Fse-response-time-index-v2.svg (SVG file, nominally 900 × 600 pixels, file size: 11 KB)

Summary

Illustrative RTI responses to a constant 150 °C gas stream. Based on Schifiliti et al. (2002), p. 4-6, Equations 11–15; article calculation.

Original illustration for Response time index, level 3 Advanced.

  • Source basis: Schifiliti et al. (2002), p. 4-6, Equations 11–15; article calculation.
  • Alt text: Three exponential temperature curves cross 68 °C after about 11.5, 23.0 and 46.1 seconds.
  • Accuracy notes: The time origin is arrival of the constant exposure; no transport, conduction or water-delivery delay is included. End each curve at its stated operating threshold, avoiding an implication about post-activation element temperatures.

Licensing

New drawing by Fire Safety Academy. © Fire Safety Academy.

File history

Click on a date/time to view the file as it appeared at that time.

Date/TimeThumbnailDimensionsUserComment
current16:42, 2 November 2026Thumbnail for version as of 16:42, 2 November 2026900 × 600 (11 KB)Emma (talk | contribs)Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity