Contents
Fse-line-plume-v2.svg (SVG file, nominally 900 × 600 pixels, file size: 8 KB)
Summary
Smoke from a 5 MW fire spills from under a 3 m balcony and rises as a line plume; the calculation uses an imaginary line source 1.7 m below the balcony edge. Based on Cooper (2002b), pp. 3-231 to 3-232.
Original illustration for Line plume, level 4 Expert.
- Source basis: Cooper (2002b), p. 3-231 (example 5 set-up: 5 MW, 4 m², balcony width 3 m, height 3 m, 65 % convective) and p. 3-232 (Figure 3-9.12, redraw, do not copy; 12.0 kg/s, 722 kW/m, source 1.7 m below the balcony, 7.6 kg/(m·s), 34.2 kg/s)
- Alt text: Cross-section: a fire plume hits the underside of a balcony, flows to its edge and rises as a line plume from an imaginary source 1.7 m below the edge.
Licensing
New drawing by Fire Safety Academy. © Fire Safety Academy.
File history
Click on a date/time to view the file as it appeared at that time.
| Date/Time | Thumbnail | Dimensions | User | Comment | |
|---|---|---|---|---|---|
| current | 17:14, 2 November 2026 | 900 × 600 (8 KB) | Jan (talk | contribs) | Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity |