Skip to content
From Fire Safety Academy Wiki
Contents
  1. 1Summary
  2. 2Licensing

Fse-gaseous-extinguishing-system-v4.svg (SVG file, nominally 900 × 600 pixels, file size: 9 KB)

Summary

Exposure time limits for inert gas agents, with the corresponding residual oxygen concentration. Based on DiNenno (2002), p. 4-184.

Original vector illustration for Gaseous extinguishing system, level 2 Intermediate.

  • Source basis: DiNenno (2002), p. 4-184 (exposure limits) and p. 4-189 (IG-541 minimum design concentration)
  • Alt text: Step chart of allowed exposure time against inert gas concentration: 5 min up to 43 %, 3 min from 43 to 52 %, 30 s above 52 %.

Licensing

New drawing by Fire Safety Academy. © Fire Safety Academy.

File history

Click on a date/time to view the file as it appeared at that time.

Date/TimeThumbnailDimensionsUserComment
current17:25, 2 November 2026Thumbnail for version as of 17:25, 2 November 2026900 × 600 (9 KB)Lisa (talk | contribs)Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity

The following page uses this file:

Metadata