Contents
Fse-sprinkler-vent-interaction-v2.svg (SVG file, nominally 900 × 600 pixels, file size: 11 KB)
Summary
Relative mass flow through a roof vent as a function of the ratio of absolute layer and ambient temperature, with the layer at 100 K and, after spray cooling, 20 K above 293 K. Based on Cooper (2002b), pp. 3-223 to 3-224.
Original illustration for Sprinkler-vent interaction, level 4 Expert.
- Source basis: Cooper (2002b), p. 3-223 (Eq. 19) and p. 3-224 (maximum at T_lay = 2 T_amb; within 80 percent above 1.3; Figure 3-9.3: redraw, do not copy)
- Alt text: Curve of relative vent mass flow against layer to ambient temperature ratio, peaking at 2; points mark 100 K and 20 K above ambient.
Licensing
New drawing by Fire Safety Academy. © Fire Safety Academy.
File history
Click on a date/time to view the file as it appeared at that time.
| Date/Time | Thumbnail | Dimensions | User | Comment | |
|---|---|---|---|---|---|
| current | 17:32, 2 November 2026 | 900 × 600 (11 KB) | Jan (talk | contribs) | Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity |