Fse-nfpa-30-v3.svg (SVG file, nominally 960 × 700 pixels, file size: 16 KB)
Summary
Required emergency venting as free air against wetted area, with the worked example (54.3 m², about 11,000 m³/h).
Original illustration for NFPA 30.
- Alt text: Log-log chart of required emergency venting rate against wetted tank area from 1 to 5,000 m², with the worked example marked