Contents
Fse-sprinkler-skipping-v2.svg (SVG file, nominally 900 × 600 pixels, file size: 20 KB)
Summary
Calculated temperature of a standard response sprinkler link in a 1,000 kW fire, without droplets and with liquid volume fractions of 1 and 2 millionths in the ceiling jet. Based on Iqbal and Salley (2004), pp. 10-15 to 10-18, and McGrattan et al. (2026), p. 107.
Original illustration for Sprinkler skipping, level 4 Expert.
- Source basis: Iqbal and Salley (2004), pp. 10-15 to 10-18 (Example 10.10-1 and its spreadsheet values); McGrattan et al. (2026), p. 107 (link equation with droplet cooling term)
- Alt text: Line chart: link temperature rising towards 88 °C; it reaches 74 °C at 174 s without droplets, 234 s and 361 s with droplets.
Licensing
New drawing by Fire Safety Academy. © Fire Safety Academy.
File history
Click on a date/time to view the file as it appeared at that time.
| Date/Time | Thumbnail | Dimensions | User | Comment | |
|---|---|---|---|---|---|
| current | 17:32, 2 November 2026 | 900 × 600 (20 KB) | Jan (talk | contribs) | Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity |