Skip to content
From Fire Safety Academy Wiki
Contents
  1. 1Summary
  2. 2Licensing

Fse-froude-scaling-v3.svg (SVG file, nominally 900 × 600 pixels, file size: 7 KB)

Summary

Critical velocity to stop smoke backflow in a corridor at full scale and in a 1/4 scale model, from Thomas's relation. Based on Klote (2002), pp. 4-279–4-280.

Original illustration for Froude scaling, level 4 Expert.

  • Source basis: Klote (2002), p. 4-279 (Equations 4 and 4a) and p. 4-280 (wastebasket example); Milke (2002b), p. 4-294 (scaling relations)
  • Alt text: Two corridors in side view: full scale 1.22 m wide with 150 kW fire and 1.45 m/s airflow; model 0.31 m wide, 4.7 kW, 0.73 m/s.

Licensing

New drawing by Fire Safety Academy. © Fire Safety Academy.

File history

Click on a date/time to view the file as it appeared at that time.

Date/TimeThumbnailDimensionsUserComment
current17:36, 2 November 2026Thumbnail for version as of 17:36, 2 November 2026900 × 600 (7 KB)Jan (talk | contribs)Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity

The following page uses this file:

Metadata