Contents
Fse-spill-fire-v2.svg (SVG file, nominally 1,180 × 850 pixels, file size: 9 KB)
Summary
For the tested JP jet fuels, flame spread changed from liquid control at about 1–12 cm/s to gas-phase spread at 130–220 cm/s near 18 °C above the closed-cup flash point.
Original illustration for Spill fire.
- Alt text: Semi-log plot of flame spread rate against liquid temperature minus flash point, low band 1 to 12 cm/s, high band 130 to 220 cm/s, jump near plus 18 degrees C.
Licensing
New drawing by Fire Safety Academy. © Fire Safety Academy.
File history
Click on a date/time to view the file as it appeared at that time.
| Date/Time | Thumbnail | Dimensions | User | Comment | |
|---|---|---|---|---|---|
| current | 08:06, 8 November 2026 | 1,180 × 850 (9 KB) | Lisa (talk | contribs) | Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity | |
| 07:41, 8 November 2026 | 1,180 × 760 (9 KB) | Lisa (talk | contribs) | Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity |
You cannot overwrite this file.
File usage
The following page uses this file: