Contents
Fse-froude-scaling-v1.svg (SVG file, nominally 900 × 600 pixels, file size: 9 KB)
Summary
A 30.5 m atrium and its 1/8 scale model. Heat release rate and fan flow shrink with the length ratio to the power 5/2, time with its square root; temperatures stay the same. Based on Milke (2002b), pp. 4-294–4-295.
Original illustration for Froude scaling, level 4 Expert.
- Source basis: Milke (2002b), p. 4-294 (scaling relations, Eqs. 1–7) and p. 4-295 (Example 1 and Figure 4-13.2, small-scale model of atrium: redraw, do not copy)
- Alt text: A tall atrium with a 5 MW fire next to a model one eighth its height with a 28 kW fire, with the scaled values listed.
Licensing
New drawing by Fire Safety Academy. © Fire Safety Academy.
File history
Click on a date/time to view the file as it appeared at that time.
| Date/Time | Thumbnail | Dimensions | User | Comment | |
|---|---|---|---|---|---|
| current | 17:36, 2 November 2026 | 900 × 600 (9 KB) | Jan (talk | contribs) | Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity |
You cannot overwrite this file.
File usage
The following page uses this file: