Minimum water that must evaporate in the flame to cool a 750 kW fire, for spray heat absorption ratios of 0.3 and 0.6, compared with the flow of a single water mist nozzle. Based on Mawhinney and Back (2002), pp. 4-313, 4-327 and 4-329, and Tewarson (2002), p. 3-100.
Original vector illustration for Water mist system, level 2 Intermediate.
- Source basis: Mawhinney and Back (2002), pp. 4-313, 4-327, 4-329; Tewarson (2002), p. 3-100
- Alt text: Bars of 5.3 and 10.5 l/min evaporated water for a 750 kW fire at SHAR 0.3 and 0.6, beside a band of 5 to 80 l/min per nozzle.