Contents
Fse-reduced-cross-section-method-v3.svg (SVG file, nominally 900 × 600 pixels, file size: 14 KB)
Summary
Remaining section modulus of a 130 mm × 533 mm glued-laminated beam heated on three sides, with a charring rate of 0.7 mm/min, with and without the zero-strength layer. Based on White (2002), pp. 4-261, 4-266 to 4-268.
Original illustration for Reduced cross-section method, level 4 Expert.
- Source basis: White (2002), pp. 4-261, 4-266, 4-267 and 4-268; calculation by Fire Safety Academy
- Alt text: Line chart of remaining section modulus of a 130 by 533 mm glulam beam over 60 minutes, with and without the zero-strength layer, crossing 50 % near 31 minutes.
Licensing
New drawing by Fire Safety Academy. © Fire Safety Academy.
File history
Click on a date/time to view the file as it appeared at that time.
| Date/Time | Thumbnail | Dimensions | User | Comment | |
|---|---|---|---|---|---|
| current | 17:26, 2 November 2026 | 900 × 600 (14 KB) | Jan (talk | contribs) | Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity |