Skip to content
From Fire Safety Academy Wiki
Contents
  1. 1Summary
  2. 2Licensing

Fse-roof-covering-fire-test-v4.svg (SVG file, nominally 1,600 × 1,020 pixels, file size: 12 KB)

Summary

Davoodi's example: flames about 5.2 m high above a burning section, tilted 45° by the wind, radiate about 66 kW/m²; with a view factor of about 0.3 the wood roof beyond a 0.9 m parapet receives about 20 kW/m², above the 12.5 kW/m² for pilot ignition.

Original illustration for Roof covering fire test.

  • Alt text: Section through a one-storey building split by a fire wall with a parapet; flames tilted 45 degrees over the parapet radiate onto the neighbouring wood roof.

Licensing

New drawing by Fire Safety Academy. © Fire Safety Academy.

File history

Click on a date/time to view the file as it appeared at that time.

Date/TimeThumbnailDimensionsUserComment
current08:17, 8 November 2026Thumbnail for version as of 08:17, 8 November 20261,600 × 1,020 (12 KB)Lisa (talk | contribs)Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity

The following page uses this file:

Metadata