazard is more characteristic of compressed gas cylinders than the effects of the gas release.[5] Fire exposure raises the pressure and weakens the metal at the same time, so cylinders carry relief devices, must be kept away from fires and are handled with care.[3]

Definition and types

In North America there are two types of gas containers: cylinders and tanks. Originally, cylinders were the smaller, portable, high-pressure containers, while tanks were larger and stationary. These distinctions have faded, and today the only real difference lies in the regulations or codes under which the container is built.[1] Cylinders are fabricated to DOT regulations in the United States and to TC regulations in Canada, and the requirements are the same in both countries. Tanks are built to Section VIII of the ASME Boiler and Pressure Vessel Code or to standards of the American Petroleum Institute.[2] Before 1 April 1967, the US rules were issued by the Interstate Commerce Commission, and some cylinders with ICC markings remain in service.[2]

The gas inside defines the second classification. NFPA 55, the US standard for compressed gases and cryogenic fluids, defines a compressed gas by its state at 20 °C and 101.325 kPa absolute. Gases without other health or physical hazards count as compressed gases only above 280 kPa absolute (40.6 psia) at 20 °C.[3] A glossary in a US nuclear regulatory guide gives a similar threshold: an absolute pressure above 276 kPa (40 psia) at 21.1 °C, or above 717 kPa (104 psia) at 54.4 °C.[6] In the physical sense used by the handbook, a compressed gas exists only in the gaseous state in its container at all normal temperatures. A liquefied gas is partly liquid and partly gas at 20 °C, and it remains under pressure as long as liquid is present.[3]

The difference matters for capacity. The largest common portable cylinder of compressed oxygen holds only about 9 kg (20 lb), or about 6.9 m³ (245 ft³) of gas at normal temperature and pressure. As an illustration, the same volume could hold about 53 kg (116 lb) of liquefied oxygen, roughly six times more.[3] Very cold liquefied gases, described under cryogenic fluids, are kept in insulated containers instead.[7] Under US transport rules, many liquefied gases are themselves classified as compressed gases.[8]

Acetylene is a special case. Its cylinders are filled with a porous mass saturated with acetone or dimethylformamide, in which the gas dissolves. The small pores limit the energy available for decomposition of the gas.[4] DOT and TC regulations recognised a maximum charging pressure of 1724 kPa at 21 °C (250 psig at 70 °F), and the pressure changes by about 31 kPa per °C (2.5 psi per °F) of temperature change.[4]

Construction, marking and requalification

The DOT regulations cover the service pressure for which a cylinder is designed, the gases it may contain, its safety devices, and testing and requalification in service. The specifications cover metal composition, physical testing, wall thickness, joining methods, openings, heat treatment, proof testing and marking.[2] For breathing-air cylinders of self-contained breathing apparatus (SCBA), the US federal rules sit in 49 CFR 178, Subpart C. Steel cylinders of manganese steel carry the marking DOT3A, and chrome alloy steel cylinders carry DOT3AA followed by the service pressure.[9]

Labelled cutaway of a steel gas cylinder with valve, protective cap, relief device and stamped markings
Main parts and markings of a steel compressed gas cylinder under US DOT rules.

Cylinders were historically made of metal, but DOT has approved composite cylinders of fibreglass construction. In 2008 they were available in sizes for gas grills and propane-powered forklift trucks. They had been used for propane in Scandinavia since the early 1990s.[2] They are lighter than steel cylinders and translucent, so the liquid level can be seen, but they cost more.[2]

For SCBA, the 49 CFR specifications do not cover composite cylinders, which DOT authorises through exemptions. Most exemptions limit their life to 15 years from the original hydrostatic test date.[9] SCBA cylinders rated at 15.3 MPa (2216 psi) gave a rated service time of 30 minutes, cylinders at 24.1 MPa (3500 psi) 45 minutes, and cylinders at 31.0 MPa (4500 psi) 60 minutes.[10]

Requalification is a periodic retest of the cylinder. As described in the 2008 handbook, DOT containers must be requalified at intervals set in the federal regulations, mostly every five years. Depending on the retest method, the interval can be as long as twelve years.[11] For SCBA, DOT specified requalification every 3 years for composite cylinders and every 5 years for all-metal cylinders.[9]

A requalified container is marked with the date. If a compressed gas cylinder has no such marking and was made more than five years ago, the handbook advises telling whoever last filled it. The owner, who is often not the user, is responsible for requalification.[11] The DOT and TC rules themselves apply only to interstate or interprovincial transport, but consensus codes extend them to storage and use at consumer sites.[7]

Pressure, temperature and stored energy

A compressed gas follows the classic gas laws closely enough for practical work. Boyle's law states that volume varies inversely with absolute pressure at constant temperature. Charles's law states that volume is proportional to absolute temperature at constant pressure.[3] Combined, they relate the state of a fixed mass of gas before and after a change:[5]

P1V1T1=P2V2T2

Symbol Description Unit
P1,P2 Absolute pressure before and after the change (gauge pressure plus 101 kPa) kPa
V1,V2 Volume before and after the change m³
T1,T2 Absolute temperature before and after the change (°C + 273) K

Pressures and temperatures must be absolute values, and the units must be consistent.[3] In a closed cylinder the volume is fixed, so the absolute pressure rises in direct proportion to the absolute temperature. The handbook's own example heats a 10 ft³ cylinder at 1000 psig from 70 °F to 150 °F, which raises the gauge pressure to 1155.3 psig.[5]

Worked example 1. A medical H or K cylinder has a nominal volume of 43.6 L and is filled with air to 2200 psig at 21.1 °C (70 °F).[12] The absolute pressure is 15.17 MPa + 0.10 MPa = 15.27 MPa. If the cylinder warms to 60 °C, the pressure becomes 15.27 × 333/294 = 17.29 MPa absolute, a rise of about 13 percent. This is the temperature range, 54–60 °C (130–140 °F), at which the handbook states that relief devices on fully charged containers will generally operate.[13] Heating to 200 °C, which a fire easily produces, would raise the pressure by about 61 percent.

Straight line of cylinder pressure against temperature from 14 to 25 MPa, with a shaded band at 54 to 60 degrees Celsius
Absolute pressure in an H or K cylinder of air charged to 2200 psig at 21.1 °C as it is heated.

When a cylinder bursts, its gas expands to atmospheric pressure in roughly the time a crack needs to split the shell, of the order of 10 µs. The peak pressure is about equal to the vessel pressure at the moment of bursting.[14] The handbook gives the isentropic expansion energy for an ideal gas as:[14]

Eburst=(Pb−Pa)Vγ−1

Symbol Description Unit
Eburst Isentropic expansion energy released by the burst J
Pb Vessel pressure at the time of bursting (absolute) Pa
Pa Pressure of the ambient air, 101 kPa at sea level Pa
V Vessel volume m³
γ Ratio of specific heats of the gas (1.4 for air) –

The SFPE Handbook gives the same perfect-gas expression for the blast wave from a ruptured vessel whose gas is not ignited.[15] One kilogram of TNT has an explosive energy of 4.2 MJ, which allows a comparison with high explosives.[14] If the vessel fails because of an internal combustion explosion, the analysis is more complicated, because combustion adds energy to the blast wave.[15]

Worked example 2. For the H or K air cylinder of example 1 at 21.1 °C, the pressure difference is 15.17 MPa and the volume is 0.0436 m³. The burst energy is then 15.17 × 106 × 0.0436 / 0.4 = 1.65 MJ, about the energy of 0.39 kg of TNT. If the cylinder bursts at 60 °C, the energy rises to about 1.87 MJ. A small E cylinder of 4.80 L filled with air to 1900 psig stores about 0.16 MJ.[12] The results show why a cylinder that fails can propel its fragments, or the whole cylinder, over long distances.

