Fse-warehouse-fire-v1.svg (SVG file, nominally 900 × 600 pixels, file size: 13 KB)
Summary
Design fires of New Zealand's C/VM2 (2025): storage 3.0 to 5.0 m high (ultra-fast, peak 50 MW) and most other buildings (peak 20 MW). Based on Ministry of Business, Innovation and Employment (2025b), p. 20.
Original vector illustration for Warehouse fire, level 2 Intermediate.
- Source basis: Ministry of Business, Innovation and Employment (2025b), p. 20 (Table 2.3.2.1); Australian Building Codes Board (2020a), Data Sheet B2, p. 3 (Equation B2.1)
- Alt text: Line chart: storage fire grows as 0.188 t squared to 50 MW at 516 s; general fire as 0.0469 t squared to 20 MW at 653 s.
Licensing
New drawing by Fire Safety Academy. © Fire Safety Academy.
File history
Click on a date/time to view the file as it appeared at that time.
| Date/Time | Thumbnail | Dimensions | User | Comment | |
|---|---|---|---|---|---|
| current | 17:45, 2 November 2026 | 900 × 600 (13 KB) | Lisa (talk | contribs) | Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity |