Davoodi's example: flames about 5.2 m high above a burning section, tilted 45° by the wind, radiate about 66 kW/m²; with a view factor of about 0.3 the wood roof beyond a 0.9 m parapet receives about 20 kW/m², above the 12.5 kW/m² for pilot ignition.
Original illustration for Roof covering fire test.
- Alt text: Section through a one-storey building split by a fire wall with a parapet; flames tilted 45 degrees over the parapet radiate onto the neighbouring wood roof.
Licensing
New drawing by Fire Safety Academy. © Fire Safety Academy.