Two straight lines of burst energy against cylinder pressure for a 43.6 litre and a 4.8 litre air cylinder
Isentropic burst energy of air cylinders of 43.6 L and 4.80 L as a function of gauge pressure.

Overpressure relief devices

In the United States, Canada and other countries, most compressed and liquefied gas containers carry spring-loaded pressure relief valves, bursting discs, or both. Fusible plugs are sometimes used on smaller containers.[5] The start-to-discharge pressure of a pressure relief device follows from the strength of the container. Its relieving capacity is usually based on the maximum heat input from fire exposure, the largest heat source normally expected.[16]

The handbook lists the usual devices per gas. Compressed oxygen cylinders use frangible discs, alone or with fusible plugs. Compressed hydrogen cylinders also use frangible discs, sometimes with fusible plugs, and ethylene cylinders use frangible discs.[17][18] Carbon dioxide cylinders, stored at about 5861 kPa at 21 °C (850 psi at 70 °F), have frangible discs.[19]

Some cylinders have no relief device by design. Containers of certain poisonous and highly toxic gases omit them, because a leaking or early-operating device is judged more dangerous than container failure; a lower filling limit gives the safety margin instead.[16] In the same way, anhydrous ammonia containers of less than 75 kg (165 lb) need no overpressure protection.[20] Chlorine cylinders have fusible plugs, which empty the cylinder completely when they operate.[19]

A relief device cannot always prevent failure on its own, but it extends the time to failure in all cases. It can also prevent failure under many fire exposure conditions.[11] It must not be blocked by corrosion or paint, or damaged, so portable containers should be checked whenever they arrive, are connected or are filled. Spring-loaded relief valves on larger stationary containers should be tested every five to ten years.[11] Inspection, maintenance and replacement of relief devices were described in 2008 as essentially unregulated.[16]

Behaviour in fire

A cylinder of a nonliquefied gas cannot suffer a BLEVE, the explosive failure of a container of liquid heated above its boiling point. Such a cylinder can still fail explosively from fire exposure.[21] The handbook gives this distinction for hydrogen and ethylene cylinders, which can fail in a fire but contain no liquid.[18] Cylinders of liquefied gases, such as LP-gas, are subject to BLEVEs. Corrosion can also cause one: carbon dioxide cylinders have failed in this way with enough energy to nearly demolish small cargo vehicles.[19]

In a fire, a relief device that opens on a flammable gas releases fuel, which can ignite as a jet fire. A flame jet that impinges on adjacent containers can make their relief devices operate as well.[22] Sprinklers have greatly reduced the number of relief devices that operate on cylinders in a fire, and therefore the number of cylinders that fail from contact with burning discharged gas.[23][4] For this purpose, sprinkler spacing and water density must be tailored to the hazard.[4]

Acetylene cylinders need special care. Their fusible-metal plugs melt at about 100 °C (212 °F), and the gas decomposes into carbon and hydrogen above about 300 °C (570 °F).[24] Decomposition can be so fast that the plugs cannot prevent rupture, which may happen from a few minutes to several hours after exposure. Cylinders exposed to fire have exploded as long as 24 hours later.[24] A small leak that ignites can heat the fusible metal and produce a torch-like flame up to 3.6 m (12 ft) long.[24] Most acetylene cylinders in Europe and elsewhere had no relief devices in 2008, which made them more susceptible to rupture.[24]

Composite cylinders fail differently from steel and aluminium ones. In room-fire tests, propane composite cylinders did not explode or BLEVE but released their contents over about 15 minutes after several minutes of fire exposure.[2] The handbook described their indoor use as controversial and still under review for NFPA 58.[2]

Storage and handling

In the United States, NFPA 55 (2005 edition), as summarised in the 2008 handbook, sets maximum allowable quantities (MAQs) of gas per control area. A control area is a space, or a whole building, separated from exposures by a fire barrier. Above the MAQ, additional fire protection measures apply.[21] The selection below is copied from Table 7.3.1; the full table also covers liquefied gases and other classes.[25]

Selected MAQs per control area for nonliquefied gases, NFPA 55 (2005), as given by Lemoff and Rivkin (2008), Table 7.3.1
Gas class Unsprinklered, no gas cabinet Unsprinklered, gas cabinet Sprinklered, no gas cabinet Sprinklered, gas cabinet
Flammable gas 1000 ft³ 2000 ft³ 2000 ft³ 4000 ft³
Oxidising gas 43 m³ (1500 ft³) 85 m³ (3000 ft³) 85 m³ (3000 ft³) 170 m³ (6000 ft³)
Toxic gas 23 m³ (810 ft³) 46 m³ (1620 ft³) 46 m³ (1620 ft³) 92 m³ (3240 ft³)
Highly toxic gas 0 m³ 0.6 m³ (20 ft³) 0 m³ 1.1 m³ (40 ft³)
Nonflammable gas No limit No limit No limit No limit

The flammable gas row is given in cubic feet, because the printed metric values do not match the imperial ones; 1000 ft³ is about 28 m³ and 4000 ft³ about 113 m³. For flammable, oxidising and toxic gases, either sprinklers or a gas cabinet doubles the MAQ, and both together quadruple it.[25] Each value is the aggregate quantity in storage and use combined.[25]

NFPA 55 also requires separation of cylinders by hazard class. Flammable, oxidising, toxic, corrosive, pyrophoric and unstable reactive gases are kept 6.1 m (20 ft) apart, while gases classed as other gas need no separation. The distance can be reduced without limit by a noncombustible barrier at least 1.5 m (5 ft) high with a fire resistance of at least half an hour.[21] Flammable gases should not be stored with oxidising gases such as oxygen and nitrous oxide, which speed up burning and can form explosive mixtures.[21] Combustibles near the cylinders should be limited, and except for one or two cylinders, storage rooms should be of noncombustible or limited-combustible construction.[21]

Plan view of cylinder groups by hazard class separated by 6.1 metre distances or a fire-rated barrier
Separation of gas cylinders by hazard class under NFPA 55 as shown in the 2008 handbook.

Indoor storage areas must be ventilated whatever the gas, because even inert gases can asphyxiate in closed spaces. NFPA 55, as described in the handbook, requires at least 0.3 m³/min per m² of floor area (1 cfm/ft²). Exhaust must discharge at least 15 m (50 ft) from air intakes.[13] Storage temperatures should stay below 54–60 °C, and outdoor cylinders exposed to the sun should keep reflective paint.[13] Indoor storage of a small number of cylinders, up to 71 standard m³ (2500 SCF), does not require sprinklers.[11] Liquefied gas cylinders should generally be stored upright, so that the relief device stays in the vapour space.[11]

Handling is part of the safety design. Any dent or gouge can reduce the safety factor and shorten failure times in a fire. If the valve of a small cylinder is broken off, the reaction of the escaping gas can propel the cylinder violently, so valve caps or collars should always be in place during storage and movement.[11] In hospitals, cylinders that fall over can complicate evacuation, and a knocked-off valve can turn a cylinder into a "high speed torpedo".[26] Many hospitals therefore pipe gases from remote sources in a medical gas system, and manifolds of cylinders supply nitrous oxide, carbon dioxide and nitrogen.[26][27]

Valves of oxidising gas cylinders should be opened slowly to prevent heating by adiabatic compression. Aluminium regulators have ignited in such service, and brass regulators are recommended instead.[28] Transfilling from one cylinder to another is hazardous and should be done only by qualified personnel.[29]

Limits and common misconceptions

A common assumption is that a gas cylinder is safe in a fire because it has a relief device. The handbook states that relief devices extend the time to failure but cannot always prevent it, and that container metal loses strength when heated.[11] A second misconception is that only liquefied gas containers explode. Compressed gas cylinders cannot BLEVE, yet they can still fail explosively, and their failures are marked mainly by flying fragments.[21][5]

A third point concerns the contents of a cylinder. Gas mixtures can form inside containers by mistake, for example where oxygen and a fuel gas are used together, and combustion inside a container can then cause overpressure failure. Consumers of industrial and medical gases seldom have the expertise to fill containers safely.[30]

The burst-energy equation assumes an ideal gas and isentropic expansion. It ignores combustion of a flammable gas and the separate effects of fragments, which need other methods.[15] Finally, the rules in this article are US and Canadian rules as summarised in the 2008 handbook. Other countries have similar but not identical regulations, and some, especially in Europe, follow different relief device practices.[1][16]

See also

Notes

  1. ↑ 1.0 1.1 1.2 Lemoff and Rivkin (2008), p. 7-35.
  2. ↑ 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 Lemoff and Rivkin (2008), p. 7-36.
  3. ↑ 3.0 3.1 3.2 3.3 3.4 3.5 3.6 3.7 Lemoff (2008), p. 6-168.
  4. ↑ 4.0 4.1 4.2 4.3 4.4 Lemoff (2008), p. 6-177.
  5. ↑ 5.0 5.1 5.2 5.3 5.4 Lemoff (2008), p. 6-169.
  6. ↑ Iqbal and Salley (2004), p. F-16.
  7. ↑ 7.0 7.1 Lemoff and Rivkin (2008), p. 7-37.
  8. ↑ Lemoff (2008), p. 6-167.
  9. ↑ 9.0 9.1 9.2 Teele (2008), p. 12-152.
  10. ↑ Teele (2008), p. 12-151.
  11. ↑ 11.0 11.1 11.2 11.3 11.4 11.5 11.6 11.7 Lemoff and Rivkin (2008), p. 7-40.
  12. ↑ 12.0 12.1 Allen (2008), p. 6-190.
  13. ↑ 13.0 13.1 13.2 Lemoff and Rivkin (2008), p. 7-41.
  14. ↑ 14.0 14.1 14.2 Zalosh (2008), p. 2-94.
  15. ↑ 15.0 15.1 15.2 Zalosh (2002), p. 3-419.
  16. ↑ 16.0 16.1 16.2 16.3 Lemoff (2008), p. 6-170.
  17. ↑ Lemoff (2008), p. 6-185.
  18. ↑ 18.0 18.1 Lemoff (2008), p. 6-181.
  19. ↑ 19.0 19.1 19.2 Lemoff (2008), p. 6-180.
  20. ↑ Lemoff (2008), p. 6-179.
  21. ↑ 21.0 21.1 21.2 21.3 21.4 21.5 Lemoff and Rivkin (2008), p. 7-38.
  22. ↑ Rivkin (2008b), p. 21-58.
  23. ↑ Lemoff (2008), p. 6-176.
  24. ↑ 24.0 24.1 24.2 24.3 Lemoff (2008), p. 6-178.
  25. ↑ 25.0 25.1 25.2 Lemoff and Rivkin (2008), p. 7-39.
  26. ↑ 26.0 26.1 Allen (2008), p. 6-188.
  27. ↑ Allen (2008), p. 6-189.
  28. ↑ Allen (2008), p. 6-194.
  29. ↑ Allen (2008), p. 6-192.
  30. ↑ Lemoff (2008), p. 6-173.

References

  • Allen, M. (2008). Medical gases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-187–6-196). National Fire Protection Association.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Lemoff, T. C. (2008). Gases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-165–6-186). National Fire Protection Association.
  • Lemoff, T. C., & Rivkin, C. H. (2008). Storage of gases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-35–7-42). National Fire Protection Association.
  • Rivkin, C. H. (2008b). Vehicle fueling using gaseous fuels. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-41–21-76). National Fire Protection Association.
  • Teele, B. W. (2008). Fire and emergency services protective clothing and protective equipment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 12-143–12-160). National Fire Protection Association.
  • Zalosh, R. (2002). Explosion protection. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-402–3-421). National Fire Protection Association; Society of Fire Protection Engineers.
  • Zalosh, R. (2008). Explosions. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-93–2-106). National Fire Protection Association.